Operation of the device
36
isoMIL425_D00203_03_M_XXEN/03.2019
5.4.4
Interface configuration
FAC
= Factory setting;
Cs
= User settings
( ) = User setting that is not modified by FAC.
Display
Setting value
Description
Range
FAC
Cs
Adr
0 / 3 … 90
3
( )
Bus-
Adr.
Adr = 0 deactivates BMS as
well as Modbus and
activates isoData with con-
tinuous data output
(115k2, 8E1)
Adr 1
--- /
“---“
( )
Baud
rate
“---“ : BMS bus (9k6, 7E1)
“1,2k“ … “115k“ -->
Modbus (variable, var.)
Adr 2
8E1
8o1
8n1
8n2
8E1
( )
Mo
dB
us
8E1
- 8 data bits
even parity, 1 stop bit
8o1
- 8 data bits
odd parity, 1 stop bit
8n1
- 8 data bits
no parity, 1 stop bit
8n2
- 8 data bits