14

26

ENC-

Input for GND Encoder connection (see Fig.2).

27-28

SENSITIVE
EDGE
(DAS)

Input, sensitive edge contact 
Resistive edge: “DAS” Jumper closed
Mechanical edge: “DAS” Jumper open 
When the edge is activated, the gate movement is stopped and reversed for about 3s.

29-30

II°CH/SERL

N.O. Contact free from Voltage, may be configured as second radio channel or service light. 
For use as second radio channel the 2CH logic must be ON. 
For use as courtesy light the 2CH logic must be OFF.

31-32

Antenna

Connection to the built-in radio receiver card (30-signal/31-screen).

+ / -

24VAC/dc

Input, 24VAC/24VDC power supply.
In case of use of plug batteries connect the battery charging card as indicated in the specific 
installation instructions.

U11

CONFIGURATION 
MEMORY

Extractable Eprom Memory. Contains all the control unit configurations (logics, parameters, 
etc.), including the radiotransmitters. In case of faults it is possible to extract Eprom and 
insert it into a different control unit, avoiding reprogramming. 

ENCODER WIRING

In case the motor is with Encoder and one wished to connect it to the control unit, carry out the connections indicated in Fig.2, in 
this case the SWO1 and SWO2 inputs may not be used as Limit switch inputs. 
It is not possible to use the Encoder and the closure Limit switch simultaneously. 
Leave SWC1 and SWC2 shorted.

TO ChECK CONNECTIONS

1)  Cut-off power supply.
2)  Manually release the wings, move them to approx. half-stroke and lock them again.
3)  Reset power supply.
4) Send a step-by-step control signal by pressing the <-> push-button.

5) The leeaves must move in OPENING.

 

In case this does not happen, it is sufficient to invert among them the motor run wires. (1<>2 for M1 motor, and 3<>4 for M2 
motor) and, if used, the relative Limit switch inputs (14<>15 for M1 motor,  and 16<>17 for M2 motor).

PROGRAMMING

The programming of the various functions of the control unit is carried out using the LCD display on the control unit and setting the 
desired values in the programming menus described below.
The parameters menu allows you to assign a numerical value to a function, in the same way as a regulating trimmer.
The logic menu allows you to activate or deactivate a function, in the same way as setting a dip-switch.
Other special functions follow the parameters and logic menus and may vary depending on the type of control unit or the software 
release.

TO ACCESS PROGRAMMING:

1 – Press the button <PG>, the display goes to the first menu, Parameters “PAR”. 
2 – With the <+> or <-> button, select the menu you want (PAR>LOG>RAD>NMAN>MACI>RES>AUTO>CODE).
3- Press the button <PG>, the display shows the first function available on the menu.
4 - With the <+> or <-> button, select the function you want.
5 - Press the button <PG>, the display shows the value currently set for the function selected.
6 - With the <+> or <-> button, select the value you intend to assign to the function.
7 - Press the button <PG>, the display shows the signal “PRG” which indicates that programming has been completed.

NOTES: 

Simultaneously pressing <+> and <-> from inside a function menu allows you to return to the previous menu without making any 
changes. Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.
After waiting 120s the control unit quits programming mode and switches off the display.
When the board is switched on, the software version is displayed for around 5 sec  
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.

PARAMETERS, LOGIC AND SPECIAL FUNCTIONS 

The tables below describe the individual functions available in the control unit.

PARAMETERS (

PAR

)

MENU

FUNCTION

MIN-MAX-(Default)

MEMO

TCA

Automatic closing time. Active only with logic “TCA”=ON.
At the end of the set time the control unit orders a closing manoeuvre.

1-240-(40s) 

Summary of Contents for BRAINY 24

Page 1: ...L8542589 05 2011 rev 0 BRAINY 24 UNIONE NAZIONALE COSTRUTTORI AUTOMATISMI PER CANCELLI PORTE SERRANDE ED AFFINI...

Page 2: ...x SWO1 ENC1 SWC1 SWO2 ENC2 SWC2 PHOT PHOTC STOP OPEN CLOSE PED P P COM ENC ENC COM ENC F1 T 2A DAS J1 DAS Open DAS N C J1 DAS Close DAS 8K2 28 27 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21...

Page 3: ...NCODER ENCODER WIRING 2 3 4 24Vac 24Vac COM NC NO RX1 TX1 24Vac 24Vac COM NC NO RX2 TX2 11 24Vac COM PHOT COM PHOT C 24Vac 12 11 12 13 18 13 19 9 10 9 10 test1 on test2 ON SCA AUX1 0 AUX1 2 SERVICE ZO...

Page 4: ...o per l installazione e la manutenzione di aperture automatiche Nessuna informazione qui presente di interesse o di utilit per l utente finale Conservare questo manuale per futuri utilizzi L installat...

Page 5: ...cabatteria l uscita in assenza di alimentazione di rete presenta una tensione 24Vdc polarizzata Verificare il corretto collegamento dei dispositivi 11 24Vdc 12 0Vdc 13 COM ENC Comune per finecorsa e t...

Page 6: ...e se utilizzati i relativi ingressi di finecorsa 14 15 per il motore M1 e 16 17 per il motore M2 Programmazione La programmazione delle varie funzionalit della centrale viene effettuata utilizzando il...

Page 7: ...a il contatto si chiude per il tempo impostato Vedere schema di collegamento Figura 4 1 240 60s TLOc Tempo attivazione elettroserratura Valore espresso in 1 10s 0 0s 50 5s 0 50 5 0 5s SLD1 Regola la v...

Page 8: ...lo sgancio dell elettroserratura Off Funzione disabilitata OFF Blco Abilita o disabilita la funzione di blocco in apertura On Funzione blocco abilitato Da utilizzare solo con motori dotati di fine co...

Page 9: ...otori On Verifica abilitata Se la verifica ha esito negativo non viene comandata nes suna manovra Off Verifica disabilitata OFF rem Abilita o disabilita l apprendimento remoto dei radiotrasmettitori c...

Page 10: ...ei parametri Inizialmente entrambe le ante vengono portate in posizione di apertura quindi dopo alcune manovre di apertura e chiusura a di verse velocit di una o di entrambe le ante la centrale visual...

Page 11: ...ti dai segmenti orizzontali La centrale visualizza il messaggio AMP1 o AMP2 in caso di intervento del sensore am perometrico antischiacciamento MESSAGGI DI ERRORE Di seguito sono elencati alcuni messa...

Page 12: ...WARNINGS This manual has been especially written to be use by qualified fitters None of the information provide in this manual can be considered as being of interest for the end users Preserve this ma...

Page 13: ...ST1 and TEST2 logics must be OFF For use as photocell test it is sufficient to activate one or both TEST logics and connect the photocells as indicated in Fig 3 11 12 24 Vac dc Output accessory power...

Page 14: ...M1 motor and 16 17 for M2 motor PROGRAMMING The programming of the various functions of the control unit is carried out using the LCD display on the control unit and setting the desired values in the...

Page 15: ...osing with respect to motor 2 0 40 3s TLS SERL contact activation time Service light 29 30 terminals At each manoeuvre the contact closes for the set time See Figure 4 connection scheme 1 240 60s TLOc...

Page 16: ...sables the block function in opening On Block function enabled To use only with motors equipped with Limit switch After the intervention of the opening Limit switch the control unit delays arrest by a...

Page 17: ...d Off Remote learning not enabled OFF RADIO RAD MENU FUNZIONE PP By selecting this function the receiver goes in waiting Push for a transmitter code to assign to the step step func tion Press the key...

Page 18: ...fter some opening and closing manoeuvres at different speeds of one or both the shutters the control unit displays the message OK In case the operation has no positive result the message ERR is displa...

Page 19: ...e N C inputs are represented by the vertical segments N O inputs are represented by the horizontal segments The control unit sees the message AMP1 or AMP2 in case of anti crushing ammeter sensor inter...

Page 20: ...omatischen ffnungsvorrichtungen bestimmt Es enth lt keine Informationen die f r den Endbenutzer interessant oder n tzlich sein k nnten Bewahren Sie dieses Handbuch f r Nachschlagzwecke auf Der Install...

