background image

 Alternatively, the static pressure should be 
measured at the start of the ductwork to 
confirm that it is within the permissible 
tolerance. 
(b) If the current drawn is greater than the 
stated  running current, in most probability this 
will be caused by insufficient static pressure 
within the ductwork, in which case system 
resistance should be increased through the 
introduction of a damper placed as close to the 
start of the ductwork as possible, thereby 
resulting in a reduction in drawn current. 
The damper should be adjusted until the 
current is in accordance with that stated on the 
data plate. 
 
(c) If the current drawn is too low the duct 
outlet grilles will require opening to reduce 
static pressure and increase air volume, if this 
is not the case overheat cut outs can be 
caused. 

 

4.4 Commissioning - hand over  

 

(a) Upon full and satisfactory completion of 
commissioning, a record of commissioning 
information    
 (contact, date, etc) should be left with the 
heater, a copy of which must also be 
forwarded to Benson  Heating Service 
Department. 
 
(b) The commissioning engineer must ensure 
that the user is familiar with the safe and 
efficient use of the heater, detailing the 
function of all controls, and main components. 
 
(c) The user should be made aware of the 
following in particular 
 
 (i) Lighting, shutdown, and operational 
information. 
 (ii) Safety features, data plate, and labelling. 
 (iii) The requirement for regular inspection - 
especially if the heater is within a more 
demanding environment - and the need for 
regular servicing carried out by competent and 
qualified persons. 
 

Caution 

After approximately 100 hours of running, the 
tension of the fan belts must be checked to 
ensure that they are correct and that they have 
not stretched. See section 5.2 for further 
instructions. 

 

5.0 Servicing  

 

Warning

  

Servicing must be carried out on a regular 
basis, the maximum interval between services 
being 1 year. It is a requirement that only 
suitably qualified and competent persons are 
allowed to undertake servicing. 
 

Before any maintenance or servicing work 
is carried out the heater must be shut down 
and allowed to cool, and have the oil and 
electric supplies to it turned off at the 
supply valve and isolator respectively. 

 

Caution  

Certain component parts are factory sealed 
and are designed so as to be tamper proof. 
Usually such items do not require servicing, 
and therefore should not be tampered with. 
 Failure to comply with this can invalidate any 
warranty, and can also lead to premature 
failure.  
The following parts fall within this category: 
thermostat, fan and motor. 
 
Additionally, the fan and limit stat has been 
factory set, and must not be re-set without 
formal consent from the manufacturer. 
 
Reference should be made to the separate 
information covering the operational details of 
the burner . 

 
Only approved spare/replacement parts can 
be fitted, failure to comply with this can 
compromise the safe and efficient running 
of the heater, and can also invalidate any 
warranty claim. 
 

5.1 Planned Servicing  

 

In order to maintain the efficient operation of 
the heater it is recommended that the following 
planned servicing and preventative 

Summary of Contents for MH300

Page 1: ...BENSON MH300 OIL FIRED MARQUEE HEATER I N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S...

Page 2: ......

Page 3: ...work Fittings 8 2 7 Oil installation and Connection 8 2 8 Electrical Supply 8 2 9 Air Supply 9 2 10 Air Distribution 10 2 11 Flue System 11 3 0 Installation 11 3 1 Electrical installation Connection...

Page 4: ...on Heating to ensure that they are familiar with the appropriate information manuals supplied by the manufacturer and that they are suitably aware of the purpose of the manuals and the safety instruct...

Page 5: ...Warning Unauthorised modifications to the appliance or departure from the manufacturers guidance on intended use or installation contrary to the manufacturers recommendations may constitute a hazard N...

Page 6: ...n to enable processing to take place 1 Heater model 2 Heater serial number 3 Order reference date of order together with full installation details name and address 4 Details or symptoms of fault Fault...

Page 7: ...ll below the cold filter plugging point cfpp in this country and with class D fuel also referred to as gas oil The critical temperature is 4oC for this summer grade The cfpp critical temperature for t...

Page 8: ...let and towards the sludge drain valve which must be sited at the lowest point in the tank If the tank is positioned on supports then there must be an adequate protective layer between tank and suppor...

Page 9: ...space being heated And The building design air change rate is less than 0 5 air changes per hour and the volume of the space is greater than 4 7m3 per kilowatt then low level ventilation is required...

Page 10: ...06m3 h per kW of rated heat input Mechanical ventilation systems where fitted must be provided with safety interlocks to prevent heater operation in case of air flow failure 2 9 3 Ventilation Openings...

Page 11: ...stant to internal and external corrosion and be capable of withstanding the stresses and loadings associated with normal use 3 0 Installation 3 1 Electrical Installation Connection Benson MH 300 cabin...

Page 12: ...rs undergo a rigorous test programme prior to being dispatched whilst such a programme does involve pre commissioning and setting up the heater to operate efficiently and well within its designed oper...

Page 13: ...position for heater on off switch f Check for the following burner sequence Interval Operand 1 5s Combustion air damper actuated burner fan motor initiates purge cycle 2 15s Solenoid valve opens ignit...

Page 14: ...settings should be only very finely adjusted to achieve a CO2 reading of 12 5 0 5 Note ii The gross efficiency must be approximately 80 Note iii All Heaters are test fired and pre commissioned as par...

Page 15: ...ding environment and the need for regular servicing carried out by competent and qualified persons Caution After approximately 100 hours of running the tension of the fan belts must be checked to ensu...

Page 16: ...Fan Motor Remove access panel Dust and other foreign matter should be cleaned by blowing over with compressed air and through the use of a soft bristle brush and cloth Solvent wipes may be used to re...

Page 17: ...ne belt contains more slack than its accompanying belts then all the belts on the unit must be replaced again using a common batch code Replacement and tensioning is carried out as follows Note The ma...

Page 18: ...ecked to ensure that they are secure and free from corrosion Terminals and connections should also be checked to ensure that no stray strands are bridging terminals Electrical continuity should also b...

Page 19: ...out Occurs Fuel Feed Incorrect Check that the Oil Pressure is correct Check that Head of Gravity is Sufficient Check that the suction Lift is not too great two pipe system Check that the Bypass Plug i...

Page 20: ...Line Check Fuel Pressure Check Nozzle Check Filter Check Fuel Lines Check Valves Burner gives a smokey flame Poor Combustion Insufficient Combustion Air Inadequate Flue Draught Check Oil Pressure Che...

Page 21: ...ockout Warm Air Short Circuit Adjust Warm Air Discharge and Cool Air Inlet Accordingly Check for High Resistance Check Outlet Grilles are not shut or Check Filter is Clear Insufficient Air Flow over t...

Page 22: ...Wiring Diagram 20 49 146...

Page 23: ...tic pressure full load pa 750 Discharge velocity full load M s 19 5 Noise level full load Dba 1 m 90 Heat Input part load kW 225 Heat output part load kW 180 Nett efficiency part load 90 5 Gross effic...

Page 24: ...nnection size Bsp 1 4 Fuel specification 35 sec Head setting 5 Air shutter Hi Lo 70 28 Electrical supply V Hz Ph 415 50 3 Fuse Size Amps 6 Maximum running current Amps 16 Flue diameter mm 225 Overheat...

Page 25: ...magnetic Compatibility BS EN 50165 1995 Safety of Electrical Equipment BS 5854 1980 Code of Practice Flues Flue Structures BS 799 Part 5 1987 Oil Burning Equipment oil tanks OFTEC OFS T 100 Polyethyle...

Page 26: ...Benson Heating Ludlow Road Knighton Powys LD7 1LP Telephone 44 0 1547 528534 Facsimile 44 0 1547 520399 Email information bensonheating co uk www bensonheating com...

Reviews: