Device communication
isoHR685W-x-I-B_D00261_05_M_XXEN/12.2021
47
Alarm message Insualtion fault
Brief overview
1
0 == No alarm
1 == Alarm 1
2 == Alarm 2
3 == Alarm 1 + Alarm 2
Number
0
5
-
-
Temperature in device
4
Temperature value preceeded by '+' or '-' sign
°C
+100
-
-
17
System frequency
3
0
Hz
123
-
-
18
Response value 1
6
R
F
kΩ
123456
2
-
19
Response value 2
6
R
F
kΩ
123456
3
-
20
System frequency
3
[ ' DC' | ' AC' | '3AC' ]
ATTENTION: Observe a blank space preceeding
AC and DC!
3AC
-
-
21
Relay (K1,K2) states
1
0 -> K1 == off, K2 == off
1 -> K1 == on, K2 == off
2 -> K1 == off, K2 == on
3 -> K1 == on, K2 == on
0
4
-
22
Impedance
6
Z
F
kΩ
1234.5
-
4
-
Unsymmetrical insulation resistance,
approximate
6
RUGF
kΩ
1234.5
-
9
-
Insulation measurement ADC value
5
ADC value in digits
12345
-
-
-
Active measuring profile
2
01 - Power circuits
02 - Control circuits
03 - Generator
04- High capacitance
05 - Inverter > 10Hz
06 - Inverter < 10Hz
07 - Custom-specific profile
08 - Service profile
Number
01
-
-
23
Frame counter
1
Counts continuously from 0 to 9.
1
-
-
24
String end
2
String end!
ATTENTION: Standard mode sent <LF><CR>,
i.e. the two characters are in reverse order!!!
ATTENTION
(String end)
sent(Standar
d mode)
<CR><LF>
+
+
+
Description
Length [Bytes] Value
Unit
Example string
Mode