22 CC613-Hxx_D00423_02_M_XXEN/11.2020
Technical data
6
Technical data
6.1
Tabular data
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Rated voltage ....................................................................................................................................................................................250 V
Overvoltage category ............................................................................................................................................. II (within terminal H)
Overvoltage category ................................................................................................................... III (terminal H and all other terminals)
Rated impulse voltage .............................................................................................................. 6 kV (terminal H and all other terminals)
Rated impulse voltage ..................................................................................................................................... 2.5 kV (within terminal H)
Double insulation acc. to OVC III between ...........................................................................................terminal H and all other terminals
Basic insulation acc. to OVC II .........................................................................................................................................within terminal H
Operating altitude .......................................................................................................................................................... ≤ 2000 m AMSL
Supply voltage (terminal B (0V, +12V))
Nominal voltage ........................................................................................................................................................................... DC 12 V
Operating range of the nominal voltage .................................................................................................................... DC 11.4 V…12.6 V
Max. nominal current ................................................................................................................................................................... 750 mA
Max. nominal current without USB load ....................................................................................................................................... 400 mA
Max. nominal current with max. USB load .................................................................................................................................... 750 mA
Residual direct current monitoring module (RDC-M, terminal A)
Measuring range ........................................................................................................................................................................... 100 mA
Response values:
Residual current I
Δn
.................................................................................................................................................................... DC 6 mA
Response tolerance I
Δn
.............................................................................................................................................................-50…0 %
Restart sequence value:
DC 6 mA ....................................................................................................................................................................................... < 3 mA
LED indications
STATUS (front panel) ................................................................................................. orange: power on/system not ready for operation
..............................................................................................................................................................................blue: system is starting
....................................................................................................................................green: system started, not ready for operation yet
.................................................................................................................... flashing green: system running, system ready for operation
........................................................................................................................................................................................red: system error
...................................................................................................................................................................................................................
Ethernet (terminal D) ..................................................................................................................................... off: no Ethernet connection
..................................................................................................................................... steady green: Ethernet connection at 100 Mbit/s
.............................................................................................................................................flashing green: data exchange at 100 Mbit/s
.......................................................................................................................................steady yellow: Ethernet connection at 10 Mbit/s
............................................................................................................................................. flashing yellow: data exchange at 10 Mbit/s
Data interface
USB host 1 (terminal C1). ............................................................................................................. USB port type A; USB 2.0 max. 250 mA
USB host 2 (terminal C2) ...............................................................................................................USB port type A; USB 2.0 max. 250 mA
Ethernet (terminal D) .............................................................................................................................................................10/100 Mbit
CONFIG (configuration interface, terminal F) .......................................................................................................micro USB port type AB
Modbus meter (terminal B) ...........................................................................................................................................................9.6 kBit
Control Pilot (terminal B (CP)) ........................................................................................................................................acc. to IEC 61851
Proximity Pilot (terminal B (PP)) ....................................................................................................................................acc. to IEC 61851