Specifications (USB Series)

19

INPUT

Capacity 350VA(227W)

500VA(300W)

650VA(390W)

Voltage

187 Vac - 280 Vac

Frequency 50Hz 

or 

60Hz 

±

3Hz (auto sensing)

OUTPUT

Voltage Simulated 

sine 

wave, 

230 

Vac

±

8% 

(on battery)
Frequency 50Hz 

or 

60Hz 

±

1Hz

(on battery)

MODEL

350VA

500VA

650VA

Voltage 
Regulation
AVR

Smart boost increases 14.8% of voltage if input is 213 to 187 Vac. 

Smart trim reduces 12.8% of voltage if input is 247 to 288 Vac

UPS output cut off immediately or input breaker protection

Transfer Time

< 4 milliseconds, including detection time

Spike Protection

PROTECTION
AND FILTERING

Overload Protection

Modem/Network

Single Line (2 Wire, RJ11) Network (UTP, RJ45) compatible
jacks, one input/two output

Unit Input

Breaker for overload and short circuit protection

UPS automatic shutdown if overload exceeds 130% in AC
mode and 100% in back-up mode. UPS alarms continuously
in > 107% or <130% in AC mode.

Short Circuit

Depending on computer load...

Type

Protection

Automatic self-test and discharge protection,
replace battery indicator

Typical
Recharge Time

4 hours (to 90% of full capacity)

Sealed, maintenance-free lead acid 

BATTERY

PHYSICAL

ALARM

ENVIRONMENT

INTERFACE

CONFORMANCE

Full/half load

Back up Time

Net Weight
Dimension 
(mm) WDH
Input inlet 
Output outlet (UPS)

289 x 243 x 325 

5.5kg/12.3lbs.

5-20 min

5-30 min.
6kg/13.23lbs

5-45 min

10A/250V*1pcs, EN60320

10A/250V*4pcs; ENG60320/F
10A/250V*4pcs; ENG60320/F

Output outlet
(Bypass)
Battery Back-Up

Slow beeping sound (about 15 sec. interval)
Rapid beeping sound (about 1 sec. interval)

Battery Low
Overload
Fault
Battery test
USB Interface
Safety
Surge
Ambient operation
Audible noise

Continuous beeping sound (about 1 sec. interval)
10 sec. beeping sound continuously
Slow beeping sound (about 15 sec. interval)

-15

°

C – 40

°

C (with battery)

-15

°

C – 70

°

C (without battery)

USB Port
CE, TUV/GS, TUV/EMC,EN5009-1-1-1, EN50091-2, EN50082-1
Meet IEEE C62.41. Category A standard
0~95%, humidity non-condensing, 0~40

°

<40dBA (1 meter from surface)

150 Joules

6.5kg/14.33lbs.

Storage condition

En

P73220uk_Gold_UPSMan  27-05-2002  15:02  Page 19

Summary of Contents for F6C325-220V

Page 1: ...En P73220uk UPS Uninterruptible Power Supply User Manual P73220uk_Gold_UPSMan 27 05 2002 15 01 Page 1...

Page 2: ...the proper operation of the UPS come into question Please save or recycle the packaging materials The UPS shipping materials were designed with great care to provide protection from transportation re...

Page 3: ...nt Panel 6 Rear Panel 7 5 Installation 9 6 Operation 10 7 Alarm 11 8 Software Options 11 9 USB Interface Port 12 10 RS232 Interface Port 14 11 Battery Replacement 15 12 Troubleshooting 17 13 Storage 1...

Page 4: ...incur computer repairs lost data and downtime Solution A Belkin Uninterruptible Power Supply UPS with Automatic Voltage Regulation AVR Typical Stand by UPS units do not have AVR to increase the output...

Page 5: ...ible shock from touching two surfaces with different electrical grounds Connect the equipment to a three wire AC outlet two poles plus ground The receptacle must be connected to an appropriate circuit...

Page 6: ...s Battery output is drawing more power than the UPS can provide 4 3 REPLACE BATTERY Red Battery is too weak or bad If UPS is in On Battery mode this means the UPS is just testing the condition of the...

Page 7: ...sential equipment and reset the circuit breaker 4 10 BATTERY BACK UP OUTLETS Data sensitive equipment such as a computer monitor and external drive should be powered by these outlets Battery power is...

Page 8: ...tery Back up outlets 4 5 Interface Port USB or RS232 Depending on model 4 6 Telephone Fax Modem or 10 base T network Protection 4 7 Battery Replacement Door 4 9 AC Breaker Circuit Breaker 4 8 AC Input...

Page 9: ...Belkin Components for details of a local reseller 5 4 Connect Computer Interface Belkin Sentry Bulldog Shutdown Management Software and the USB or RS232 cable depending on model can be used with this...

Page 10: ...on when the UPS is supplying power to the connected loads The UPS can be utilised as a master on off switch for the protected equipment NOTE The UPS maintains the battery charge when in the off positi...

Page 11: ...Belkin Sentry Bulldog Shutdown Management Software or as stated in step 6 3 The alarm stops when the UPS returns to line normal operation 7 1 LOW BATTERY rapid alarm In backup mode when the battery en...

Page 12: ...up procedure Charge the UPS 2 4hours before installing the software Connect the supplied RS232 serial cable excluding 325VA Series to the UPS and connect the other end to a designated port on the PC T...

Page 13: ...n For Alarm 10 Voltage Sensitivity To Improve Transfer Time and Avoid Effect Of I P Distortion 11 Outlet Relay ON OFF Set Delay Time to Control Outlet Relay On Off 12 Next Shutdown Time To Next Schedu...

Page 14: ...condition 3 Monitoring inverter status 4 Monitoring UPS status 5 Monitoring the utility status 6 Providing the power switch function for the computer to turn on off the utility on schedule To save po...

Page 15: ...e battery compartment cover down Diagram b 11 1 3 Grasp the battery and slide it partially out Then grab the battery firmly and remove the battery wires will disconnect as the battery is pulled out Di...

Page 16: ...contact Belkin Components Diagram a Diagram b Slide the battery compartment cover Diagram d Slide the battery back in Avoid pinching the wires Diagram c Slide the battery partially out Diagram e Slid...

Page 17: ...g the power cord Replace the breaker Normal condition Recharge the UPS at least 4 hours Remove some unnecessary loads Replace battery Remove the non critical loads Replace battery 13 0 Storage Conditi...

Page 18: ...ad Type Protection Automatic self test and discharge protection replace battery indicator Typical Recharge Time 4 hours to 90 of full capacity Sealed maintenance free lead acid BATTERY PHYSICAL ALARM...

Page 19: ...load Type Protection Automatic self test and discharge protection replace battery indicator Typical Recharge Time 4 hours to 90 of full capacity Sealed maintenance free lead acid BATTERY PHYSICAL ALAR...

Page 20: ...SET FORTH ABOVE ARE EXCLUSIVE IN LIEU OF ALL OTHERS WHETHER ORAL OR WRITTEN EXPRESSED OR IMPLIED BELKIN SPECIFICALLY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES INCLUDING WITHOUT LIMITATION WARRANTIES O...

Reviews: