Application/inputs and outputs
62
PEM330-333_D00004_01_M_XXEN/08.2015
The following settings are possible:
2.
Setpoint limit
: Specifies the value that the setpoint parameter must go
below or exceed for the setpoint to become active. Returns to normal
condition in case of:
the limit value is exceeded
0.95 x setpoint limit
the value is below the limit value
1.05 x setpoint limit
For P, Q and λ, also negative values can be entered as setpoint limits.
3.
Setpoint delay
: Specifies the minimum duration
which the setpoint condition must be met before the setpoint beco-
mes active or
which the setpoint return condition must be met before the setpoint
becomes inactive.
An event will be generated and stored in the SOE Log for any setpoint status
changes. The range of the setpoint delay is between 0 and 9,999 seconds.
4.
Setpoint trigger
: Specifies what action the setpoint will take when it
becomes active. This action includes "No Trigger" and "Trigger DOx".
Setpoint type
Parameters
Values exceeded
Phase voltages
U
LN
(x100 V)
Line-to-line voltages
U
LL
(x100 V)
I
(x1000 A)
P
ges
(x1000 kW)
Q
ges
(x1000 kvar)
Value below limit
Phase voltages
U
LN
(x100 V)
Line-to-line voltages
U
LL
(x100 V)
Power factor λ (×1000)