background image

Dimensions, installation, commissioning, service

CR24-..

www.belimo.com

27

Pr

oduct information S4-CR24-.. • en • v2.3 • 08.2022 • Subject t

o changes

Commissioning / Power on behaviour

Commissioning

1.  Assemble the baseplate of the housing and connect the cables (see page 15).

2.  Configure the DIP switches on the printed circuit board according to the required application.

3.  Assemble the printed circuit board on the baseplate of the housing and then mount the 

 

housing cover (see page 15).

4.  Switch on the nominal voltage (AC 24 V).

5.  Optional: start the test and simulation mode (see below).
When the voltage is applied, the system starts operating normally in AUTO mode (unless the test 

and simulation mode is selected). The 

 

active operating status is determined primarily by the configuration of the DIP switches and the 

status of the inputs

Power on behaviour

After power on of the voltage supply the output gets initialized as 

 

follows:

–  ao1  =  0 V

–  ao2  =  0 V

–  ao3  =  closed (200 s)
Subsequently the controller switches automatically to the control mode.

Test and simulation mode

All controllers are supplied with two auxiliary programs for commissioning and servicing:

–  Internal function test

–  Control sequence simulation

Activating test and simulation mode

The test and simulation mode of CR24-B.. controllers can be activated easily with the mode 

switch on the operator panel. With CR24-A.. controllers, the housing cover must be removed first.

To activate test mode

1. Set the mode switch to MAX

 

–  The red LED (MAX status indication) lights up

2. Keep the mode switch pressed for ten seconds

 

–  The internal function test is activated (see below)

To activate simulation mode

3. Press the mode switch again briefly (for approximately one second)

 

– 

The green LED (AUTO status indication) flashes

 

–  Control sequence simulation is activated (see below)

Deactivating test and simulation mode

The test and simulation mode can be deactivated either by pressing the mode switch again for 

ten seconds or by interrupting the power supply. It is also deactivated automatically 15 minutes 

after the last user action (auto-reset).

Internal function test

The internal function test tests the nominal voltage that is connected to the controller (AC 24 V), 

in other words the complete electrical wiring system from the control cabinet to the controller.

The three LEDs (status indication) indicate the voltage level (see below) and states during the test.

Nominal voltage (AC 24 V)

LED (status indication)

Scenario A

Scenario B

Scenario C

MAX

red

flash

flash

permanently on

ECO

orange

flash

flash

permanently on

AUTO

green

permanently off

flash

permanently on

<20 V

20...22 V

>22 V

Note

Case B and C do not need further attention. In case 

A (<20 V) attation must be paid to the following 

points:

– Quality of the wiring and connections

– Cable length/diameter and 

the transformer sizing.

Summary of Contents for CR24 Series

Page 1: ...Single room controllers CR24 B2E CR24 A2E Single room controllers CR24 B3 CR24 A3 Single room controllers 5 7 9 13 Operation 15 Functions Setpoint calculation Energy hold off Stand by VAV Function Ele...

Page 2: ...oduct information S4 CR24 en v2 3 08 2022 Subject to changes VAV applications Single room controllers Water applications Air applications CR24 B1 CR24 B2E CR24 B3 CR24 B2 Compact Universal Rotary actu...

Page 3: ...st effective system solutions for individually controlling the room climate and reducing energy consumption The controllers can be used in both pure VAV and combined systems with 2 and 4 pipe water ap...

Page 4: ...d Volume increase in heating mode selectable Internal function test including nominal voltage test Commissioning mode with output and sequence simulation VAV controller diagnosis via integrated PC Too...

Page 5: ...otection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE conformity to 89 336 EEC Ambient conditions Operation 0 50 C 20 90 RH without condensation Trans...

Page 6: ...y unoccu pied Frost The frost protection function is activated if the actual room temperature falls below 10 C Change over Change over heating or heating cooling External temperature sensor An externa...

Page 7: ...f approx 150 s Norms und standards Protection class III Safety extra low voltage Degree of protection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE con...

Page 8: ...cted to the analog input ai1 for instance in order to measure the average room temperature in the exhaust air duct External setpoint shift An external DC 0 10 V signal at the analog input ai2 can be u...

Page 9: ...oltage Degree of protection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE conformity to 89 336 EEC Ambient conditions Operation 0 50 C 20 90 RH without...

Page 10: ...ion can optionally be increased Output mode The do3 output mode can be set accordingly to the application to stage for one stage electrical reheater or on off radiator valve binary for two stage elect...

Page 11: ...former Parallel connection of other actuators possible Note the performance data Inputs Outputs 3 ai1 Supply air temperature limiter 6 ao1 System output for Belimo VAV controller di1 Energy hold off 9...

Page 12: ...12 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Page 13: ...w voltage Degree of protection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE conformity to 89 336 EEC Ambient conditions Operation 0 50 C 20 90 RH with...

Page 14: ...shift An external DC 0 10 V signal at the analog input ai2 can be used to shift the basic setpoint 0 10 K for instance for the summer winter compensation These functions are described in detail on pag...

Page 15: ...also during operation Internal function test A comprehensive internal function test including a nominal voltage test AC 24 V can be started for the controller with the mode switch The three LEDs statu...

Page 16: ...16 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Page 17: ...mfort Basic setpoint WH 3 K Setpoint adjustment Setpoint shift 0 10 V Comfort heating setpoint WA 1 K Dead band Stand by Comfort heating setpoint WA 2 K Stand by offset heating Comfort heating setpoin...

Page 18: ...to the automatic sensor detection the change into energy hold off takes about 40 seconds If a local detector e g a motion detector acts on the digital input di2 and closes the corresponding contact t...

Page 19: ...60 70 80 C 30 40 50 60 70 80 An external NTC temperature sensor can be connected to the analog input ai1 Sensor type NTC 5k 5 k Function The temperature of the supply air is limited by shedding indi...

Page 20: ...rooms hotel rooms etc e g time switch controlled Assisting smoke extraction Controlling air quality 2 point signal Notes The VAV output ao1 is set to a fixed value of V max 10 V The heating output ao3...

Page 21: ...ting cooling output ao2 of the CR24 B3 controller Typical applications Change over heating or heating cooling Note For chilled ceiling applications refer to page 23 The CR24 B1 controller is suitable...

Page 22: ...litate room preconditioning Boost V max Digital input di3 CR24 B3 only Configuration This boost function is configured using DIP switches 4 boost on and 5 boost V max 2 3 4 5 6 1 Configuration CR24 B3...

Page 23: ...ng can be combined with the change over function Typical applications Switchable heated chilled ceiling systems that also require dew point limiting Chilled ceiling with dew point limiting Digital inp...

Page 24: ...the local safety interlock STh from responding unless absolutely necessa ry and relieves the load on devices and installations When the system is started up after a power on or EHO off or when EHO ac...

Page 25: ...sing cover 2 Pull out slightly the wall of the housing to release the pcb 3 Remove the printed circuit board Rotary knob for setpoint adjustment If the rotary knob has been removed proceed as follows...

Page 26: ...y of the environment No of CR24 Cable cross section Cable length 10 0 75 mm2 max 250 m 20 0 75 mm2 max 200 m 20 1 00 mm2 max 250 m 25 0 75 mm2 max 170 m 25 1 00 mm2 max 220 m 25 1 50 mm2 max 250 m 30...

Page 27: ...with the mode switch on the operator panel With CR24 A controllers the housing cover must be removed first To activate test mode 1 Set the mode switch to MAX The red LED MAX status indication lights...

Page 28: ...ated without a flow Simulations can be carried out on the CR24 at any time even if the ventilation system is not operating The two triac outputs are activated for a maximum of 15 seconds in simulation...

Page 29: ...www belimo com 29 Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Page 30: ...30 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Page 31: ...www belimo com 31 Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Page 32: ...m Agentina Australia Bahrain Belgium Bosnia Herzegovina Brazil Bulgaria Canada Chile Croatia Cyprus Czech Republic Denmark Egypt Estonia Finland France Great Britain Germany Greece Hong Kong Hungary I...

Reviews: