Modbus Register Map
92
PEM330-333_D00004_01_M_XXEN/08.2015
Tab. 8.15: Minimum values
Comments:
1)
Only in the case of wye connection.
2)
"x100 V" means that the voltage value in the register is 100 times
the actual measured value (therefore, the value of the register
must be divided by 100 to obtain the measuring value).
43308
RO
λ
ges min
x1000
43312
RO
f
min
x100 Hz
43316
RO
min. unbalance U
x1000
43320
RO
min. unbalance I
x1000
43324
RO
THD
UL1 min
x10.000
43328
RO
THD
UL2 min
x10.000
43332
RO
THD
UL3 min
x10.000
43336
RO
THD
I1 min
x10.000
43340
RO
THD
I2 min
x10.000
43344
RO
THD
I3 min
x10.000
Register Property Description
Format