
Functions CR24-..
www.belimo.com
17
Pr
oduct information S4-CR24-.. • en • v2.3 • 08.2022 • Subject t
o changes
Introduction
CR24-B.. only
The control functions define the behavior of the controller outputs and influence the current
setpoint.
Both the level of comfort and the energy saving
potential can be significantly enhanced by
installing suitable sensors on the input side.
Please refer to the table on page 3 for an overview of the functions of the three basic CR24-B..
types. These functions are described in detail below.
Operating status
Heating setpoint
Cooling setpoin
t
Comfort
Basic setpoint W
H
± 3 K Setpoint adjustment
+ Setpoint shift 0...10 V
Comfort heating setpoint W
A
+ 1 K Dead band
Stand-by
Comfort heating setpoint W
A
– 2 K Stand-by offset heating
Comfort heating setpoint W
A
+ 1 K Dead band
+ 3 K Stand-by offset cooling
Energy hold off
Fixed 15°C (building protection)
Fixed 40°C (building protection)
Frost
Fixed 10°C
Not relevant
Setpoint calculation
Examples
Comfort
Stand-by
Y
t
R
10
2
0
Energy hold off
Stand-by
Basic setpoint W
H
Cooling
Heating
±3 K Setpoing adjustment
Setpoint shift 0...10 V
Dead band
Frost
Comfort heating setpoint W
A
VAV
Y
t
R
+1 K Dead band
23°C Comfort heating setpoint W
A
Y
t
R
+1 K Dead band
23°C Comfort heating setpoint W
A
+3 K Stand-b
y offse
t cooling
–2 K Stand-b
y offset h
eating
Summary of Contents for CR24 Series
Page 12: ...12 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...
Page 16: ...16 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...
Page 29: ...www belimo com 29 Product information S4 CR24 en v2 3 08 2022 Subject to changes...
Page 30: ...30 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...
Page 31: ...www belimo com 31 Product information S4 CR24 en v2 3 08 2022 Subject to changes...