Special functions for coupled IT systems
Special functions for coupled IT systems
isoHR685W-x-I-B_D00261_05_M_XXEN/12.2021
52
11.4.2.3 Transferring the configuration file to an ISOMETER®
The configuration file is installed via the web user interface of the iso685-x-P device in the
browser of a computer in the network. Proceed as follows:
1.
Apply a supply voltage to all correctly connected devices in the interconnection.
2.
Parameterise the Ethernet settings for all devices and check that the devices can
communicate via Ethernet.
3.
Parameterise the BCOM addresses created in the Group Manager for all devices
4.
Activate the ISOloop function on all devices
5.
Enter the IP address of the device to which you want to upload the configuration file
in the browser window.
6.
Navigate to the following menu item: "Device" > "Menu" > "Settings" > "File"
The following input window appears in the content area of the COMTRAXX® user
interface.
7.
Select target folder "group" (1.)
8.
Select file "grp_0102.cfg" in the corresponding folder of your source PC (2.)
9.
In the target path line (3.), the following must appear after the symbol:
\group\grp_0102.cfg
10. Start the upload by pressing the "Save" button (4.)
11. The configuration settings of the interconnection are automatically distributed after
completing the procedure.
All devices in the interconnection must be switched on
The ISOloop information is transferred from device to device according to
an address sequence defined in the configuration. Therefore, when uploa-
ding the configuration file, all devices in the interconnection must be swit-
ched on and connected to the network.
After completion, the file is available for download in the download area of each
device:
11.4.3 Configuration and function on the ISOMETER®
The ISOloop function is enabled or disabled in the menu at
Alarm settings -> ISO-
loop
. The function must be activated and configured for all ISOMETER®s in the system
that have to work synchronously.
To enable the devices in the ISOloop interconnection to communicate with each other,
the Ethernet settings (DHCP on or IP address, subnet mask and default gateway) must be
made in addition to the ISOloop function.
Menu
Alarm settings -> ISOloop
Activate ISOloop function
Menu
Alarm settings -> Inputs -> Digital input X
Select ISOloop as function
ISOloop function
If the ISOloop function is not activated before the Group Manager file is
uploaded, or if the devices do not have valid IP/BCOM parameters, the file
is not automatically distributed in the system.