VAV
– Module NMV-D2M
N-E3 Actuator settings
N-E3.1 Adaption
For adapting the control characteristics to the available range of control.
Setting
Function
Remarks
Manual (2x)
Adaption is initiated by
Recommended
2x press manual disengagement button
setting
Off
Adaption deactivated
Automatic
Adaption initiated:
(Power ON
- after each power off
and manual (2x))
- 2x press manual disengagement button
N-E3.2 Synchronisation
Initiation criteria for synchronising the position calculation.
Setting
Function
Remarks
at 0% manual (1x)
Synchronising at Closed position
Recommended
- at first commissioning
setting
- when manual disengagement button
at 0% manual (1x)
Synchronising at Closed position
and Power ON
- at each power-up
- at power fail
- when manual disengagement button
at 100% manual (1x)
Synchronising at Open position
and Power ON
- at each power-up
- at power fail
- when manual disengagement button is pressed
N-E3.4 Torque
Adapting the maximum value of torque to suit the type of air box being
used.
Step
Function
Torque
100%
Rated active torque
min.
8 Nm
75%
75% of active torque
ca.
6 Nm
50%
50% of active torque
ca.
4 Nm
25%
25% of active torque
ca.
2 Nm
N-E3.5 NMV-D2M versions information
Indication of the version of software and the configuration table currently
being used in the controller.
- Firmware
: Software version (Hex-Code)
- Config. Table ID
: Configuration table (Hex-Code)
N-E4 Adaption
With this function it is possible to acquire the positions of the upper and
lower damper end-stops and store them in the NMV-D2M. Running time
and working range are then adapted to the available angle of rotation. As-
certaining the positions of the mechanical end-stops allows a smooth ap-
proach to the end-stops so preventing any unnecessary overloading of
the actuator and damper mechanisms.
Actuator setting
An incorrect actuator setting can cause the air box to
malfunction or even to be damaged.
For this reason the settings should only be changed
after prior consultation with the manufacturer.
!
Support enquiries
– Versions information
The versions data is stored in the log file by the log
function each time information is read. It can be
displayed with the ‘Read log data’ function <F3>.
This information should always be given in response
to an enquiry.
Adaption behaviour
The adaption behaviour can be adjusted to suit
particular applications, see N-E3.1