Page 21: ...ter TEST1 und TEST2 auf OFF stehen F r den Gebrauch als Fotozellentest gen gt es eine oder beide Logikschalter TEST zu aktivieren und die Fotozellen wie in Abb 3 angezeigt anzuschlie en 11 12 24 Vac d...

Page 22: ...5 f r die Motore M1 und 16 17 f r Motor M2 Programmierung Die Programmierung der verschiedenen Funktionen der Steuerzentrale erfolgt ber das LCD Display an der Zentrale selbst indem die gew nschten We...

Page 23: ...ngszeit Kontakt SERL Innenleuchte Klemmen 29 30 Bei jeder Bewegung schlie t sich der Kontakt f r die Dauer der eingestellten Zeit Siehe Anschlussplan Abbildung 4 1 240 60s TLOc Aktivierungszeit Elektr...

Page 24: ...en mit Endschalter zu benutzen Nach dem Eingreifen der ffnungsendschalter verz gert die Zentrale den Halt um etwa 0 5s damit ein besserer Anschlag des Fl gels in die Arrettierungen erm glicht wird Off...

Page 25: ...er Funkger te wie im Abschnitt Fern bernahme Funkger te On Fern bernahme freigeschaltet Off Fern bernahme nicht freigeschaltet OFF RADIO RAD MENU FUNZIONE PP Bei Wahl dieser Funktion setzt sich der Em...

Page 26: ...geln zeigt die Zentrale die Meldung OK an Wenn der Vorgang ohne positives Ergebnis bleibt wir die Meldung ERR Wiederholen Sie den Vorgang erneut nachdem Sie die Verkabelungen berpr ft aben und sicher...

Page 27: ...normalerweise geschlossenen Eing ngen entsprechen die vertikalen Segmente Den normalerweise offenen Eing nge entsprechen die horizontalen Segmente Die Zentrale zeigt die Meldung AMP1 oder AMP2 an wen...

Page 28: ...es Aucune information donn e dans ce manuel ne sera d in t r t ou d utilit a l utilisateur final Conservez ce manuel pour de futures utilisations L installateur doit donner tout renseignement relatif...

Page 29: ...iques TEST1 et TEST2 doivent tre OFF Pour utilisation comme test photocellules il suffit d activer une ou les deux logiques TEST et de connecter les photocellules de la fa on indiqu e sur la Fig 3 11...

Page 30: ...its ci apr s Le menu param tres permet d associer une valeur num rique une fonction comme pour un trimmer de r glage Le menu des logiques permet d activer ou de d sactiver une fonction comme pour le r...

Page 31: ...t la vitesse de fonctionnement normal 30 70 40 SpD1 R gle la vitesse du moteur 1 durant la phase de vitesse normale Valeur exprim e en pourcentage 30 99 99 SpD2 R gle la vitesse du moteur 2 durant la...

Page 32: ...urs do t s de fins de course Apr s l intervention des fins de course d ouverture l ar moire retarde l arr t d environ 0 5s de mani re consentir une meilleure but e du battant sur les dispositifs d arr...

Page 33: ...le code n est pas valide le message ERR s affiche 2Ch En s lectionnant cette fonction la r ceptrice se met en attente Push d un code metteur attribuer au second canal radio lectrique Presser la touche...

Page 34: ...s r p ter la proc dure d autoset Durant les man uvres l cran affiche certains sigles OPM1 OPM2 durant l ouverture du moteur 1 ou 2 et CLM1 CLM2 durant la fermeture du moteur 1 ou 2 PROTECTION D ACC S...

Page 35: ...l cran en cas d anomalies de fonctionnement Amp1 Erreur obstacle moteur 1 anti crasement V rifier la pr sence d obstacles sur la course du battant moteur 1 Amp2 Erreur obstacle moteur 2 anti crasement...

Page 36: ...instalaci n y el mantenimiento de aper turas autom ticas Ninguna informaci n de las aqu presentadas es de inter s o de utilidad para el usuario final Guardar este manual para futuras consultas El inst...

Page 37: ...rta o test fotoc lulas Para utilizar como Indicador cancela abierta las l gicas TEST1 y TEST2 deben estar en modo OFF Para utilizar como test fotoc lulas bastar con activar una o ambas l gicas TEST y...

Page 38: ...M2 y si se utilizan las entradas de final de carrera correspondientes 14 15 para el motor M1 y 16 17 para el motor M2 Programaci n La programaci n de las diferentes funciones de la centralita se efect...

Page 39: ...el contacto se cierra durante el tiempo configurado Consulte el esquema de conexi n de la figura 4 1 240 60s TLOc Tiempo de activaci n de la electrocerradura Valor expresado en 1 10se 0 0s 50 5s 0 50...

Page 40: ...ci n deshabilitada OFF Blco Habilita o deshabilita la funci n de bloqueo en apertura On Funci n bloqueo habilitado Se utiliza solamente con motores que cuentan con final de carrera Despu s de la inter...

Page 41: ...ada operaci n deshabilitada OFF TSTm Habilita o deshabilita el control de los motores On Control habilitado Si el control no se realiza con xito no se controla ninguna operaci n Off Control deshabilit...

Page 42: ...para memorizar el recorrido de las hojas y para configurar los par metros En principio ambas hojas se colocan en posici n de apertura luego despu s de algunas maniobras de apertura y cierre a distint...

Page 43: ...ntales La central muestra el mensaje AMP1 o AMP2 en caso de intervenci n del sensor ampe rom trico antiaplastamiento MENSAJES DE ERROR A continuaci n se muestran algunos mensajes que se visualizan en...

Page 44: ...nego personelu w celu instalacji I konserwacji bram automatycznych adna z zawartych tu informacji nie jest u yteczna ani celowa dla ko cowego u ytkownika Przechowywa niniejszy podr cznik do przysz ego...

Page 45: ...ej bramy lub test fotokom rek W przypadku zastosowania jako Kontrolka otwartej bramy dla logiki TEST1 i TEST2 nale y ustawi warto OFF W przypadku zastosowania jako test fotokom rek wystarczy uaktywni...

Page 46: ...lnika 1 2 dla silnika M1 i 3 4 dla silnika M2 oraz odpowiednie wej cia wy cznik w kra cowych je li s u ywane 14 15 dla silnika M1 i 16 17 dla silnika M2 Programowanie Programowanie r nych funkcji cent...

Page 47: ...zaciski 29 30 Przy ka dym manewrze kontakt zamyka si na ustalony czas Schemat pod cze zosta pokazany na Rysunku 4 1 240 60s TLOc Czas w czania zamka elektrycznego Warto wyra ona w 1 10s 0 0s 50 5s 0...

Page 48: ...Stosowana tylko z silnikami wyposa onymi w wy czniki kra cowe Po zadzia aniu wy cznik w kra cowych otwierania centralka op nia zatrzymanie o oko o 0 5 s w ten spos b skrzyd o lepiej uderza w blokady...

Page 49: ...w On Zdalne zapami tywanie nadajnik w za czone Off Zdalne zapami tywanie nadajnik w nieza czone OFF RADIO RAD MENU FUNZIONE PP Po wybraniu tej funkcji odbiornik przechodzi w tryb oczekiwania Push na k...

Page 50: ...ie po kilku manewrach otwierania i zamykania z r nymi pr dko ciami jednego lub obu skrzyde centralka wy wietla komunikat OK Je eli operacja nie zako czy si pozytywnym wynikiem zostaje wy wietlony komu...

Page 51: ...ziome Centralka wy wietla komunikaty AMP1 lub AMP2 w przypadku zadzia ania czujnika am perometrycznego zapobiegaj cego przygnieceniu KOMUNIKATY O B DZIE Poni ej zosta y wyszczeg lnione komunikaty wy w...

Page 52: ...FO BMT 4DIBSOJFS EJF OFOEFO 4DISBVCFO MPDLFSO BCFS OJDIU BVTCBVFO EBNJU EFS FDLFM HF GGOFU XFSEFO LBOO 1SFTTFS MFT EFVY BJMFUUFT MBU SBMFT QPVS E DSPDIFS MFT EFVY DBDIF WJT OMFWFS MFT EFVY WJT TVS MF...

Reviews: