Technical data
64
isoMIL425_D00203_03_M_XXEN/03.2019
Environment/EMC
EMC .......................................................................................................................... IEC 61326-2-4, DIN EN50121-3-2
Ambient temperatures:
Operation ................................................................................................................................................ -40…+70 ºC
Transport ................................................................................................................................................ -50…+85 ºC
Storage ................................................................................................................................................... -55…+80 ºC
Climatic class acc. to IEC 60721:
Stationary use (IEC 60721-3-3)................................................................................................................................ 3K7
Transport (IEC 60721-3-2) ....................................................................................................................................... 2K4
Long-time storage (IEC 60721-3-1) ........................................................................................................................ 1K6
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ............................................................................................................................... 3M7
Transport (IEC 60721-3-2) ..................................................................................................................................... 2M4
Long-term storage (IEC 60721-3-1) .................................................................................................................... 1M12
Connection
Connection type ...............................................................................................................................push-wire terminal
Nominal current ....................................................................................................................................................≤ 10 A
Conductor sizes .............................................................................................................................................AWG 24-14
Stripping length ................................................................................................................................................... 10 mm
rigid .........................................................................................................................................................0.2…2.5 mm
2
flexible without ferrules........................................................................................................................0.75…2.5 mm
2
flexible with ferrules with/without plastic sleeve...............................................................................0.25…2.5 mm
2
Multi-conductor flexible with TWIN ferrules with plastic sleeve..........................................................0.5…1.5 mm
2
Opening force........................................................................................................................................................... 50 N
Test opening, diameter....................................................................................................................................... 2.1 mm