PRC487

Connection

Connect the device according to the wiring diagram described in
the operating instructions of the MEDICS® module. Please obser-
ve the tightening torque for the terminal screws (see technical
data).

Connections

GND3

Ground,
common input for the terminals 4, 5, 6, IN3, IN4, SDA,
SCL 

4

Input line 3, high or open = failure line 3

5

Input line 2, high or open = failure line 2

6

Input line 1, high or open = failure line 1

Ub

12 V

7

PWM-open-collector output: response value under-
voltage 
Low = upper response value
High = lower value

8

Contact without function

9

Open-collector output test relay
0 V = relay On, TEST

10

Contact without function

IN3

Input contactor relay: High or open = failure K3

IN4

Input manual operation: Low = manual operation

k, l

Connection current transformer for N conductor mo-
nitoring

A, B

BMS bus

A3, A4

Supply voltage U

S

GND1

Ground of the input IN1

IN1

Input state of switching element K1: Low = K1 On

GND2

Ground of the input IN2

IN2

Input status of switching element K2: Low = K2 On

11, 14

Relay contact to activate K1 (K1 on) with open-circuit
monitoring.

21, 24

Relay contact to deactivate K1 (K1off) with open-cir-
cuit monitoring.

31, 34

Relay contact to activate K2 (K2on) with open-circuit
monitoring.

41, 44

Relay contact to deactivate K2 (K2off). with open-cir-
cuit monitoring.

51, 52, 54 Potential free changeover contact for common alarm

message. 

45

Open-circuit monitoring

SDA, SCL

I

2

C bus. Internal serial interface for communication

with open-circuit monitoring device CV460 or relay
module RK4xx. 

Only permanently installed devices, which at least sa-
tisfy the requirements of overvoltage category CAT II
(300 V), may be connected to the inputs and outputs
(except for the supply voltage).

Anschluss

Schließen Sie das Gerät entsprechend dem Anschlussplan in der
Anleitung des MEDICS®-Moduls an. Beachten Sie dabei das An-
zugsdrehmoment für die Klemmschrauben (siehe Technische
Daten).

Anschlüsse

GND3

Masse, gemeinsamer Eingang der Klemmen 4, 5, 6,
IN3, IN4, SDA, SCL

4

Eingang Leitung 3
high oder offen = Ausfall Leitung 3

5

Eingang Leitung 2
high oder offen = Ausfall Leitung 2

6

Eingang Leitung 1
high oder offen = Ausfall Leitung 1

Ub

A 12 V

7

PWM-Open-Collector-Ausgang Ansprechwert Unter-
spannung 
Low = oberer Ansprechwert
high = unterer Wert

8

Dieser Kontakt hat keine Funktion

9

Open-Collector-Ausgang Test-Relais 
0 V = Relais ein, TEST

10

Dieser Kontakt hat keine Funktion

IN3

Eingang Hilfsschütz: High oder offen = Ausfall K3

IN4

Eingang Handbetrieb: Low = Handbetrieb

k, l

Anschluss Stromwandler für N-Leiterüberwachung

A, B 

BMS-Bus

A3, A4 

Versorgungsspannung U

s

GND1

Masse des Eingangs IN1

IN1

Eingang Schaltzustand Schaltglied K1: Low = K1 ein

GND2

Masse des Eingangs IN2

IN2

Eingang Schaltzustand Schaltglied K2: Low = K2 ein

11,14

Relaiskontakt zur Ansteuerung des Einschaltens von
K1 (K1on) mit Drahtbruchüberwachung

21, 24

Relaiskontakt zur Ansteuerung des Ausschaltens von
K1 (K1off) mit Drahtbruchüberwachung

31,34

Relaiskontakt zur Ansteuerung des Einschaltens von
K2 (K2on) mit Drahtbruchüberwachung

41, 44

Relaiskontakt zur Ansteuerung des Ausschaltens von
K2 (K2off) mit Drahtbruchüberwachung

51, 52, 54 Potentialfreier Wechsler als Sammelstörmeldung. 
45

Drahtbruchüberwachung

SDA, SCL

I²C-Bus. Interne serielle Schnittstelle zur Kommunika-
tion mit Drahtbruch-Überwachung CV460 bzw. Re-
laisbaustein RK4xx.

