9.1.1 List of components
A1
Oil burner control
S3
Operations thermostat
E1
Preheater
S4
Temperature limiter
F1
Fuse, max 10 A
S7
Main switch
H1
Alarm lamp
T1
Ignition transformer
M1
Burner motor
Y1
Solenoid valve
P1
Timer (Accessory)
X1
Plug-in contact, burner
R1
Photocell QRB
X2
Plug-in contact, boiler
U2
UV-Detector QRC
Preheater wiring colours:
A Blue
B Brown
C Black
The installation must be connected to the mains and fused according to local
regulations.
9.1.2 Function LOA1..2..4..
1a.
Operations switch ON, thermostat ON
The burner motor starts, ignition sparks initiated and pre-ventilation
continues until the set pre-ventilation period is over and the solenoid
valve (2) opens.
1b.
Operations switch ON, thermostat ON
The preheater is energized and the pre-heating period begins.
This continues until the operating temperature is reached and the
preheater thermostat closes. The burner motor starts, ignition
sparks initiated and pre-ventilation continues until the set pre-
ventilation period is over and the solenoid valve (2) opens.
2.
Solenoid valve opens
The oil mist is formed and ignited. The photocell indicates flame.
The ignition spark ceases 15 sec. after flame indication.
3.
a
b
Safety period runs out
If the flame is not present before the end of this period, the oil burner
control blocks further operation.
If the flame for any reason disappears after this time period, the
burner will make a new start attempt.
4-5
During operation
If burner operations are interrupted via the main switch or
thermostat, a new start will be initiated when conditions according
to point 1 are fulfilled.
Oil burner control blocks
Red light on the oil burner control illuminates. The burner is re-
started by pressing the reset button.