42
Installation BAT-R
Release 17 12/2020
Perform the following steps for the supply voltage to be connected, or for
device variants with 2 supply voltage connections of this type, for
every
supply voltage to be connected.
Remove the terminal connector from the device.
Connect the wires according to the pin assignment on the device with the
clamps.
Fasten the wires in the terminal block by tightening the terminal screws.
2.5.2
Supply voltage with the characteristic value K
(60 V DC ... 250 V DC / 110 V AC ... 230 V AC, 50 Hz ...
60 Hz)
Figure 3: Supply voltage with characteristic value K (60 V DC ... 250 V DC /
110 V AC ... 230 V AC, 50 Hz ... 60 Hz): 3-pin terminal block with screw
locking
WARNING
ELECTRIC SHOCK
Install this device only in a switch cabinet or in an operating site with
restricted access, to which maintenance staff have exclusive access.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.
Type of the voltages
that can be
connected
Specification of the supply
voltage
Pin assignment on the device
DC voltage
Rated voltage range DC:
60 V DC ... 250 V DC
Voltage range DC incl.
maximum tolerances:
48 V DC ... 320 V DC
+/L
Plus terminal of the supply voltage
-/N
Minus terminal of the supply
voltage
Protective conductor
Table 10: Supply voltage with characteristic value K (60 V DC ... 250 V DC /
110 V AC ... 230 V AC, 50 Hz ... 60 Hz): type and specification of the
supply voltage, pin assignment on the device