background image

In ducted applications the ductwork must be 
designed so as to give a static pressure within the 
limits stated in section 8 of this manual.  
It should be noted that if the static pressure is too 
high, nuisance shut-down will occur when the 
heater goes out on the overheat limit thermostat, if 
the static pressure is too low, then damage can be 
caused to the fan motor. 
 
Warm air outlets on ducted applications must be 
such that they cannot be closed or become 
blocked, which again would lead to an increase in 
static pressure and nuisance shut-down. 
 The outlets must not be sited so that warm air can 
be discharged onto combustible materials, if 
necessary, guard rails should be used to ensure 
that effected areas are kept clear. 
 Return air intakes must not be located so that 
potentially harmful or hazardous contaminated air 
can be drawn into the system. 
 

2.11 Flue system  

 
Warning  

 
Each heater must have its own separate flue, with a 
flue diameter of not less than 

225mm

 The minimum 

vertical length of flue must not be less than 1m.  
The flue should rise vertically, and the number of 
bends should be kept to a minimum.  
It is strongly advised that BS 5854; 1980, and BS 
5440; parts 1 and 2, are used as consultative 
documents when considering flue requirements. 
 
Care should be taken to ensure that the flue 
terminal is not situated in a high-pressure area, the 
proximity of buildings and other obstacles which will 
influence this must be taken into account, 
preferably at the design stage.  
 
Provision must be made for the disconnection of the 
flue for inspection and service requirements, and it 
is strongly advised that where bends are fitted 
inspection covers are included. 
 
The materials from which the flue is constructed 
must be non-combustible, resistant to internal and 
external corrosion, and be capable of withstanding 
the stresses and loadings associated with normal 
use.

 

3.0 Installation 
 
3.1 Electrical Installation/Connection  

 

Benson MH 300 cabinet heaters are 
415V 50Hz 3PH NEUTRAL & EARTH  
It is recommended that reference is made to the 
wiring diagrams contained within section 7 of this 
manual prior to installation or connection to the 
supply. 
The electrical supply must be as specified and 
suitable for the heater, and must be run within 
conduit to a point adjacent to the heater, and be 
terminated to provide an isolation point that will 
prevent remote or inadvertent activation.  
Cables, conduit, and fittings that are used to make 
the connection between the isolator and the heater 
must conform to the appropriate IEE regulations. All 
heaters are supplied fused and pre-wired, all must 
be earthed. 
 Final connections for any additional external 
controls must be completed on site, and must be 
carried out according to IEE regulations. 
Separate user information is provided for the time 
control unit and the burner, and forms part of the 
product information pack which accompanies every 
heater when dispatched.

 

 

Warning  

Always isolate from mains electrical supply before 
commencing work on the heater. 
 

Always ensure that the appropriate personal 
protective equipment is used. 

 

3.2 Air Distribution Installation 

  

The materials selected must be of low heat 
capacity, and it is preferable that all warm air 
ductwork is thermally insulated.  
Where ducting may be subject to deterioration from 
exposure to moisture or high humidity material 
selection and insulation are prime considerations. 
Joints and seams must be airtight and fastened 
securely and designed to remain so, even when 
operating at high temperatures. 
 Adequate support must be designed into the layout 
of the ductwork to ensure that the integrity of the 
seams and joints is maintained. 
 The support must be independent and separate 

Summary of Contents for MH300

Page 1: ...BENSON MH300 OIL FIRED MARQUEE HEATER I N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S...

Page 2: ......

Page 3: ...work Fittings 8 2 7 Oil installation and Connection 8 2 8 Electrical Supply 8 2 9 Air Supply 9 2 10 Air Distribution 10 2 11 Flue System 11 3 0 Installation 11 3 1 Electrical installation Connection...

Page 4: ...on Heating to ensure that they are familiar with the appropriate information manuals supplied by the manufacturer and that they are suitably aware of the purpose of the manuals and the safety instruct...

Page 5: ...Warning Unauthorised modifications to the appliance or departure from the manufacturers guidance on intended use or installation contrary to the manufacturers recommendations may constitute a hazard N...

Page 6: ...n to enable processing to take place 1 Heater model 2 Heater serial number 3 Order reference date of order together with full installation details name and address 4 Details or symptoms of fault Fault...

Page 7: ...ll below the cold filter plugging point cfpp in this country and with class D fuel also referred to as gas oil The critical temperature is 4oC for this summer grade The cfpp critical temperature for t...

Page 8: ...let and towards the sludge drain valve which must be sited at the lowest point in the tank If the tank is positioned on supports then there must be an adequate protective layer between tank and suppor...

Page 9: ...space being heated And The building design air change rate is less than 0 5 air changes per hour and the volume of the space is greater than 4 7m3 per kilowatt then low level ventilation is required...

Page 10: ...06m3 h per kW of rated heat input Mechanical ventilation systems where fitted must be provided with safety interlocks to prevent heater operation in case of air flow failure 2 9 3 Ventilation Openings...

Page 11: ...stant to internal and external corrosion and be capable of withstanding the stresses and loadings associated with normal use 3 0 Installation 3 1 Electrical Installation Connection Benson MH 300 cabin...

Page 12: ...rs undergo a rigorous test programme prior to being dispatched whilst such a programme does involve pre commissioning and setting up the heater to operate efficiently and well within its designed oper...

Page 13: ...position for heater on off switch f Check for the following burner sequence Interval Operand 1 5s Combustion air damper actuated burner fan motor initiates purge cycle 2 15s Solenoid valve opens ignit...

Page 14: ...settings should be only very finely adjusted to achieve a CO2 reading of 12 5 0 5 Note ii The gross efficiency must be approximately 80 Note iii All Heaters are test fired and pre commissioned as par...

Page 15: ...ding environment and the need for regular servicing carried out by competent and qualified persons Caution After approximately 100 hours of running the tension of the fan belts must be checked to ensu...

Page 16: ...Fan Motor Remove access panel Dust and other foreign matter should be cleaned by blowing over with compressed air and through the use of a soft bristle brush and cloth Solvent wipes may be used to re...

Page 17: ...ne belt contains more slack than its accompanying belts then all the belts on the unit must be replaced again using a common batch code Replacement and tensioning is carried out as follows Note The ma...

Page 18: ...ecked to ensure that they are secure and free from corrosion Terminals and connections should also be checked to ensure that no stray strands are bridging terminals Electrical continuity should also b...

Page 19: ...out Occurs Fuel Feed Incorrect Check that the Oil Pressure is correct Check that Head of Gravity is Sufficient Check that the suction Lift is not too great two pipe system Check that the Bypass Plug i...

Page 20: ...Line Check Fuel Pressure Check Nozzle Check Filter Check Fuel Lines Check Valves Burner gives a smokey flame Poor Combustion Insufficient Combustion Air Inadequate Flue Draught Check Oil Pressure Che...

Page 21: ...ockout Warm Air Short Circuit Adjust Warm Air Discharge and Cool Air Inlet Accordingly Check for High Resistance Check Outlet Grilles are not shut or Check Filter is Clear Insufficient Air Flow over t...

Page 22: ...Wiring Diagram 20 49 146...

Page 23: ...tic pressure full load pa 750 Discharge velocity full load M s 19 5 Noise level full load Dba 1 m 90 Heat Input part load kW 225 Heat output part load kW 180 Nett efficiency part load 90 5 Gross effic...

Page 24: ...nnection size Bsp 1 4 Fuel specification 35 sec Head setting 5 Air shutter Hi Lo 70 28 Electrical supply V Hz Ph 415 50 3 Fuse Size Amps 6 Maximum running current Amps 16 Flue diameter mm 225 Overheat...

Page 25: ...magnetic Compatibility BS EN 50165 1995 Safety of Electrical Equipment BS 5854 1980 Code of Practice Flues Flue Structures BS 799 Part 5 1987 Oil Burning Equipment oil tanks OFTEC OFS T 100 Polyethyle...

Page 26: ...Benson Heating Ludlow Road Knighton Powys LD7 1LP Telephone 44 0 1547 528534 Facsimile 44 0 1547 520399 Email information bensonheating co uk www bensonheating com...

Reviews: