The inputs of the safety edges are at calibrated resistance.

 

  If a resistive safety edge is used, the relevant jumpers (J2 for ASC and J1 for ASA) should be 

closed. Conversely, if a mechanical edge is used the jumpers should be left open. In the event the 
safety edges are not mounted, leave the corresponding jumper open and move the short-circuit 
Dip-Switch to ON (No. 1 for ASA and no. 2 for ASC).

  N.B.: for the safety edge, two inputs are provided, 

NEVER CONNECT THE SAFETY EDGE TO 

THE COMMON TERMINAL.

CAUTION: When the control unit is powered, do not touch any metallic parts.

Dip-Switch Function - SW2 "Select"  
DSW1

      Operating mode of the “P.P. button” and of the remote control.

                 Off: Open/Stop/Close sequence
                 On: Open/Close/Open sequence

DSW2

      “Service man” function. The automatic system carries out the opening and closing opera-

tions as long as the Open and Close push-buttons, respectively are kept pressed.

                 Off: Service Man function disabled 
                 On: Service man function enabled. In this case the Open push-button cannot be used 

as control for pedestrian use. 

DSW3

      “Multiple-flat” function: the “P.P.” (STEP-BY-STEP) input does not cause the motor stop-

ping in the opening phase. At end of opening, the “P.P.” input is enabled for the gate 
closure. 

                 Off: Multiple-flat function is disabled
                 On: Multiple-flat function is enabled

DSW4

      “Forewarning” function: the flashing light switches on 3 seconds before the beginning of 

every movement.

                 Off: Forewarning flashing light is disabled
                 On: Forewarning flashing light is enabled

DSW5

      Photocell activation during the opening phase. If the photocell beam is obscured, the 

motor stops. The movement starts after 1 second from the photocell reset.

                 Off: No activation 
                 On: Temporary stop

DSW6

      “Pedestrian” function: the “Open” input controls the temporary opening (adjustable from 

about 1.5 to 10 metres).

                 Off: Operation as “Open Push-button”
                 On: Operation as “Pedestrian push-button”

DSW7

      Enables or disables electronic braking. The activation of electronic braking allows the 

reduction of the gate inertia and therefore of the stopping space.

                 Off: Electronic braking disabled
                 On: Electronic braking enabled

DSW8

      Automatic closure. 

                 Off: Automatic closure disabled 
                 On: Automatic closure enabled 

The selections which are preset with the Dip-Switches are memorized in the Stop phase. If a vari-
ation to the configuration of the Dip-Switches is carried out, the control unit operation is modified 
after the following stop.

Dip-Switch SW1 “Bypass” Function 

The Dip-Switches “Bypass” allow to short-circuit the normally closed inputs that are not in use.

DSW1

  Input ASA

             Off= Enabled input
             On= Disabled input (leave the gate open).

DSW2

  Input ASC

             Off= Enabled input
             On= Disabled input (leave the gate open).

Summary of Contents for RI.10KI

Page 1: ...STEUERUNG F R CENTRALE A MICROCONTR LEUR POUR CENTRALITA A MICROPROCESADOR POR CENTRALKA Z MIKROPROCESOREM DLA Libro istruzioni Operating instructions Betriebsanleitung Livret d instructions Libro de...

Page 2: ...tibilit lectromagn tique Reglamento de compatibilidad electromagn tica 89 336 MCE 93 68 MCE Wytyczna odno nie zdolno ci wsp dzia ania elektromagne tycznego 89 336 EWG 93 68 EWG Norme armonizzate appli...

Page 3: ...3 F2 F3 F1 ON ON...

Page 4: ...i Funzione Descrizione 1 2 Ingresso 230Vac Alimentazione centrale 230Vac 50Hz Fase morsetto 1 Neutro morsetto 2 3 4 5 Uscita Motore Rispettivamente Marcia 3 Marcia 4 e Comune 5 6 7 LAMP Al lampeggiant...

Page 5: ...ta On Funzione condominiale abilitata DSW4 Funzione Prelampeggio la luce lampeggiante viene attivata 3 secondi prima dell inizio di ogni manovra Off Prelampeggio disabilitato On Prelampeggio abilitato...

Page 6: ...volta terminata la programmazione riportare i Dip Switch nelle posizioni normali Questa centrale esegue automaticamente il test di integrit del circuito di potenza Qualora dovesse rilevare un malfunz...

Page 7: ...7...

Page 8: ...15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 def 60 63 66 69 72 75 78 81 84 87 90 93 96 99 102 105 108...

Page 9: ...3 4 5 Output Motor Respectively Move 3 Move 4 and Common 5 6 7 LAMP To the flashing light at 230Vac 8 CHIUDE Input CLOSE push button Normally Open N O contact 9 APRE Input OPEN push button N O contact...

Page 10: ...function is disabled On Multiple flat function is enabled DSW4 Forewarning function the flashing light switches on 3 seconds before the beginning of every movement Off Forewarning flashing light is d...

Page 11: ...e the Dip switches to the normal posi tions This control unit performs the power circuit integrity test automatically Should a fault be detected the unit stops and indicates the fault through two blin...

Page 12: ...12...

Page 13: ...13 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 def 60 63 66 69 72 75 78 81 84 87 90 93 96 99 102 105 108...

Page 14: ...2 Eingang 230Vac Speisung der Zentrale 230Vac 50Hz Fase Klemme 1 Nulleiter Klemme 2 3 4 5 Ausgang Motor bzw Betrieb 3 Betrieb 4 und Mittelleiter 5 6 7 LAMP zur Blinkleuchte zu 230Vac 8 CHIUDE Eingang...

Page 15: ...ohngemeinschaftsfunktion deaktiviert On Wohngemeinschaftsfunktion aktiviert DSW4 Funktion Vorblinken die Blinkleuchte wird 3 Sekunden vor jeder Bewegung aktiviert Off Vorblinken deaktiviert On Vorblin...

Page 16: ...er in ihre Ausgangspositionen bringen Diese Zentrale testet automatisch die Funktionst chtigkeit des Leistungskreislaufes Falls eine St rung ermittelt wird blockiert sie sich und meldet die St rung du...

Page 17: ...17...

Page 18: ...18 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 def 60 63 66 69 72 75 78 81 84 87 90 93 96 99 102 105 108...

Page 19: ...Entr e 230Vca Alimentation centrale 230Vca 50Hz Phase borne 1 Neutre borne 2 3 4 5 Sortie Moteur Respectivement Marche 3 Marche 4 et Commun 5 6 7 LAMP Vers le clignotant 230Vca 8 CHIUDE Entr e touche...

Page 20: ...ermeture du portail Off Fonction copropri t invalid e On Fonction copropri t valid e DSW4 Fonction Pr clignotement la lumi re clignotante est activ e 3 secondes avant le d but de chaque man uvre Off P...

Page 21: ...ter Apr s avoir achev la programmation replacer les Dip Switches dans leurs positions nor males Cette centrale ex cute automatiquement les tests d int grit du circuit de puissance En cas de dysfonctio...

Page 22: ...22...

Page 23: ...23 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 def 60 63 66 69 72 75 78 81 84 87 90 93 96 99 102 105 108...

Page 24: ...Vac Alimentaci n central 230Vac 50Hz Fase borne 1 Neutro borne 2 3 4 5 Salida Motor Respectivamente Marcha 3 Marcha 4 y Com n 5 6 7 LAMP Al intermitente de 230Vac 8 CHIUDE Entrada bot n CIERRA Contact...

Page 25: ...d inhabilitada On Funci n comunidad habilitada DSW4 Funci n Intermitencia previa la luz intermitente es activada 3 segundos antes del comienzo de cada maniobra Off Intermitencia previa inhabilitada On...

Page 26: ...na vez terminada la programaci n colocar de nuevo los Dip switch en las posiciones normales Esta central ejecuta autom ticamente el test de integridad del circuito de potencia Si registra una anomal a...

Page 27: ...27...

Page 28: ...28 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 def 60 63 66 69 72 75 78 81 84 87 90 93 96 99 102 105 108...

Page 29: ...ampy migaj cej na 230Vac 8 CHIUDE ZAMYKA Wej cie przycisku ZAMYKA Styk N O 9 APRE OTWIERA Wej cie przycisku OTWIERA Styk N O wymienny z wej ciem dla Sterownika no nego 10 P P Wej cie przycisku POSUW P...

Page 30: ...dokonaniu otwarcia wej cie P P jest zdatne do zamykania bramy Off Funkcja wsp u ytkowa wy czona On Funkcja wsp u ytkowa w czona DSW4 Funkcja Ostrzegawcza wiat o migaj ce w cza si 3 sekundy wcze niej...

Page 31: ...o zako czeniu programowania nale y przywr ci Dip Switch do pozycji normalnych Centralka ta automatycznie wykonuje test sprawdzaj cy ca kowito obwodu mocy W przypadku wychwycenia jakiej niesprawno ci c...

Page 32: ...zamykanie automatyczne Dip Switch 1 4 On On Off Off Czas wyczekiwania zostaje wyzerowany gdy styk wej cia FTC zostanie otwarty lub styk wej cia Otwiera zostanie zamkni ty Czas dzia ania funkcji Peda...

Page 33: ...ia Dip Switch 1 3 Off Off On Sekundy Czasdzia aniaregulowanyjestprzeznast puj cemen pow czeniusi silnikapozadzia aniuwy cznikakra cowego 7sekund przed up ywem nastawionego czasu centralka rozpoczyna z...

Page 34: ......

Page 35: ......

Page 36: ...AUTOMATISMI BENINC Srl Via Capitello 45 36066 Sandrigo VI Tel 0444 751030 r a Fax 0444 759728...

Reviews: