Technical data sheet

NF24A-MOD

www.belimo.com

NF24A-MOD • en-us • 2022-03-15 • Subject to change

6 / 7

Quick addressing

Service tools connection

Operating controls and indicators

Membrane key and LED display green

Off:

No power supply or malfunction

On:

In operation

Flashing:

In address mode: Pulses according to set address (1...16)
When starting: Reset to factory setting (Communication)

Press 
button:

In standard mode: Triggers angle of rotation adaptation
In address mode: Confirmation of set address (1...16)

Membrane key and LED display yellow

Off:

Standard mode

On:

Adaptation or synchronisation process active
or actuator in address mode (LED display green flashing)

Flickering:

BACnet / Modbus communication active

Press 
button:

In operation (>3 s): Switch address mode on and off
In address mode: Address setting by pressing several times
When starting (>5 s): Reset to factory setting (Communication)

Service plug
For connecting parametrisation and service tools

Operating elements
The manual override, locking switch and direction of rotation switch elements are 
available on both sides

Service

1. Press the "Address" button until the green "Power" LED is no longer illuminated. LED flashes 
in accordance with the previously set address.
2. Set the address by pressing the "Address" button the corresponding number of times (1...16).
3. The green LED flashes in accordance with the address that has been entered (...16). If the 
address is not correct, then this can be reset in accordance with Step 2.
4. Confirm the address setting by pressing the green "Adaptation" button.
If no confirmation occurs for 60 seconds, then the address procedure is ended. Any address 
change that has already been started will be discarded.
The resulting BACnet MS/TP and Modbus RTU address is made up of the set basic address plus 
the short address (e.g. 100+7=107).

The actuator can be configured by ZTH EU via the service socket.
For an extended configuration the PC tool can be connected.

1

2

3

Summary of Contents for NF24A-MOD

Page 1: ...Modbus see interface description MP Bus max 8 Functional data Torque motor 90 in lb 10 Nm Torque Fail Safe 10 Nm Operating range Y 2 10 V Operating range Y variable 0 5 10 V Position feedback U 2 10 V...

Page 2: ...pecially in aircraft or in any other airborne means of transport Outdoor application only possible in case that no sea water snow ice insolation or aggressive gases interfere directly with the actuato...

Page 3: ...tically stops when the end stop is reached The first time the supply voltage is switched on i e at the time of commissioning the actuator carries out a synchronization The synchronization is in the ho...

Page 4: ...connection to MP PP terminal ZK2 GEN Electrical installation Supply from isolating transformer The wiring of the line for BACnet MS TP Modbus RTU is to be carried out in accordance with applicable RS...

Page 5: ...15 Subject to change 5 7 Connection with switching contact e g p monitor Requirements for switching contact The switching contact must be able to accurately switch a current of 16 mA 24 V Modbus RTU B...

Page 6: ...ommunication Service plug For connecting parametrisation and service tools Operating elements The manual override locking switch and direction of rotation switch elements are available on both sides S...

Page 7: ...th Min 85 Min 15 Clamping range Further documentation Tool connections BACnet Interface description Modbus Interface description Overview MP Cooperation Partners MP Glossary Introduction to MP Bus Tec...

Reviews: