Operation and setting
55
IRDH375_D00124_05_M_XXEN/01.2020
6.4.3 Memory setting (on/off)
Memory: on
= Fault memory is activated
The device must be reset with the RESET button after
clearing the fault.
Memory: off
= Fault memory deactivated (factory setting)
6.4.4 Current output for external measuring instruments
(IRDH375B)
Factory setting: 0…20 mA
The current output of the IRDH375 can be set to "0…20 mA" or "4…20 mA" via
the menu point "M+/M-:". The maximum load is 500 Ω.
Function 0…20 mA:
R
F
= insulation fault,
I
= current in mA
Function 4…20 mA:
R
F
= insulation fault,
I
= current in mA
The associated characteristic curves are illustrated on page 85.
During the automatic self test, the alarm relays are not
switched over.