37
Bentone
Photocell current checks
Photocell current is measured with a direct current ammeter
(mulitimeter μA) connected in series with the photocell.
9.1.3 Technical data
LOA24
Pre-ignition period:
13 s
Pre-ventilation period:
13 s
Post-ignition period:
15 s
Safety period:
< 10 s
Re-connection after release:
< 50 s
Reaction time flame extinction:
< 1 s
Ambient temperature:
–20 - +60°C
Min. current with flame:
65 µA
Max current when dark, start:
5 µA