(section B)
(j) Repeat steps 3.2 c,e,f.
----------- O R ----------
3 >15s
Burner ignition...
4 <20s
Burner ignition cycle complete
Warning
If burner ignition is not satisfactorily accomplished,
commissioning must not proceed until the reason or fault has
been identifi ed and rectifi ed, if necessary by reference to the
separate burner information or to section 6 of this manual.
(k) Repeat steps 3.2 c,a,
(l) Repeat steps 3.2 d,e,f, allowing the heater to reach thermal
equilibrium.
(m) Adjust room thermostat to its highest setting, and allow
the heater to continue to fi re.
(n) Gradually reduce the temperature setting on the room
thermostat until the burner shuts down, (@ < ambient and
then gradually increase the temperature setting on the
thermostat until heat is called for, (@ > ambient) and the
burner automatically re-fi res.
(o) Re-set time clock to a minimum off period, checking that
the burner shuts down, and then automatically re-lights once
the minimum off period has elapsed (Separate information on
the time clock is contained within the information package
supplied with the heater).
(p) Check limit stat by tripping the fan motor overload re-set
by pressing the reset button on the overload, located on the
heater electrical panel. The time between the fan stopping
and burner shut down should be noted (90 seconds max),
once the burner has shut down the overload on the motor
should be released.
(q) Undertake fl ue gas analysis using approved and calibrated
analysing equipment recording data on the commissioning
card, ie, CO, CO2, net and gross fl ue temperatures.
Record burner oil pump pressure, ambient temperature,
barometric pressure, and smoke reading (0 - 1 Baccarach
scale).
Note (i)
The burner air and oil pressure settings should be only very
fi nely adjusted to achieve a CO2 reading of 12.5% (+/- 0.5%).
Note (ii)
The gross effi
ciency must be approximately 80% sample
taken at 1m above the fl ue spigot point.
Note (iii)
All unit Heaters are test fi red and pre-commissioned as part of
the manufacturing process, if however, during on site
commissioning the data are found to be not in accordance
with the manufacturers data, then the following action is
recommended.
* Re-check all readings and calculations.
* Adjust burner as per manufacturers instructions.
* Consult the Technical Department, details on rear page.
(r) Complete commissioning card and provide operating
instructions for the user, high-light the fact that the
manufacturer recommends that in the interests of safety and
effi
ciency the heater is serviced on a regular basis only by
qualifi ed and competent persons.
The completed commissioning card must be returned to the
supplier (details on rear page) immediately after the
satisfactory completion of commissioning, failure to do so can
invalidate any subsequent warranty claim.
(s) Set all controls to the requirements of the user.
(t) Final adjustment for the direction of the air fl ow from the
heater should be made.
3.3
Commissioning - air delivery system
Final adjustment of the air louvres are adjusted outwards and
ensure blades are not resonating.
Caution
On ducted applications it is necessary that the system is
balanced in order to optimise the effi
ciency of the heater and
the air distribution and delivery system Failure to balance the
system can result in fan motor overloading and premature
component failure, it can also result in an ineffi
cient heating/
ventilation system.
(a) Check that the amount of fan produced air volume is in
accordance with the heater specifi cation, if the volume is too
great the fan can be overloaded. Ensure that the running
current is as per that stated on the heater data plate.
Alternatively, the static pressure should be measured at the
start of the ductwork to confi rm that it is within the
permissible tolerance.
(b) If the current drawn is greater than the stated running
current, in most probability this will be caused by insuffi
cient
static pressure within the ductwork, in which case system
resistance should be increased through the introduction of a
damper placed as close to the start of the ductwork as
possible, thereby resulting in a reduction in drawn current.
The damper should be adjusted until the current is in
accordance with that stated on the data plate.
Summary of Contents for OUH 2 100
Page 20: ...Wiring Diagram 33 65 245 Models OUHA OUHC40 ON OFF Riello Oil Fried Burner...
Page 21: ...Wiring Diagram 33 65 246 Models OUHA 60 70 ON OFF Riello Oil Fried Burner...
Page 22: ...Wiring Diagram 73 65 010 Models OUHA 90 100 ON OFF Riello Oil Fried Burner...
Page 23: ...Wiring Diagram 33 65 247 Models OUHC 60 100 ON OFF Riello Oil Fried Burner...
Page 24: ...Wiring Diagram 33 65 248 Models OUHA OUHC 40 HI LOW Riello Oil Fried Burner...
Page 25: ...Wiring Diagram 33 65 249 Models OUHA 60 70 HI LOW Riello Oil Fried Burner...
Page 26: ...Wiring Diagram 73 65 011 Models OUHA 90 100 HI LOW Riello Oil Fried Burner...
Page 27: ...Wiring Diagram 33 65 250 Models OUHC 60 100 HI LOW Riello Oil Fried Burner...
Page 35: ...Turbulator positions in models 40 70 8 off Turbulator positions in models 90 100 12 off...
Page 43: ...Notes...