Serial interfaces
76
IRDH375_D00124_05_M_XXEN/01.2020
BMS bus address ranges
Addresses*
Device
Meaning
0
There is no device with address 0 !
Information sent to address 0 applies to all
devices connected to the interface (broad-
cast)
1
PRC1470
Control and indicating device
1…30
IRDH275B/
375B/575
Insulation monitoring device
1…30
COM465
Protocol converter
2…30
EDS47x-12
Insulation fault evaluators (localisation)
31…60
SMO480-12
Signal converter relay
61…90
EDS47xE-12
Insulation fault evaluators (localisation)
111…119
PGH47x
Test device for insulation fault location
121…150
PGH47xE
Test device for insulation fault location
Malfunctions due to wrong address assignment!
Assigning wrong addresses to external devices may cause
malfunctions. When assigning addresses, take care that
there are no gaps greater than five in the respective ranges
(1…30, 31…60, 61…90, 111…119 and 121…151) .