Modbus TCP server
28
CP9xx-Kit_D00399_00_M_XXEN/07.2019
5.2.2.9
R&U = Range and unit
The units of the bits 0 to 4 are coded.
Bits 6 and 7 describe the validity range of a value. Bit 5 is reserved.
The complete byte is calculated from the sum of the unit and the range of validity.
Attention!
If the unit byte refers to CODE, the recorded value or status will result in a text message. The content of this text
message is listed in the table on Seite 29 or Seite 31. The floating point value contains an internal CODE but no
valid measured value.
Bit
7
6
5
4
3
2
1
0
Meaning
Unit
X
X
X
0
0
0
0
0
Invalid (init)
X
X
X
0
0
0
0
1
No unit
X
X
X
0
0
0
1
0
Ω
X
X
X
0
0
0
1
1
A
X
X
X
0
0
1
0
0
V
X
X
X
0
0
1
0
1
%
X
X
X
0
0
1
1
0
Hz
X
X
X
0
0
1
1
1
Baud
X
X
X
0
1
0
0
0
F
X
X
X
0
1
0
0
1
H
X
X
X
0
1
0
1
0
°C
X
X
X
0
1
0
1
1
°F
X
X
X
0
1
1
0
0
Second
X
X
X
0
1
1
0
1
Minute
X
X
X
0
1
1
1
0
Hour
X
X
X
0
1
1
1
1
Day
X
X
X
1
0
0
0
0
Month
X
X
X
…
…
…
…
…
Reserved
X
X
X
1
1
1
1
0
CODE
X
X
X
1
1
1
1
1
Reserved
X
X
X
…
…
…
…
…
Reserved
X
X
X
1
1
1
1
1
Reserved
Ran
g
e
of
va
li
d
it
y
0
0
X
X
X
X
X
X
Actual value
0
1
X
X
X
X
X
X
The actual value is lower
1
0
X
X
X
X
X
X
The actual value is higher
1
1
X
X
X
X
X
X
Invalid value
Summary of Contents for B95061094
Page 8: ...Important information 8 CP9xx Kit_D00399_00_M_XXEN 07 2019...
Page 10: ...Safety instructions 10 CP9xx Kit_D00399_00_M_XXEN 07 2019...
Page 14: ...Product description 14 CP9xx Kit_D00399_00_M_XXEN 07 2019...
Page 22: ...Installation connection and commissioning CP9xx Kit 22 CP9xx Kit_D00399_00_M_XXEN 07 2019...