Sequence 

 

a) 

Test start ‘Check system supply pressure’ 

 

- [System test: Setp

oint V’mid]   

 

- Actual value zero [m

3

/h] / [l/s] 

 

- Damper 100% open 

 

 
 

N-P1.7  VAV- / CAV-Box

..........................................................................................

wrong direction of rotation 

 

Suggestion for a remedy 

 

a) 

Check  direction  of  rotation  (‘Service’  register 
‘OPEN’ or ‘CLOSE’ operation) 

 
b)  Correct direction of rotation or mount the actuator 

correctly (note the mark on the damper blade)  

 

Suitable Test-Sequences 

 

BasicTest Max-Min 5m.txt

 

 

 

Note:   
The Test-Sequence is discontinued because of the lack of system 
supply pressure. Fault alarm: ‘Inadequate supply air pressure’ is given.   

Possible faults 

 

- Incorrect direction of rotation 

- NMV-D2M shaft connector and damper spindle 

installed with offset  (90°) 

 

A
A

D
A

Sequence 

 

a)  Step 1:  Damper open  (uncontrolled) 
 

- Volumetric flow already very high when the 

damper is only slightly open ! 

 

- Damper 20...100% open 

 

b) 

Step 2:  V’max 

 

- Actual value not reaching setpoint 

 

- Damper apparently 100% open 

 

c) 

Step 3:  V’min 

 

- Volume increases despite the damper closing 

and being clearly above the setpoint ! 

 

- Damper in control range 

 

d)  Step 4:  Damper closed 
 

- Actual value: Volumetric flow present despite the 

damper apparently being closed ! 

 

- Damper appears to be closed 

Suggestion for a remedy 

 

Remove the NMV-D2M and match the closed position 
correctly to that of the closed damper blade.

 

Suitable Test-Sequences 

 

Test 0 CAV (Open-Max-Min-Close) 8m.txt 

 

 
Note:   
If the system does not attain the required supply pressure 

– during the 

Test start 

– the Test-Sequence is discontinued and the fault alarm ‘In-

adequate supply air pressure’ is given.  

 

The spindle is fitted with clear offset in order to record this symptom. As 
a result different values of offset can occur on-site in this situation.   

Possible fault 

 

0° position of the actuator does not correspond to that 
of the closed damper blade. This produces offset, i.e. 
the  damper  remains  open  although  the  actuator  is 
closed. When  the  actuator is 100% open  the damper 
is already moving back in the ‘Close’ direction (90°). 

 

N-P1.8  VAV- / CAV-Box

.................................................................

leakage air with VAV controller closed 

 

A
A

D
A

 

NMV-D2M 

– Diagnosis

Summary of Contents for NMV-D2M

Page 1: ...4 A1 PC T V2 1 NMV D2M 11 02 04 EN PC Tool Module NMV D2M V2 1 O E M 3 5V VDC...

Page 2: ...following de tail information Please contact your local Belimo agent or representative for more infor mation and the latest VAV documentation All Belimo product documentation in pdf format can be down...

Page 3: ...Print CTRL P N A4 1 Addressing F2 N A4 2 Address setting PP MP N A4 2 1 Methods of addressing N A4 2 2 by manual disengagement button N A4 2 3 according to serial number N A4 2 4 Reset to OEM setting...

Page 4: ...ion of the elements N S4 1 Live trend N S4 2 Start Stop N S4 2 1 Selecting the operating step N S4 2 2 Voltage readings in Live Trend N S4 2 3 Trend file N S4 3 File name N S4 3 1 Storage directory pa...

Page 5: ...rating step control systems than the standard NMV D2M The technical documentation provided by the manufacturers of the air boxes should be given close attention N A 1 2 Support for VAV Compact NMV D2...

Page 6: ...rom installation AC24 V ZIP RS232 1 2 5 OFF Actuator RS232 ON U PP T Belimo PC Tool Cable from kit ZIP RS232 NMV D2M AC 230 V ZN230 24 Cable from kit ZKS VAV b Power supply AC DC 24 V Duplicated NMV D...

Page 7: ...s cable MP Bus Cable from kit ZIP RS232 Cable from kit ZIP RS232 Belimo PC Tool MP MP 8 MP 1 MP AC 230 V ZN230 24 AC24V ZIP RS232 1 2 5 OFF Actuator RS232 ON U PP T UK24LON BELIMO 2 Connecting PC Tool...

Page 8: ...NMV D2M controller The functions are shared between the two Service and Expert registers de pending on the particular application In addition to these two registers the module also offers users a vari...

Page 9: ...s assigned to NMV D2M F2 Options General Language Select program language Com Port Set communication Port 1 4 Module release Activate special functions only for manufacturers MFT PC Actuator password...

Page 10: ...The settings of operating flow rate programmed by the manufacturer V min V mid and V max are flagged by the so called seal bit If any of these values are adjusted on site it will be indicated by the...

Page 11: ...control active e g CAV Close step N A3 2 9 Select required actuator bus mode Open address window Select required address e g MP4 The selected active communication link is shown in the actuator identif...

Page 12: ...ation Type OEM info Position Serial number MP address Version designation NMV D2M controller settings Mode Operating flow rate setting calibration value V nom V max V mid V min Direction of rotation T...

Page 13: ...ddressing for PP Bus mode setting MP Multi Point Address MP1 MP8 is selected when several NMV D2M s or other Be limo MFT 2 actuators are incorporated into a higher level system via the MP Bus In this...

Page 14: ...number Enter the serial number by hand or bar code reader When there is a direct link to the actuator the serial number read from the NMV D2M appears as the default value Press OK An appropriate sign...

Page 15: ...ave been exe cuted from the appropriate PC can be displayed on the PC Tool and be printed out if necessary without an active connection to the NMV D2M N A5 1 Log data Description of the elements Log D...

Page 16: ...ipped with an NMV D2M can be printed out directly from the display screen mask for documentation purposes Display screen mask zoom function change entry Mouse Click on or Keyboard Use TAB to focus on...

Page 17: ...Direction of rotation open Direction of damper rotation Actuator setting MP Address NMV D2M address setting Mode Mode setting 0 10 2 10 V Setpoint w variable setting setpoint signal w Volumetric flow...

Page 18: ...d function is provided so that the control parameters of a VAV CAV box equipped with a Belimo VAV Compact NMV D2M can be checked An overall analysis of these values will show the system supply pressur...

Page 19: ...used an entry is made in this field for each trend and test recording If this function is not being used a default name is used instead N A7 2 Procedure Project data must be entered before execution...

Page 20: ...ry for NMV D2M log data The NMV D2M log files are stored in the selected directory N A8 5 Trend data path selection Destination directory for NMV D2M Trend and Test data All NMV D2M tnd files are stor...

Page 21: ...riginally set during installation of the equipment These settings are made by the manufacturer of the air boxes who also bears overall responsibility for their proper functioning Any incorrect changes...

Page 22: ...a connected switch reliably the start point of the working range must be properly set first Start point DC 0 6 V It is essential for the Start Point to be set to 0 6 V Stop point DC 10 V Reference si...

Page 23: ...n for further information N E2 3 Direction of rotation damper opening Depending on the design of the air box the manufacturer sets the direc tion of rotation of the damper accordingly The direction of...

Page 24: ...e min 8 Nm 75 75 of active torque ca 6 Nm 50 50 of active torque ca 4 Nm 25 25 of active torque ca 2 Nm N E3 5 NMV D2M versions information Indication of the version of software and the configuration...

Page 25: ...l value of volumet ric flow Range of adjustment 30 100 V nom V min V min is the lower limit value depending on the maximum value of volu metric flow Range of adjustment 0 100 V max Range of control x...

Page 26: ...t influenced by the V nom V max ratio The smaller the V max setting the bigger gets the influence of the physical control limita tion to the usable control range width Below you ll find a chart showin...

Page 27: ...me h x 100 If the Stop Go ratio is relatively high an unstable reference signal is a possible cause N S2 5 Calibration value A setting for a specific air box that the manufacturer of the unit has asce...

Page 28: ...tion is active PC status Operation active NMV D2M status the preset operating step N S3 4 Local override control In order to ensure active local override control these local commands are given a highe...

Page 29: ...Variable Status Variable operation V min V max Issue of the setpoint for volumetric flow as an absolute value e g in m3 h or as a relative value in Range operating volumetric flow setting V min V max...

Page 30: ...on the screen in real time With the latter data that has been recorded previously is read from the data carrier and displayed on the screen N S4 1 Trend Description of the elements Project controller...

Page 31: ...2 2 Selecting the operating step Simultaneous display of the two windows allows the volumetric flow rate to be changed while a trend is being recorded so that the resulting system response can be obs...

Page 32: ...ectory of the PC Tool program directory VAVTrend User defined path The user can select the destination directory in the EXTRAS OP TIONS NMV D2M menu All trend files are then stored in that direc tory...

Page 33: ...ail displays etc highlight the required trend file and right clicking on it will open a list with available options Print Trend data Two options can be used Print Print actual Trend file Multi Print s...

Page 34: ...n with the STOP button by interrupting communication by local initiation of synchronising or adaption The TEST function cannot be started when OPERATION or LIVE TREND is activated Test report As with...

Page 35: ...trend display will normally be the same as that from Live Trend See N S4 1 Trend Description of the elements The input file defined Test Sequence and output file Test log are im portant for the test...

Page 36: ...1 Max 3m txt Function System check V max 180 s Duration Check 1 x 180 s ca 3 4 minutes Test 2 Max Auto 6m txt Function System check V max 180 s Auto reference input w active 180 s Duration Check 2 x 1...

Page 37: ...1 OG ZUL_12 04 2002_Test_a tnd Storage directory path Default As a subdirectory of the PC Tool program directory VAVTrend User defined path The user can select the destination directory in the menu EX...

Page 38: ...y pressure 5 VAV CAV excessive system supply pressure 6 VAV CAV oversized air box 7 VAV CAV wrong direction of rotation 8 VAV CAV leakage air with VAV controller closed 9 VAV unstable reference signal...

Page 39: ...es Test 3 Max Auto Min 9m txt or BasicTest Max Min 5m txt without Auto Step NMV D2M Diagnosis a b c S A D A Suitable Test Sequences Test 0 CAV Open Max Min Close 8m txt Test 4 Max Mid Min 9m txt Basic...

Page 40: ...x Volumetric flow does not reach setpoint Damper 100 open c Step 2 V min Volumetric flow at setpoint Damper in control range Suggestion for a remedy 1 Increase supply pressure increase pressure contro...

Page 41: ...CAV Box oversized air unit Sequence a The setpoint is reduced in 1 steps b Setpoint less than active differential pressure 2 Pa NMV D2M function Leakage flow suppression activated c Setpoint less than...

Page 42: ...g setpoint Damper apparently 100 open c Step 3 V min Volume increases despite the damper closing and being clearly above the setpoint Damper in control range d Step 4 Damper closed Actual value Volume...

Page 43: ...hat the damper actuator is in constant motion So an adverse effect on service life is an inevitable consequence Pressure control is affected and as a result also the remaining VAV boxes in the same se...

Page 44: ...g volumetric flow V min Reaction terminal 3 open Damper closed Damper open check Possible cause a V min setting 0 b V min setting gives active pressure below 2 Pa Creep flow suppression active try V m...

Page 45: ...or still stationary Level 3 Function Check Continue with whole system test if necessary Contact the manufacturer Possible cause Damper blade jammed check free movement of damper by hand correct the fa...

Page 46: ...r calculating area Area circle A 0 785 x d2 Area rectangle A l x b Formulae for calculating volumetric flow Volumetric flow m3 h A m2 x V m3 x 3600 Formulae for calculating velocity Velocity m s Volum...

Page 47: ...47 4A1PC T V2 1 NMV D2M EN 11 02 04 doc PM VAV Subject to technical changes VAV Module NMV D2M Notes...

Page 48: ...48 4A1PC T V2 1 NMV D2M EN 11 02 04 doc PM VAV Subject to technical changes VAV Module NMV D2M...

Reviews: