FEATURES

• Indicator lights visible without removing cover.

Power LED will illuminate when input power is applied to the

controller. Zone LEDs will illuminate when relay is energized.

• PRIORITY: This is typically used in domestic hot water

applications where it may be desirable to give hot water

production a priority over space heating requirements for a

certain period of time. Zone 1 is the priority zone and the

functionality is enabled via DIP switch 1. The priority timer is

selectable for 30 or 60 minutes, via DIP switch 3.

• PURGE: In normal operation, the last circulator will stop and

the boiler will shut down as soon as there is no longer a call

for heat. If the purge functionality is enabled via DIP switch

2, the boiler will shut down, but the circulator will continue

to run for 90 seconds to extract additional BTUs from the

boiler.

• EXERCISE: When the exercise functionality is enabled via

DIP switch 4, each circulator will run for 10 seconds after

every 72 hours of inactivity. This prevents scale and other

deposits from accumulating around the rotating parts and

ensures a trouble free start up at the beginning of each

heating season.

DESCRIPTION

The Bell & Gossett ZoneTrol II and McDonnell & Miller Zone-

Smart Pump Controllers are designed to control 120 VAC

circulating pumps in hydronic systems.

Max.

T-stat

Number of

Max.

Model

Current

Zones

HP/Pump

Z-4 / ZS-4

0.085

4

1/3

Z-6 / ZS-6

6

Bell & Gossett

®

ZoneTrol II

Models Z-4, Z-4B, Z-4M, Z-6, Z-6B, Z-6M

McDonnell & Miller ZoneSmart

Models ZS-4, ZS-4B, ZS-4M, ZS-6, ZS-6B, ZS-6M

SAFETY

INSTRUCTION

This safety alert symbol will be used in this manual and on the

unit safety instructions decal to draw attention to safety related

instructions. When used, the safety alert symbol means

ATTEN-

TION! BECOME ALERT! YOUR SAFETY IS INVOLVED!

FAILURE TO FOLLOW THE INSTRUCTIONS MAY RESULT

IN A SAFETY HAZARD.

INSTALLER:

PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

DIP SWITCH SETTINGS

Switch

ON

OFF

1

Slave

Master

Priority Off

Priority On

2

Purge On

Purge Off

3

Priority 30 minutes

Priority 60 minutes

4

Exercise On

Exercise Off

5

Reset

Normal

6

Power Delay On

Power Delay Off

OUTDOOR RESET

For controllers with intergal outdoor reset controller,

please  refer to Instruction  Manual 210668. This document

can be downloaded at www.bellgossett.com or

www.mcdonnellmiller.com.

MECHANICAL INSTALLATION INSTRUCTIONS

The pump controller should be securely mounted on a wall

near the pumps using four #8 screws (not included).

ELECTRICAL INSTALLATION INSTRUCTIONS

1. Disconnect the electrical supply to the pump before

installing the controller.

2. Refer to the applicable wiring diagram

- Figure 1A: Cold Start Boiler

- Figure 1B: Tankless Coil

3. Verify that the circulator(s) do not exceed the electrical rat-

ing of the controller.

WARNING: Electrical Shock Hazard

Electrical connections are to be made by a qualified

electrician in accordance with all applicable codes, ordi-

nances and good practices Disconnect and lock out the

power before making electrical connections. Failure to fol-

low these instructions could result in serious personal injury

and/or death.

UL

®

C

US

LISTED

20 amps maximum combined load.

INSTRUCTION MANUAL 

210667C