Modbus Register Map
80
PEM330-333_D00004_01_M_XXEN/08.2015
41054
RW
Calculation method
S
UINT16 B1B0:
00* = vector
01 = scalar
41055
Reserved
41056
RW
Polarity measuring
current transfor-
mer L1
UINT16 0* = normal
1 = reversed
41057
RW
Polarity measuring
current transfor-
mer L2
UINT16 0* = normal
1= reversed
41058
RW
Polarity measuring
current transfor-
mer L3
UINT16 0 = normal
1 = reversed
41059…41222
Reserved
41223
RW
Specified time for
demand measure-
ment
UINT16 1, 2, 3, 5, 10, 15*,
30, 60 minutes
41224
Reserved
41225
RW
Rotating field
UINT16 0* = ABC right
1 = CBA left
41226
WO
Clear peak demand
value
UINT16 Writing „0xFF00“
to the register
resets the peak
demand value to 0
Register Property
Description Format
Range/unit