Ø
If SILENCE is activated during NIGHT Mode it will be held for the program-
med time (see "Silence" paragraph).
Auto
Another of the FireClass100 features is the Automatic Alarm Threshold variation.
Sensors are particularly sensitive, therefore, when persons are present in
the protected ambient the Alarm Threshold must be increased by the
non-
modifiable default value
(to allow for cigarette smoke etc.). The Alarm
Threshold of the Analogue Sensors can be controlled automatically.
DAY Mode
If the Analogue Sensors are programmed with the
T
and/or
S
option - the
Alarm Threshold of the Analogue Sensors will be increased by 10% during
the programmed times.
NIGHT Mode
The non-modifiable default value will be restored.
Drift Compensation
When Drift Compensation is programmed for an Analogue Sensor (valid for
Analogue smoke ionisation sensors only) it will supply a precise analysis, and
therefore, indicate whether the Sensor is at risk of generating false alarms.
Drift Compensation is automatic. In the event of Drift Compensation
FAULT, the User need only identify the FAULT type and the Sensor gene-
rating the FAULT.
There are two types of Drift Compensation FAULT: automatic which corre-
sponds to the non-modifiable threshold, and the Threshold programmed by
the Installer (modifiable).
The threshold programmed by the Installer offers a faster way of detecting
the high dust level of an ambient.
Maintenance request
The FireClass100 control panel can be programmed to request maintenan-
ce. The Maintenance request will be signalled on the programmed date by
FAULT status.
To change the Maintenance request date:
Ø
use the Installer PIN to access the
PROGRAMMING
phase, and postpone
the request.
+
The FC200/COM Telecom Module ---- when installed and properly pro-
grammed will call the programmed telephone numbers.