background image

For connection

of additional

controllers

Used only with optional reset

control - refer to

instruction

manual 210668

for details

To

thermostats

}

Input Power

120/1/60

To zone

circulators

Refer to Fig 1A for cold start or

Fig. 1B for tankless coil application

EXPANSION

BOIL OUT SUP COM

H

N

24 VAC

R W

ZONE 1

ZONE 1

L N

ZONE 2

L N

ZONE 3

L N

ZONE 4

L N

ZONE 5

L N

ZONE 6

L N

R W

ZONE 2

R W

ZONE 3

R W

ZONE 4

R W

ZONE 5

R W

ZONE 6

THERMOSTATS

INSOLATED END

SWITCH

X

X ZC ZR

120 VAC

L

N

G

CIRCULATORS

}

To TT

on boiler

Jumper

X

X ZC ZR

ZC

ZR

To ZC on

aquastat

To ZR on

aquastat

GENERAL WIRING DIAGRAM

Refer to Instruction Manual 210688 for units with outdoor reset controller.

Figure 1A: Cold Start Boiler

When a thermostat calls for heat,

the corresponding circulator will

start and the XX end switch will

close to enable the boiler.

Figure 1B: Tankless Coil

When a thermostat calls for heat,

the corresponding circulator will

start when the boiler temperature

reaches the low limit setting.

General Wiring Diagram

(6 zone controller shown)

WARNING: Electrical Shock Hazard

When wiring per the Tankless Coil

Application, pump controller and boiler

aquastat must be on the same circuit and

have a common disconnect. Failure to fol-

low these instructions may introduce a

secondary source of power resulting in

personal injury or death.

4. Make electrical connections according to the applicable

wiring diagram. Run the pump power through the holes in

the controller chassis to the applicable L/N terminals. Keep

120 VAC and 24 VAC wiring separate. All 120 VAC wiring

should be 14 AWG (minimum) copper electrical wire.

Perform all wiring in accordance with applicable codes.

5. If the priority function is to be enabled, the priority zone

(e.g., Domestic Hot Water) pump should be wired to the

Zone 1 L/N terminals.

6. Run the thermostat wires through the grommet(s) in the

controller chassis and connect to the appropriate R/W ter-

minals. If the priority function is to be enabled, the priority

zone (e.g., Domestic Hot Water) T-Stat should be wired to

the Zone 1 R/W terminals. Keep 24 VAC wiring separate

from 120 VAC wiring.
NOTE: During the initial power-up of the zone controller,

some “power stealing” thermostats may require up to 3

minutes to function properly. If the installation requires the

pump relays and X-X relay to be held open during this

power-up sequence, the installer can position DIP switch

6 to the “ON” position. This will cause the controller to

suspend relay operation during the thermostat power-up

period. Normal operation and cycling of the heating system

will resume after the 3 minute time period. This applies to

initial power-up only and does not affect normal system

operation.

EXPANSION

The 4 and 6 zone controllers can be connected together to

accommodate larger systems. A six conductor straight pinned

cable with two male RJ-11 terminations is required for con-

nection of multiple controllers. This cable can be ordered from

your distributor as McDonnell & Miller part number 109454.
The “master” controller should have DIP switch 1 set to the

OFF position. “Slave” controllers should have DIP switch 1 set

to the ON position. If the Priority function is to be enabled

(e.g., domestic hot water production) Zone 1 on the Master

controller will be the priority zone.

Xylem Inc.

 

8200 N. Austin Avenue 

Morton Grove, Illinois 60053 

Phone: (847) 966-3700 

Fax: (847) 965-8379

www.xyleminc.com/brands/bellgossett

Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries. 
© 2012 Xylem Inc.  210667C  May 2012

Reviews: