Technical data sheet

NF24A-MOD

www.belimo.com

NF24A-MOD • en-us • 2022-03-15 • Subject to change

2 / 7


Mode of operation

Converter for sensors

Functional data Noise level, motor

40 dB(A)

Mechanical interface

Universal shaft clamp 10...25.4 mm

Position indication

Mechanical

Service life

Min. 60'000 fail-safe positions

Safety data Protection class IEC/EN

III, Safety Extra-Low Voltage (SELV)

Power source UL

Class 2 Supply

Degree of protection IEC/EN

IP54

Degree of protection NEMA/UL

NEMA 2

Enclosure

UL Enclosure Type 2

EMC

CE according to 2014/30/EU

Certification IEC/EN

IEC/EN 60730-1 and IEC/EN 60730-2-14

Certification UL

cULus according to UL60730-1A, UL60730-2-14 

and CAN/CSA E60730-1

The UL marking on the actuator depends on 
the production site, the device is UL-compliant 
in any case

Mode of operation

Type 1.AA

Rated impulse voltage supply / control

0.8 kV

Pollution degree

3

Ambient temperature

-22...122°F [-30...50°C]

Storage temperature

-40...176°F [-40...80°C]

Ambient humidity

Max. 95% RH, non-condensing

Servicing

maintenance-free

Weight Weight

4.6 lb [2.1 kg]

        

Safety notes

This device has been designed for use in stationary heating, ventilation and air-conditioning 
systems and must not be used outside the specified field of application, especially in aircraft or 
in any other airborne means of transport.
Outdoor application: only possible in case that no (sea) water, snow, ice, insolation or 
aggressive gases interfere directly with the actuator and that is ensured that the ambient 
conditions remain at any time within the thresholds according to the data sheet.
Only authorized specialists may carry out installation. All applicable legal or institutional 
installation regulations must be complied during installation.
The device may only be opened at the manufacturer's site. It does not contain any parts that 
can be replaced or repaired by the user.
Cables must not be removed from the device.
To calculate the torque required, the specifications supplied by the damper manufacturers 
concerning the cross-section, the design, the installation situation and the ventilation 
conditions must be observed.
The device contains electrical and electronic components and must not be disposed of as 
household refuse. All locally valid regulations and requirements must be observed.

Product features

The actuator is fitted with an integrated interface for BACnet MS/TP, Modbus RTU and MP-Bus. 
It receives the digital positioning signal from the control system and returns the current status.

Connection option for a sensor (passive, active or with switching contact). In this way, the 
analog sensor signal can be easily digitized and transferred to the bus systems : BACnet, 
Modbus or MP-Bus.

Summary of Contents for NF24A-MOD

Page 1: ...Modbus see interface description MP Bus max 8 Functional data Torque motor 90 in lb 10 Nm Torque Fail Safe 10 Nm Operating range Y 2 10 V Operating range Y variable 0 5 10 V Position feedback U 2 10 V...

Page 2: ...pecially in aircraft or in any other airborne means of transport Outdoor application only possible in case that no sea water snow ice insolation or aggressive gases interfere directly with the actuato...

Page 3: ...tically stops when the end stop is reached The first time the supply voltage is switched on i e at the time of commissioning the actuator carries out a synchronization The synchronization is in the ho...

Page 4: ...connection to MP PP terminal ZK2 GEN Electrical installation Supply from isolating transformer The wiring of the line for BACnet MS TP Modbus RTU is to be carried out in accordance with applicable RS...

Page 5: ...15 Subject to change 5 7 Connection with switching contact e g p monitor Requirements for switching contact The switching contact must be able to accurately switch a current of 16 mA 24 V Modbus RTU B...

Page 6: ...ommunication Service plug For connecting parametrisation and service tools Operating elements The manual override locking switch and direction of rotation switch elements are available on both sides S...

Page 7: ...th Min 85 Min 15 Clamping range Further documentation Tool connections BACnet Interface description Modbus Interface description Overview MP Cooperation Partners MP Glossary Introduction to MP Bus Tec...

Reviews: