BENNING IT 130 

short instructions 

 

- 8 - 

 

1.4  Indications and meaning of symbols 

Terminal voltage monitor 

 

The terminal voltage monitor displays on-line the voltages on the test terminals and information about 

active test terminals in the AC installation measuring mode. 

 

 

The voltage applied is displayed by means of the testing terminal symbol. All three 

testing terminals L, N and PE are used for the selected measurement. 

 

The voltage applied is displayed by means of the testing terminal symbol. The 

testing terminals L and N are used for the selected measurement. 

 

The testing terminals L and PE are active testing terminals. The testing terminal N 

should be connected as well in order to have a correct input voltage. 

 

The polarity of the testing voltage applied (R LOW, R ISO) is displayed at the 

output terminals L and N. 

 

 

Battery indication 

 

 

Battery capacity indication. 

 

Low battery. 

The storage battery charge condition is too low to ensure correct measuring results. 

Recharge the storage batteries or replace the batteries. 

 

Charging in progress (if power supply adapter is connected). 

 

 

Messages 

 

 

Measurement is running, consider displayed warnings. 

 

Conditions on the input terminals allow starting the measurement; consider other 

displayed warnings and messages. 

DC VOLTAGE!  Warning!

 Too high DC voltage (> 50 V DC) applied to the testing terminals! 

 

Conditions on the input terminals do not allow starting the measurement, consider 

displayed warnings and messages. 

 

RCD tripped-out during the measurement (in RCD functions). 

 

Portable RCD selected (PRCD). 

 

Instrument is overheated. The measurement is prohibited until the temperature 

decreases under the allowed limit. 

 

RCD of type EV (Electric Vehicle) 

 

RCD of type MI (Mobile Installation) 

 

Result(s) can be stored.  

 

High electrical noise was detected during measurement. Results may be impaired. 

 

L and N are changed. 

Summary of Contents for 044103

Page 1: ...Installation Tester BENNING IT 130 Short instructions GB Detailed instruction manual on enclosed CD Rom...

Page 2: ...o KG M nsterstra e 135 137 D 46397 Bocholt Phone 49 0 2871 93 0 Fax 49 0 2871 93 429 www benning de duspol benning de 05 2020 BENNING This document must not be reproduced or used in any other form wit...

Page 3: ...and fuses 11 1 10 Calibration and Service 12 1 11 Optional accessories 13 2 Measurements 14 2 1 Null balance compensation of the test cables 14 2 2 TRMS voltage V AC DC frequency and phase sequence r...

Page 4: ...inspection and repair Do not use the instrument in AC supply systems with voltages higher than 550 V AC Service repairs or adjustment of instruments and accessories is only allowed to be carried out b...

Page 5: ...isconnect all test cables accessories from the tester and from the installation and switch the tester off before opening the cover of the battery fuse compartment Dangerous voltages may be applied to...

Page 6: ...ntrast 8 ON OFF Switches the instrument power on or off The instrument automatically turns off 15 minutes after the last key was pressed 9 HELP CAL Help function with connection diagrams press for app...

Page 7: ...rying case item no 10008291 1 x Commander test probe switchable by means of TEST key item no 044155 1 x test cable with shock proof plug item no 10008295 1 x universal three wire test cable black blue...

Page 8: ...N Battery indication Battery capacity indication Low battery The storage battery charge condition is too low to ensure correct measuring results Recharge the storage batteries or replace the batteries...

Page 9: ...urrent clamp can be increased Measured signal is out of range clipped Results are impaired Simple error in the IT network Fuse F1 F2 or F3 is defective If one of the fuses F2 or F3 has blown the devic...

Page 10: ...T network RCD TESTING according to EN 61008 EN 61009 IEC 60364 4 41 BS 7671 AS NZS 3017 SET ISC FACTOR setting 0 20 3 00 SELECT COMMANDER ON OFF INITIAL SETTINGS CLAMP SETTINGS BENNING CC 1 044037 BEN...

Page 11: ...e batteries will be recharged automatically as soon as the charger is connected to the charging socket An integrated protective circuit controls the charging process Power supply socket polarity Note...

Page 12: ...rantees compliance with the technical and accuracy specifications stated in the operating manual for the first 12 months after the delivery date To maintain accuracy of the measuring results the devic...

Page 13: ...terior lighting Commander test plug For shock proof socket switchable with TEST and MEM keys with PASS FAIL indication by means of green red LED PE contact electrode for detecting a phase voltage at t...

Page 14: ...t the test cables Shorted test leads 3 Press the key 4 Press the key CAL HELP After performing test leads compensation first measured value and then 0 00 is displayed Successful compensation is displa...

Page 15: ...se adapter optional in a three phase system 3 The measuring result can be stored by means of the MEM key Uln Voltage between phase L and neutral conductors N Ulpe Voltage between phase L and protectiv...

Page 16: ...500 V 1000 V Minimum limiting value without 0 01 M 200 M 3 Connection diagrams Connection of 3 wire test lead and Commander probe tip 4 Press and hold the key until result is stabilized Double click...

Page 17: ...NUITY function 3 Connection diagrams Connection of the three wire test cable and of the optional measuring line BENNING TA 5 044039 Connection of 3 wire test lead and Commander probe tip 4 a R LOW low...

Page 18: ...actor for test current x I N 1 2 5 x I N Limiting value for contact voltage 25 V 50 V 3 Connection diagrams Connecting the Commander test plug optional TN 044149 and the 3 wire test lead 4 Press the k...

Page 19: ...CD Fuse type gL gG gG B C K D Nominal current of the fuse Tripping time of the fuse 3 Connection diagrams Connecting the Commander test plug 044149 and the 3 wire test lead 4 Press the key 5 The measu...

Page 20: ...tion of the optional Commander test plug 044149 and of the three wire test cable Voltage drop Connection of the optional Commander test plug 044149 and of the three wire test cable 4 Press the key 5 T...

Page 21: ...nce Maximum limiting value without 1 5 k 3 Connection diagrams Connection of the optional earthing set 044113 4 Press the key 5 The measuring result can be stored by means of the MEM key R Earth resis...

Page 22: ...unction I Note Please set the current clamp adapter used under SETTINGS 2 Connection diagrams Connection of the optional current clamp adapter BENNING CC 1 044037 BENNING CC 3 044038 4 Press the key 5...

Page 23: ...Set function 2 Set limit LUX Minimum illumination OFF 0 1 lux 20 klux 3 Connection diagrams Positioning of the luminous intensity sensor BENNING luxmeter type B 044111 4 Press the key 5 The measuring...

Page 24: ...t RISO ISFL Single fault leakage current only in IT networks Maximum limiting value without 3 0 mA 20 0 mA 3 Connection diagrams Connection of the three wire test cable 4 Press the key 5 The measuring...

Reviews: