Function
26
IRDH375_D00124_05_M_XXEN/01.2020
Function input F1/F2 for connection or disconnection of
IT systems being monitored
The ISOMETER® can be disconnected from the IT system and set to STANDBY
mode with the function input F1/F2. If the input F1/F2 is bridged, the connec-
tions L1/L2 are switched off via internal coupling relays, the measuring func-
tion is stopped and the message "STANDBY" appears on the display. Software
version 1.4 or higher does not indicate the measured insulation resistance
during the disconnection, but indicates the value > 10 MΩ. Furthermore, the
alarm relays and alarm LEDs no longer provide alarm messages. After opening
the function input F1/F2, the connection to the IT system will be restored and
a completely new measuring cycle for insulation monitoring is started.
With this function, selective disconnection of an IRDH375B in interconnected
IT systems can be carried out via auxiliary contacts of the respective coupling
switch. One coupling switch each in a line-type or ring-type arrangement can
deactivate a subsequent IRDH375B. This arrangement guarantees that only
one ISOMETER® is active in each galvanically connected system. In a ring-type
arrangement with all coupling switches closed, it can be assumed that all
ISOMETER®s are deactivated. In order to prevent this, a BMS Master (IRDH375B
BMS address 1) monitors the condition of the function input F1/F2 of all Slave
ISOMETER®s.
When all Slave ISOMETER®s are in the STANDBY mode, the insulation monitor-
ing function of the Master ISOMETER® and hence the function input F1/F2 of
the Master are without function in this mode.
Details are shown in the graphic below.
Summary of Contents for ISOMETER IRDH375
Page 37: ...Connection 38 IRDH375_D00124_05_M_XXEN 01 2020 1 2 ...
Page 61: ...Operation and setting 62 IRDH375_D00124_05_M_XXEN 01 2020 6 6 4 Diagram COM SETUP IRDH375B ...
Page 63: ...Operation and setting 64 IRDH375_D00124_05_M_XXEN 01 2020 6 7 2 Diagram PASSWORD ...
Page 68: ...Serial interfaces 69 IRDH375_D00124_05_M_XXEN 01 2020 ...
Page 93: ...Technical data IRDH375 B 94 IRDH375_D00124_05_M_XXEN 01 2020 ...
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ......