the Device type (S = Sensor or M = Module);
Ø
the Device address (01 through 99 or ZC = Conventional Zone).
If the first ALARM was generated by a Software Zone it will show:
Ø
the Zone address (Z01 through Z16).
Last Alarm
As per the First Alarm but for the most recent Alarm.
Total Alarms
The total number of Alarms since the last RESET.
Up/Down move
Use the
↑
or
↓
key to scroll the alarm
identifiers
.
Press the
ESC
key to access the logger and view the most recent event
(see "Logger" paragraph).
During an ALARM status the User can SILENCE or RESET the system,
and also view the logger.
MORE ALARMS
The MORE ALARMS LED will go ON to signal the presence of several
alarm conditions.
Software Zones
Input Points and Output Points can be associated to the 16 Sotftware Zo-
nes of the FireClass100. ALARM status on an Input Point will generate the
same status on its Software Zones.
Positive Alarm Sequence (PAS)
A Software Zone (enabled for the
Fixed Delay
) will go into ALARM status
when the
Fixed Delay
ends.
Press
ACK
to extend a running
Fixed Delay
- the
PAS Delay
(when ena-
bled) will be added automatically to the
Fixed Delay
.
The Software Zone will go into ALARM status when the delay time ends.
Ø
Fixed Delay
will be signalled by blinking on the Zone LED (1 sec. ON - 0.5
sec. OFF), and by an intermittent sound on the buzzer (1 sec. sound - 0.5
sec. pause);
Ø
PAS Delay
will be signalled by blinking on the Zone LED (2 sec. ON - 2
sec. OFF), and by an intermittent sound from the buzzer (2 sec. sound - 2
sec. pause)
+
A Output Point can also be associated to Input Points; in this case the Out-
put Point will be activated when at least one of its Input Points goes into
ALARM status.
USER GUIDE
15