An die Ein- und Ausgänge (außer Versorgungsspan-
nung) dürfen nur fest installierte Geräte, die mindes-
tens die Anforderungen der Überspannungskatego-
rie CAT II (300 V) erfüllen, angeschlossen werden.

Summary of Contents for PRC487

Page 1: ...rotected by a password Operating elements Fig 1 Figure 1 Operating elements Steuergerät für Umschalteinrichtungen Bestimmungsgemäße Verwendung Das Steuergerät PRC487 dient zur zentralen Steuerung von ME DICS Modulen der Baureihen UMC USC und UFC ME DICS Module sind besonders geeignet zur Überwachung und Umschaltung der Stromversorgung von medizinisch genutzten Räumen nach DIN VDE 0100 710 Diese An...

Page 2: ...o personnel Substantial damages to the electrical installation and destruction of the device may occur Legende der Bedienelemente 1 Beleuchtete Text Anzeige 2 x 16 Zeichen 2 LED ALARM gelb leuchtet wenn ein Ansprechwert überschritten oder ein Fehler erkannt wurde 3 LED RS485 gelb informiert über Aktivitäten auf dem BMS Bus 4 LED ON grün leuchtet wenn Gerät im Betrieb ist 5 Im Anzeige Modus Öffnet ...

Page 3: ...nected to the inputs and outputs except for the supply voltage Anschluss Schließen Sie das Gerät entsprechend dem Anschlussplan in der Anleitung des MEDICS Moduls an Beachten Sie dabei das An zugsdrehmoment für die Klemmschrauben siehe Technische Daten Anschlüsse GND3 Masse gemeinsamer Eingang der Klemmen 4 5 6 IN3 IN4 SDA SCL 4 Eingang Leitung 3 high oder offen Ausfall Leitung 3 5 Eingang Leitung...

Page 4: ...zw K13 5 Drahtbruch K1 ON Drahtbruch in der Ansteuerung von K1 Hauptschütz 5 Drahtbruch K1 OFF Drahtbruch in der Ansteuerung zum Abfallen von K1 Hauptschütz 5 K1 on K2 off Commissioning Prior to commissioning check proper connection of the device Operation and setting During operation the PRC487 is in the display mode Pressing the MENU button changes to the Menu mode All the parameters for the swi...

Page 5: ...rt Es erfolgt keine automatische Rückschaltung auf Leitung 1 außer wenn Leitung 2 ausfällt Alarmtext anzeige des PRC487 Bedeutung Kanal Details about fault finding are provided in the operating instruc tions of the respective switchover module Failure K1 Failure of contactor for line 1 con tactor is switched on but no voltage on distribution board 5 Fault K2 on Fault when controlling K2 6 Fault K2...

Page 6: ...altung ist aktiv 5 Handbetrieb Steuerung der Schütze ist auf Handbetrieb umgestellt Es erfolgt keine automatische Umschaltung mehr 6 1 EXIT 2 SETUP 3 SETUP K Q 4 SETUP OPTION 5 TEST COM 6 PASSWORD 7 INFO Operating messages The following messages are provided at the PRC487 BMS bus Settings in the Menu mode Operating steps 1 Press MENU Enter to activate the Menu mode 2 Select the appropriate submenu...

Page 7: ...alter mit Motorantrieb per Dauersig nal über Hilfsschütze angesteuert mit Zusatzbau stein CV460 Q D Leistungsschalter mit Motorantrieb direkt ange steuert 1 EXIT 2 SETUP SETUP submenu In the SETUP K Q menu general parameters can be set 1 EXIT To leave the submenu 2 ADDRESS To set the address of the PRC487 Changing the address has an ef fect on the connected MK24 alarm indicator and test combina ti...

Page 8: ...ng des Lichtbogens in der Überstrom Schutzeinrichtung muss kleiner sein als die minimale Umschaltverzögerungszeit tan toff 2 SETUP 3 SETUP K Q 6 Y1 Undervoltage response value of the SUE487 respectively SUD487 voltage relay At this value switchover from the preferred supply to the second supply takes place provided that voltage is present on this line The response value Y1 is adjustable between 70...

Page 9: ...chovertime t 0 5s beingacharacteristicof the switchover module Abb 3 Zeitlicher Ablauf einer Umschaltung L1 Leitung 1 bevorzugte Einspeisung L2 Leitung 2 zweite Einspeisung L3 Leitung 3 Ausgang der Umschalteinrichtung sK1 Q1 sK2 Q2 Steuersignal für Schaltelement K1 Q1 K2 Q2 Leistungskontakt des Schaltelements K1 Q1 K2 Q2 tu Gesamtumschaltzeit der Umschalteinrichtung tan Ansprechzeit 50 250 ms des ...

Page 10: ...g ohne Funktion Q1 I Y Schaltelement Q1 hat Überstromauslösung Q2 I Y Schaltelement Q2 hat Überstromauslösung 3 SETUP K Q 4 SETUP OPTION K1on Allows setting of the parameters for output 11 14 of the PRC487 Function signal at 11 14 The parameters are t The time for which the signal on 11 14 must be present This input is always required even for continuous signal setting It specifies the maximum On ...

Page 11: ...Die Rückschaltung muss manuell zu einem geeigneten Zeitpunkt durch Öffnen des Eingangs vorgenommen werden oder erfolgt automatisch nach Ausfall der zweiten Leitung only valid for switchover modules with circuit breakers 4 111 4 5 121 4 6 131 4 and 7 141 4 Open circuit monitoring of the switching elements can be activa ted via these four menu items RK4xx 8 IN 10 and 9 IN 11 The following settings a...

Page 12: ...ldung Schaltelement K1 Q1 ist einge schaltet B K Q2 Betriebsmeldung Schaltelement K2 Q2 ist einge schaltet 4 SETUP OPTION 5 TEST COM 5 TEST COM 6 PASSWORD 6 PASSWORD 7 INFO 10 111 4 11 121 4 12 131 4 and 13 141 4 If the respective message is provided these four menu items can be used to activate the closing of the associated contact pairs at the RK4xx only for switchover modules with circuit break...

Page 13: ...710 VDE 0100 Teil 710 2002 11 ÖVE EN7 1991 ÖVE ÖNORM E8007 A1 2001 02 01 ÖVE ÖNORM E8007 A2 2002 11 01 IEC 60364 7 710 2002 11 Factory settings The factory settings are documented in the respective protocol Measuring results and settings in operating instructions of the MEDICS module Test When a test is activated at the PRC487 the PRC487 will also acti vate a test at the voltage relay SUE487 resp ...

Page 14: ...minals DIN EN 60529 IP20 Screw fixing 2 x M4 DIN rail mounting acc to IEC 60715 Flammability class UL94V 0 Weight approx 530 g Technische Daten Isolationskoordination nach IEC 60664 1 Bemessungsspannung AC 250 V Bemessungs Stoßspannung Verschmutzungsgrad 4 kV 3 Spannungsbereiche Versorgungsspannung US siehe Typenschild Arbeitsbereich von US 0 7 1 3 x Us Eigenverbrauch max 3 VA Ansprechwerte Unters...

Page 15: ...s Abweichende Ausführungen Dieses Feld ist nur beklebt falls Änderungen gegenüber der Stan dardausführung des Gerätes vorgenommen wurden Bestellangaben Typ Type Versorgungsspannung Us Supply voltage Us Art Nr Art No PRC487 AC 230 V B 92 042 000 PRC487 133 AC 127 V B 92 042 002 PRC487 29 DC 110 V B 92 042 004 PRC487 29 DC 24 V B 92 042 003 PRC487 9 AC 230 V B 92 042 005 ...

Page 16: ...ax 49 6401 807 259 Web http www bender de com Postfach 1161 35301 Grünberg Germany Alle Rechte vorbehalten Nachdruck und Vervielfältigung nur mit Genehmigung des Herausgebers Änderungen vorbehalten Bender GmbH Co KG All rights reserved Reprinting and duplicating only with permission of the publisher Subject to change Bender GmbH Co KG ...

Reviews: