VAV
– Module NMV-D2M
Connect via safety
isolating transformer
N-A4.2 Addressing <F2>
Conventional mode address: PP
When several NMV-
D2M’s or MFT(2) actuators communicate over the
MP-Bus they must be clearly identifiable.
Bus mode address: MP1...MP8
N-A4.2.1 Address setting PP / MP
-
Conventional mode setting ‘PP’
(
P
oint-to-
P
oint)
The ‘PP’ address is selected when an NMV-D2M under conventional con-
trol is connected to the PC-Tool.
See Connection diagram N-A2.1 and N-A2.2.
When an NMV-D2M is add
ressed ‘PP’ it is automatically assigned pa-
rameters for conventional mode.
For VAV, modulating control is effected with 0/2...10 V DC or, for CAV, by
means of step control. The signal for the actual value of volumetric flow
U5 is available at Terminal 5.
An NMV-D2M set for bus mode (MP) can be reset for conventional control
by addressing for ‘PP’.
-
Bus mode setting ‘MP’
(
M
ulti-
P
oint)
Address ‘MP1...MP8’ is selected when several NMV-D2M’s or other Be-
limo MFT(2) actuators are incorporated into a higher level system via the
MP-Bus. In this case the connection is always made at the bus interface,
e.g. UK24LON and never directly to the communication socket of the
NMV-D2M.
See Connection diagram N-A2.3.
If an NMV-
D2M is given an MP address ‘MP1...MP8’ it will automatically
be assigned parameters for MP-Bus operation. In this case control is ef-
fected digitally over the MP-Bus.
N-A4.2.2 Methods of addressing
The screen mask for addressing the NMV-D2M is called from the menu,
the toolbar or the <F2> function key.
There are two methods available:
- Addressing by manual disengagement push-button
- Addressing according to serial number
MP
~
T
+
_
AC 24 V
DC 24 V
5
3
2
1
NMV-D2M
U
MP
w
~
T
+
_
5
3
2
1
NMV-D2M
U
MP
w
~
T
+
_
Further
NMV-D2M or
MFT2 actuators
UKK24LON
or
DDC with MP-Bus interface
5
3
2
1
NMV-D2M
U
MP
w
~
T
+
_
Reference value input w
Actual volumetric flow signal U
5
PP-Communication Tool
T
AC 24 V
~
T
DC 24 V
+
_
Addressing <F2>
!