CONTROL DRAWING for Industrial ETHERNET
Rail Switch 2 and Rail Transceiver 2 Family

According to ANSI / ISA 12.12.01-2012

Rev.: 0 Date: 2012-07-13

Document No.:  000163806DNR

Page 1 of 1

NON HAZARDOUS LOCATION

Power Supply: (Redundant: P1, P2)
 24 

DC

Relay Contacts:

Associated Apparatus:

Equipment with nonincendive 
fi eld wiring 

1

HAZARDOUS LOCATION Class 
I, Division 2 Groups A, B, C, D

The Use in Hazardous Locations is only allowed for Rail Switch 2 and Rail Transceiver 2 Family model No‘s which are individually labelled 

FOR USE IN CLASS I, DIVISION 2 HAZARDOUS LOCATIONS

Notes:

 

The nonincendive fi eld wiring circuit concept allows interconnection of nonincendive fi eld wiring apparatus and associated nonincendive 

fi eld wiring apparatus using any of the wiring methods permitted for unclassifi ed locations when certain parametric conditions are met

Capacity:  

Ca ≥ Ci + CCable 

Inductivity:   

La ≥ Li + LCable 

The maximum cable length has to be determined as follows:
(a) max. Cable Length < (La - Li) / 

LCable 

and (b) max. Cable Length < (Ca - Ci) / 

CCable

 

The lower value of (a) and (b) is to apply.
CableL: inductance per unit length of used cable.

CableC: capacitance per unit length of used cable.

Other C-parameters and L-parameters are according to ANSI / ISA 12.12.01-2012 section 7.

Where cable capacitance and inductance values per foot are not known, the following values shall be used:

CCable

 60 pF/foot, 

LCable

 0.2 µH/foot

Nonincendive fi eld wiring circuits must be wired in accordance with the National Electric Code (NEC), NFPA 70, article 501.

1

Nonincendive Field Wiring Parameters:

The Relay Contacts are dependent upon the 

following Entity Parameters:

V

max

I

max

C

i

L

i

30 V

90 mA

2.5 nF

1 µH

WARNING – EXPLOSION HAZARD – SUBSTITUTION OF ANY COMPONENTS MAY IMPAIR SUITABILITY FOR HAZAR-

DOUS LOCATIONS OR EXPLOSIVE ATMOSPHERES.

WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR 
THE AREA IS KNOWN TO BE NON-HAZARDOUS.

DO NOT OPEN WHEN ENERGIZED.

Relay Contacts:

Associated Apparatus:

Equipment with nonincendive 
fi eld wiring 

1

Power Supply: (Redundant: P1, P2)
 24 

DC

Detail: RS2-xxx

Detail: RT2-xxx

The equipment must be installed in a tool-locked enclosure.

Summary of Contents for HIRSCHMANN RS2-3TX/2FX EEC

Page 1: ...e four 10 100 MBit s twisted pair ports 10 100BASE TX RJ45 connectors and one 100 MBit s fiber optic port 100BASE FX Duplex SC connector or ST connector on R2 4TX 1FX ST EEC The RS2 4TX EEC module has...

Page 2: ...components recommen ded or approved by Hirschmann The product can only be operated correctly and safely if it is transpor ted stored installed and assembled properly and correctly Furthermore it must...

Page 3: ...Li LCable and b max Cable Length Ca Ci CCable The lower value of a and b is to apply CableL inductance per unit length of used cable CableC capacitance per unit length of used cable Other C parameters...

Page 4: ...an 119 V Connectors shall be connected or dis connected exclusively in dead voltage state DIP switches shall be switched exclusi vely in dead voltage state Safety Guidelines Environment z Warning The...

Page 5: ...a cross over or straight cable 1 3 SPECIFIC FUNCTIONS OF THE F O INTERFACE Link control The RS2 xTX xFX EEC monitors the connec ted F O line for interrupts using idle signals during frame pauses in a...

Page 6: ...wer P1 and P2 LEDs for data link status DA STAT 1 to 5 FAULT LED LEDs for power P1 and P2 LEDs for data link status DA STAT 1 to 5 on the RS2 4TX EEC FAULT LED 2 3 4 DA STAT 1 2 P 1 DA STAT FAULT 2 3...

Page 7: ...3 Port 2 Port 4 Suppress message about link status via indicator contact RS2 4TX EEC LA1 0 1 LA5 LA3 LA2 LA4 Port 1 Port 5 Port 3 Port 2 Port 4 Suppress message about link status via indicator contact...

Page 8: ...al EN 61000 4 5 Test level 2 Surge voltage asymmetrical EN 61000 4 5 Test level 3 Cable based RF faults EN 61000 4 6 Test level 3 Radiated emission EMC EN 55022 Class A CFR 47 Part 15 Class A Stabilit...

Page 9: ...FX SM EEC 943 772 001 Rail Switch RS2 4TX EEC 943 819 001 Rail Switch RS2 4TX 1FX EEC 943 773 001 Rail Switch RS2 4TX 1FX ST EEC 943 119 002 Rail Switch RS2 4TX 1FX SM EEC 943 774 001 Accessories Ethe...

Page 10: ...Automation and Control GmbH Stuttgarter Stra e 45 51 72654 Neckartenzlingen Germany Tel 49 0 1805 14 1538 Fax 49 0 7127 14 1551 E mail hac support belden com Internet http www hirschmann com 039 651 0...

Reviews: