Technical data sheet 

CR24-B2

www.belimo.com

7

Pr

oduct information S4-CR24-.. • en • v2.3 • 08.2022 • Subject t

o changes

Technical data

Electrical data

Nominal voltage

AC 24 V  50/60 Hz

For wire sizing

3 VA, 

without actuators

Power supply range

AC 19.2...28.8 V

Connections

Terminal block 1...3: 2.5 mm

Terminal block 4...8: 1.5 mm

2

Functional data

Control characteristics

P

– 

P-band heating / cooling

Selectable: 1.5 / 1.0 K or 3.0 / 2.0 K

External temperature sensor (ai1)

Type NTC, 5 k�, sensing range 10...45°C

 

for example Belimo type 

01DT-1HP

Heating

 setpoint

Range 15...36°C (default 21°C)

–  Energy hold off

Heating 15°C / cooling 40°C

–  Stand-by

Heating –2 K / c3 K

Dead band

1 K

Frost limit temperature

10°C

Operation (CR24-B.. only)

– 

Mode switch and status indication (LEDs) AUTO (green) – ECO (orange) – MAX (red)

– 

Rotary knob for setpoint adjustment

±3 K

Communication port for field devices

2 x PP (for PC-Tool, MFT remote control etc.)

Inputs

2 x analog, 3 x digital

–  External temperature sensor

 (ai1)

Type NTC, 5 k�, 

sensing range

 10...45°C

–  External setpoint shift

 (ai2)

0...10 V 

corresponds to

 0...10 K

–  Digital inputs

 (di1, di2, di3)

Contact rating

 10 mA

Outputs

2 x analog

– 

VAV system output (ao1)

(0)2...10 V, max. 5 mA

– 

Heating output (ao3)

3-point, AC 24 V, max. source current 0.5 A / 10 VA

(optimized for actuators with a running time of 

 

approx. 150 s)

Norms und standards

Protection class

III Safety extra-low voltage

Degree of protection

IP 30 to EN 60529

Mode of operation

Type 1 to EN 60730-1

Software class

A to EN 60730-1

EMC

CE conformity to 89/336/EEC

Ambient conditions

–  Operation

    0...+50°C / 20...90% RH (without condensation

–  Transport and storage

–25...+70°C / 20...90% RH (without condensation

Dimensions / Weight

Dimensions (H x W x D)

99 x 84 x 32 mm

Weight

105 g

Housing colors

Baseplate 

 

Cover

NCS2005-R80B light gray 

 

(corresponds approx. to RAL 7035)

 

RAL 9003-Signalweiss

Temperature controllers for single room 
applications with two analog outputs:
•  The analog output ao1 can be used in VAV 

applications to contol one or more  

VAV controllers.

•  The analog heating output ao3 supplies a 

3-point signal.

Safety notes

!

•  The controller is not allowed to be used outside the specified field of application, 

especially in aircraft or in any other airborne means of transport.

•  It may only be installed by suitably trained personnel.  

All applicable legal or institutional installation regulations must be complied with.

•  The device may only be opened at the manufacturer's site. It does not contain any parts that can 

be replaced or repaired by the user.

•  The device contains electrical and electronic components and is not allowed to be disposed of as 

household refuse. All locally valid regulations and requirements must be observed.

Device variants

Type CR24-A2, same functionality as the 

CR24-B2 but without an operator panel.

Summary of Contents for CR24 Series

Page 1: ...Single room controllers CR24 B2E CR24 A2E Single room controllers CR24 B3 CR24 A3 Single room controllers 5 7 9 13 Operation 15 Functions Setpoint calculation Energy hold off Stand by VAV Function Ele...

Page 2: ...oduct information S4 CR24 en v2 3 08 2022 Subject to changes VAV applications Single room controllers Water applications Air applications CR24 B1 CR24 B2E CR24 B3 CR24 B2 Compact Universal Rotary actu...

Page 3: ...st effective system solutions for individually controlling the room climate and reducing energy consumption The controllers can be used in both pure VAV and combined systems with 2 and 4 pipe water ap...

Page 4: ...d Volume increase in heating mode selectable Internal function test including nominal voltage test Commissioning mode with output and sequence simulation VAV controller diagnosis via integrated PC Too...

Page 5: ...otection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE conformity to 89 336 EEC Ambient conditions Operation 0 50 C 20 90 RH without condensation Trans...

Page 6: ...y unoccu pied Frost The frost protection function is activated if the actual room temperature falls below 10 C Change over Change over heating or heating cooling External temperature sensor An externa...

Page 7: ...f approx 150 s Norms und standards Protection class III Safety extra low voltage Degree of protection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE con...

Page 8: ...cted to the analog input ai1 for instance in order to measure the average room temperature in the exhaust air duct External setpoint shift An external DC 0 10 V signal at the analog input ai2 can be u...

Page 9: ...oltage Degree of protection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE conformity to 89 336 EEC Ambient conditions Operation 0 50 C 20 90 RH without...

Page 10: ...ion can optionally be increased Output mode The do3 output mode can be set accordingly to the application to stage for one stage electrical reheater or on off radiator valve binary for two stage elect...

Page 11: ...former Parallel connection of other actuators possible Note the performance data Inputs Outputs 3 ai1 Supply air temperature limiter 6 ao1 System output for Belimo VAV controller di1 Energy hold off 9...

Page 12: ...12 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Page 13: ...w voltage Degree of protection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE conformity to 89 336 EEC Ambient conditions Operation 0 50 C 20 90 RH with...

Page 14: ...shift An external DC 0 10 V signal at the analog input ai2 can be used to shift the basic setpoint 0 10 K for instance for the summer winter compensation These functions are described in detail on pag...

Page 15: ...also during operation Internal function test A comprehensive internal function test including a nominal voltage test AC 24 V can be started for the controller with the mode switch The three LEDs statu...

Page 16: ...16 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Page 17: ...mfort Basic setpoint WH 3 K Setpoint adjustment Setpoint shift 0 10 V Comfort heating setpoint WA 1 K Dead band Stand by Comfort heating setpoint WA 2 K Stand by offset heating Comfort heating setpoin...

Page 18: ...to the automatic sensor detection the change into energy hold off takes about 40 seconds If a local detector e g a motion detector acts on the digital input di2 and closes the corresponding contact t...

Page 19: ...60 70 80 C 30 40 50 60 70 80 An external NTC temperature sensor can be connected to the analog input ai1 Sensor type NTC 5k 5 k Function The temperature of the supply air is limited by shedding indi...

Page 20: ...rooms hotel rooms etc e g time switch controlled Assisting smoke extraction Controlling air quality 2 point signal Notes The VAV output ao1 is set to a fixed value of V max 10 V The heating output ao3...

Page 21: ...ting cooling output ao2 of the CR24 B3 controller Typical applications Change over heating or heating cooling Note For chilled ceiling applications refer to page 23 The CR24 B1 controller is suitable...

Page 22: ...litate room preconditioning Boost V max Digital input di3 CR24 B3 only Configuration This boost function is configured using DIP switches 4 boost on and 5 boost V max 2 3 4 5 6 1 Configuration CR24 B3...

Page 23: ...ng can be combined with the change over function Typical applications Switchable heated chilled ceiling systems that also require dew point limiting Chilled ceiling with dew point limiting Digital inp...

Page 24: ...the local safety interlock STh from responding unless absolutely necessa ry and relieves the load on devices and installations When the system is started up after a power on or EHO off or when EHO ac...

Page 25: ...sing cover 2 Pull out slightly the wall of the housing to release the pcb 3 Remove the printed circuit board Rotary knob for setpoint adjustment If the rotary knob has been removed proceed as follows...

Page 26: ...y of the environment No of CR24 Cable cross section Cable length 10 0 75 mm2 max 250 m 20 0 75 mm2 max 200 m 20 1 00 mm2 max 250 m 25 0 75 mm2 max 170 m 25 1 00 mm2 max 220 m 25 1 50 mm2 max 250 m 30...

Page 27: ...with the mode switch on the operator panel With CR24 A controllers the housing cover must be removed first To activate test mode 1 Set the mode switch to MAX The red LED MAX status indication lights...

Page 28: ...ated without a flow Simulations can be carried out on the CR24 at any time even if the ventilation system is not operating The two triac outputs are activated for a maximum of 15 seconds in simulation...

Page 29: ...www belimo com 29 Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Page 30: ...30 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Page 31: ...www belimo com 31 Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Page 32: ...m Agentina Australia Bahrain Belgium Bosnia Herzegovina Brazil Bulgaria Canada Chile Croatia Cyprus Czech Republic Denmark Egypt Estonia Finland France Great Britain Germany Greece Hong Kong Hungary I...

Reviews: