background image

8

IR423-D4_D00038_05_M_DEEN/06.2017

ISOMETER® IR423-D4

Bender GmbH & Co. KG

Tel.: +49 6401 807-0

E-Mail: [email protected]

Londorfer Str. 65 

 35305 Gruenberg 

• 

Germany

Fax: +49 6401 807-259

  www.bender.de

Alle Rechte vorbehalten. 
Nachdruck und Vervielfältigung 
nur mit Genehmigung des Herausgebers.
Änderungen vorbehalten!

©

 Bender GmbH & Co. KG

All rights reserved.

Reprinting and duplicating

only with permission of the publisher.

Subject to change!

©

 Bender GmbH & Co. KG

BENDER

 

Group

Mechanische Beanspruchung nach IEC 60721:
Ortsfester Einsatz (IEC 60721-3-3) ..........................................................................................  3M4
Transport (IEC 60721-3-2) .......................................................................................................  2M2
Langzeitlagerung (IEC 60721-3-1) ..........................................................................................  1M3
Anschluss .............................................................................................................. Schraubklemmen
Anschlussvermögen:
starr / flexibel / Leitergrößen AWG.............................  0,2…4 / 0,2…2,5 mm

2

 / AWG 24…12

Mehrleiteranschluss (2 Leiter gleichen Querschnitts):
starr / flexibel ......................................................................................  0,2…1,5 / 0,2…1,5 mm

2

Abisolierlänge..........................................................................................................................  8 mm
Anzugsdrehmoment .................................................................................................  0,5…0,6 Nm
Anschluss ..................................................................................................................  Federklemmen
Anschlussvermögen:
starr  ............................................................................................. 0,2…2,5 mm

2

 ( AWG 24…14)

flexibel ohne Aderendhülse ......................................................  0,75…2,5 mm

2

 (AWG 19…14)

flexibel mit Aderendhülse  .......................................................... 0,2…1,5 mm

2

 ( AWG 24…16)

Abisolierlänge........................................................................................................................  10 mm
Öffnungskraft ............................................................................................................................  50 N
Testöffnung, Durchmesser ...................................................................................................  2,1 mm

Sonstiges

Betriebsart..................................................................................................................... Dauerbetrieb
Einbaulage ............................................................................................................................ beliebig
Schutzart, Einbauten (DIN EN 60529) ....................................................................................... IP30
Schutzart, Klemmen (DIN EN 60529) ........................................................................................ IP20
Gehäusematerial..........................................................................................................  Polycarbonat
Entflammbarkeitsklasse ....................................................................................................  UL94 V-0
Schnellbefestigung auf Hutprofilschiene.......................................................................... IEC 60715
Schraubbefestigung ................................................................................... 2 x M4 mit Montageclip
Software-Version ...........................................................................................................  D248 V1.3x
Gewicht ..............................................................................................................................  ca. 150 g

Option W

Umgebungstemperatur ....................................................................................... -40 ºC…+70 ºC
Klimaklassen nach IEC 60721:
Ortsfester Einsatz (IEC 60721-3-3) (mit Betauung und Eisbildung) ......................................... 3K5
Mechanische Beanspruchung nach IEC 60721:
Ortsfester Einsatz (IEC 60721-3-3) ..........................................................................................  3M7

Bestellangaben ( B 7… =  Federklemmen)

Typ Versorgungsspg. 

U

s

*

Nennspg. U

n

Art.-Nr.

IR423-D4-1

AC 16…72 V, 30…460 Hz

AC 0…300 V, 30…460 Hz

B71016304

DC 9,6…94 V

B91016304

IR423-D4-2

AC/DC 70…300 V, 30…460 Hz AC 0…300 V, 30…460 Hz

B71016305
B91016305

IR423-D4W-1 AC 16…72 V, 30…460 Hz

AC 0…300 V, 30…460 Hz B71016304W

DC 9,6…94 V

B91016304W

IR423-D4W-2 AC/DC 70…300 V, 30…460 Hz AC 0…300 V, 30…460 Hz B71016305W

B91016305W

Montageclip für Schraubmontage (1 Stück je Gerät, Zubehör)

B98060008

*Absolutwerte des Spannungsbereichs

Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3)  .................................................................................................3M4
Transport (IEC 60721-3-2) .........................................................................................................2M2
Storage (IEC 60721-3-1) ............................................................................................................1M3
Connection...............................................................................................................  screw terminals
Connection properties:
rigid / flexible / AWG  .................................................  0.2…4 / 0.2…2.5 mm

2

 / AWG 24…12

Two conductors with the same cross section:
rigid / flexible ....................................................................................... 0.2…1.5 / 0.2…1.5 mm

2

Stripping length ......................................................................................................................  8 mm
Tightening torque, terminal screws ..........................................................................  0.5…0.6 Nm
Connection........................................................................................................ push-wire terminals
Connection properties:
rigid ............................................................................................. 0.2…2.5 mm

2

 ( AWG 24…14)

flexible without ferrules ............................................................ 0.75…2.5 mm

2

 ( AWG 19…14)

flexible with ferrules.................................................................... 0.2…1.5 mm

2

 ( AWG 24…16)

Stripping length ....................................................................................................................  10 mm
Opening force ............................................................................................................................. 50 N
Test opening, diameter ........................................................................................................  2.1 mm

Other details

Operating mode ..............................................................................................................  continuous
Position ..........................................................................................................................  any position
Degree of protection internal components (EN 60529) ........................................................... IP30
Degree of protection terminals (EN 60529)  ............................................................................. IP20
Enclosure material ....................................................................................................... polycarbonat
Flammability class.............................................................................................................. UL94 V-0
DIN rail mounting acc. to .................................................................................................. IEC 60715
Screw fixing ............................................................................................ 2 x M4 with mounting clip
Software version ............................................................................................................  D248 V1.3x
Weight ......................................................................................................................... approx. 150 g

Option W

Ambient temperature ..........................................................................................  -40 °C…+70 °C
Climatic categories acc. to IEC 60721:
Stationary use (IEC 60721-3-3) (with condensation and formation of ice)  ............................ 3K5
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3)  .................................................................................................3M7

Ordering details (B 7… = Push-wire terminals)

Type Supply 

voltage 

U

s

*

Nominal voltage U

n

Art. No.

IR423-D4-1

AC 16…72 V, 30…460 Hz

AC 0…300 V, 30…460 Hz

B71016304

DC 9,6…94 V

B91016304

IR423-D4-2

AC/DC 70…300 V, 30…460 Hz AC 0…300 V, 30…460 Hz

B71016305
B91016305

IR423-D4W-1 AC 16…72 V, 30…460 Hz

AC 0…300 V, 30…460 Hz B71016304W

DC 9,6…94 V

B91016304W

IR423-D4W-2 AC/DC 70…300 V, 30…460 Hz AC 0…300 V, 30…460 Hz B71016305W

B91016305W

Mounting clip for screw fixing (1 piece per device, accessories)

B98060008

*absolute value of the voltage range

Summary of Contents for ISOMETER IR423-D4

Page 1: ...R s muss auch dann akus tischund oderoptischwahrnehmbarsein wenndas Gerät innerhalb eines Schaltschrankes installiert ist GEFAHR VORSICHT VORSICHT Insulation monitoring device Intended use The IR423 ISOMETER monitors the insulation resistance of an un earthed AC system of 0 300 V to earth that is supplied by a mo bile generator according to DIN VDE 0100 551 The IR423 is suitable for AC systems wit...

Page 2: ...dead Observe the installation rules for live working DANGER schen IT System und Erde schließen den Messkreis Der aktuelle gemessene Isolationswiderstand wird auf dem Display des Geräts angezeigt Selbsttest automatisch Nach dem Zuschalten der Versorgungsspannung führt das Gerät einen Selbsttest durch Eventuelle Anschlussfehler oder Funkti onsstörungen werden ermittelt Durch den Selbsttest wird der ...

Page 3: ... of the generator clip erforderlich siehe Bestellinformation mittels Werk zeug in eine über das Gehäuse hinaus ragende Position Befestigen Sie danach das Gerät mit zwei M4 Schrauben 2 Verdrahten Sie das Gerät gemäß Anschlussplan Die Leitungen an KE und E sind getrennt zu führen Die Frontplattenabdeckung ist an der mit einem Pfeil gekenn zeichneten unteren Seite aufzuklappen Anschlussplan Anwendung...

Page 4: ...t Taste Starten eines Selbsttests 1 5 s Aufwärts Taste Menüpunkte Werte T Test button Starting a self test 1 5 s Up key menu items values R Reset Taste Löschen des Fehlerspeichers 1 5 s Abwärts Taste Menüpunkte Werte R Reset button deleting the fault memory 1 5 s Down key menu items values MENU Start des Menübetriebs 1 5 s Enter Taste 1 5 s Menü Untermenü Punkt Wert bestätigen 1 5 s zurück zur näc...

Page 5: ... be reached by pressing the MENU button for at least 1 5 seconds Werkseinstellung Preset Funktion Einstellen der Parameter Beispielhaft wird die Änderung des Alarm Ansprechwerts Ran2 R2 beschrieben So gehen Sie vor 1 Drücken Sie die Taste MENU Enter länger als 1 5 s Im Dis play erscheint das blinkende Kürzel AL 2 Bestätigen Sie mit Enter Der Parameter R1 blinkt 3 Drücken Sie die Abwärts Taste um d...

Page 6: ...connected system using a genuine earth fault e g via a suitable resistance Verzögerungszeiten einstellen Hiermit können Sie eine Ansprechverzögerung ton 0 99 s so wie eine Anlaufverzögerung t 0 10 s vorgeben Werkseinstellung herstellen und Passwort Schutz Mit Hilfe dieses Menüs können Sie den Passwort Schutz einschal ten das Passwort ändern oder den Passwort Schutz abschalten Zudem können Sie das ...

Page 7: ...nd Eisbildung 2K3 Langzeitlagerung IEC 60721 3 1 ohne Betauung und Eisbildung 1K4 Technical data IR423 D4 factory setting Insulation coordination acc to IEC 60664 1 IEC 60664 3 Rated insulation voltage 250 V Rated impulse voltage Pollution degree 4 kV 3 Protective separation reinforced insulation between A1 A2 L1 L2 E KE T R 11 12 14 21 22 24 Voltage test acc IEC 61010 1 2 2 kV Supply voltage Supp...

Page 8: ...1016305 B91016305 IR423 D4W 1 AC 16 72 V 30 460 Hz AC 0 300 V 30 460 Hz B71016304W DC 9 6 94 V B91016304W IR423 D4W 2 AC DC 70 300 V 30 460 Hz AC 0 300 V 30 460 Hz B71016305W B91016305W Montageclip für Schraubmontage 1 Stück je Gerät Zubehör B98060008 Absolutwerte des Spannungsbereichs Classification of mechanical conditions acc to IEC 60721 Stationary use IEC 60721 3 3 3M4 Transport IEC 60721 3 2...