background image

15

Subject to technical modifications

22PD differential pressure sensor / 

Commissioning

Commissioning

Standard mode

In standard mode, the device reads out the pressure transmitter and calculates 
the differential pressure depending on the selected range. The differential pres-
sure is displayed on the LCD and is provided as current or voltage at the ana-
logue output. The output value is updated once per second.
To measure and display the differential pressure correctly, the pressure present 
at the HIGH connection must be higher than that at the LOW connection. When 
the pressure connections are switched, the sensor always outputs 0 V or 4 mA. 
When this is the case, it is possible to switch the pressure connections in the 
menu. It should be noted that, for correct measurement, the connecting cable 
marked HIGH must always be connected with the HIGH pressure transmitter, 
and the cable marked LOW must always be connected with the LOW pressure 
transmitter.
If the LOW connection remains open to ambient pressure, then the HIGH 
 connection is used to measure a positive pressure.
To achieve a positive output behaviour, the pressure applied at the HIGH 
 connection for bidirectional operation should be higher than that at the LOW 
connection. Negative pressure is displayed when the pressure at the HIGH 
 connection is lower than that at the LOW connection.
The differential pressure sensor shows a linear behaviour with respect to the 
differential pressure measured and the corresponding signal output value. This 
means for example that, for a 0…10 bar sensor in uni-directional operation, 0 bar 

= 0 V or 4 mA and 10 bar = 5 or 10 V or 20 mA, while in bi-directional operation 
−10 bar = 0 V or 4 mA and +10 bar = 5 or 10 V or 20 mA. 0 bar corresponds in 
this case to 2.5 or 5 V or 12 mA. 
The  output  value  can  be  influenced  by  device  settings,  such  as  the  time  for 

 signal damping or average value formation.

The setting of the average pressure value calculations defines how many mea-

sured values are applied for averaging and thus as the basis for the output val-
ue. If, for example, the average pressure value calculation is set to 30 seconds, 
then 30 one-second measured values are saved and averaged to form the out-

put value. The next second adds a new measured value and deletes the first in 

the series in order to calculate a new 30-second average for the output. The 
output is updated every second with a new average value. The user menu can 

be applied to set average value from 1 to 60 seconds.

In standard mode, the device also monitors the 

<DOWN>

<ZERO/UP> 

and 

<MENU>

 buttons and initiates corresponding measures. The buttons are used 

to access the user menu. The device also monitors the VOLT/mA switch to 
 determine the suitable output signal scale. The user menu can be used to set 

the voltage range to either 0...5 V or 0...10 V.

Auto-Zero calibration

An automatic zero-point calibration of the sensor can be initiated by pressing 
the internal 

<ZERO>

 button and holding it down for a minimum of 3 seconds. 

Once both pressure connections are near zero, the device calculates with a new 
zero point. Automatic zero-point calibration can also be initiated by holding the 
ZERO terminal for at least 3 seconds on ground potential by pressing the 
 remotely mounted Zero switch.

Generally speaking, performing a measurement range calibration in the field is 

not recommended. This holds true unless a high-quality calibration standard 
with low differential pressure ranges is available and an unchanging sensor 
temperature can be ensured during the calibration procedure.

Summary of Contents for 22PDP

Page 1: ...HIG H LOW HIG H LOW 22PDP differential pressure sensor Edition 2022 04 A Operating instructions ...

Page 2: ...2 22PDP differential pressure sensor ...

Page 3: ...tter cables 7 Configuration 8 Warning notice 8 Wiring Starting mode Port wiring 9 Software Version Number 11 Model Pressure Range 11 Output Type 11 User menu Menu 12 Down Up 12 Output output signal voltage range 12 Pressure Range 13 Pressure Scale 13 Damping average value and signal damping 13 Output output signal direct reverse 14 Pressure Port 14 Backlight 14 Commissioning Standard mode 15 Auto ...

Page 4: ...does not exceed the value specified as the highest pressure for the respective sensor This corre sponds for example to a maximum of 10 bar for the 22PDP 186 sensor model Measurement inaccuracies could occur if the sensor is operated in the over pressure range Pressures in excess of the specified value could damage the sensor See nominal sizes in the table on page 13 Prior to installation Read the ...

Page 5: ...e is sufficient space present around the device for the electrical connections and that the distance to the pressure measurement sites does not exceed the cable lengths of the pressure transmitters Avoid mounting positions with strong vibrations or excessive humidity HIG H LOW HIG H LOW Figure 1 The housing is equipped with a cover with a lid for tool free opening snap fit Open the covering by pul...

Page 6: ...hat at the LOW connection Make sure that the pressure transmitters as shown in a typi cal application in Figure 5 are connected correctly Both pressure transmitters have a G external thread for connection to the pipe to be monitored Do not permit any material to fall into the pressure connections as contaminations could damage the pressure transmitters HIGH LOW LOW HIGH LOW HIGH LOW HIGH LOW HIGH ...

Page 7: ...ely See Figure 7 1 HIGH LOW Figure 7 Re connect the pressure transmitter cable by aligning the cable plug with the pressure transmitter contact notch groove carefully pressing it into the pres sure transmitter and then tightening the screw cap hand tight Make sure that you are using the pressure transmitter and the cable which are both marked HIGH See Figure 8 HIGH LOW 1 2 HIGH LOW Figure 8 Repeat...

Page 8: ...ging the output signal type e g from the volt age output to the current output Selection of the output signal The differential pressure sensor is equipped with output signals for user selec tion of 4 20 mA 0 5 V and 0 10 V The factory setting for operation is voltage output 0 10 V The sensor can be changed to the current output mode by sliding the output selection switch located on the printed cir...

Page 9: ... and the output signal type To simplify installation you can remove the terminal from the printed circuit board by pulling it upward and off the pins on the circuit board Ensure correct placement of the terminal after the wiring is completed The la belling of the terminal pins on the printed circuit board must be visible in its en tirety and must not be hidden by the terminal Connect the DC plus o...

Page 10: ...al modifications 22PDP differential pressure sensor Wiring Figure 10 In the event of a separate power supply ensure that the grounding DC or supply common AC are connected from the sensor the controller and the power supply ...

Page 11: ...lied with current The LCD displays the current operating settings for 2 seconds All of the information in the menu and in the display are in English 1 Software Version Number Version 2 Model Pressure Range P Range 3 Output Type Output At the end of starting mode the device switches into normal mode and displays the measured differential pressure 0 00 bar ...

Page 12: ...alue If the user menu has been inactive for 5 minutes no button pressed then the menu is exited and the device returns to standard mode The operation and parameters of the user menu are explained in the following Menu Press the MENU button and release it again to call up the user menu Down Up This element appears only when the output signal switch on the circuit board is in VOLT position Use DOWN ...

Page 13: ...ss the MENU button to save changes and proceed to the next menu point 3 Pressure Scale P Scale 0 Max The default pressure scale is uni directional from 0 to the maximum range e g 0 10 bar Use DOWN or UP to switch the setting to a bidirectional scale or measurement e g 10 bar The setting switches from 0 Max to Max Press the MENU button to save changes and proceed to the next menu point 4 Damping av...

Page 14: ...r pressure LOW connection lower pressure Use DOWN or UP to switch to Reverse HIGH connection lower pressure LOW connection higher pressure when the connections need to be swapped in the software due to an installation error Press the MENU button to save changes and proceed to the next menu point 7 Backlight Backlite Auto The backlight is set by default to Auto operation DOWN or UP can be used to s...

Page 15: ...0 bar 0 V or 4 mA and 10 bar 5 or 10 V or 20 mA 0 bar corresponds in this case to 2 5 or 5 V or 12 mA The output value can be influenced by device settings such as the time for signal damping or average value formation The setting of the average pressure value calculations defines how many mea sured values are applied for averaging and thus as the basis for the output val ue If for example the ave...

Page 16: ...ingle source At the same time we rely on tested Swiss quality with a five year warranty Our worldwide representatives in over 80 countries guarantee short delivery times and comprehensive support through the entire product life Belimo does indeed include everything The small Belimo devices have a big impact on comfort energy effi ciency safety installation and maintenance In short Small devices bi...

Reviews: