Installation
EAGLE20/30
Release
11
0
9/2020
49
EMC and immunity
Note:
You will find detailed information on the certificates and declarations applying to your device in a separate
overview.
See table 5 on page 18.
EMC interference
emission
Standard
applications
Navy applications Railway
applications
Substation
applications
Radiated emission
EN 55032
Class A
—
—
Class A
GL Guidelines
—
EMC 1
—
—
FCC 47 CFR Part 15
Class A
—
—
Class A
EN 61000-6-4
Fulfilled
—
Fulfilled
—
Conducted emission
EN 55032
AC and DC supply connections
Class A
—
—
Class A
GL Guidelines
AC and DC supply connections
—
EMC 1
—
—
FCC 47 CFR Part 15
AC and DC supply connections
Class A
—
—
Class A
EN 61000-6-4
AC and DC supply connections
Fulfilled
—
Fulfilled
—
EN 55032
Telecommunication connections
Class A
—
—
Class A
EN 61000-6-4
Telecommunication connections
Fulfilled
—
Fulfilled
—
EMC interference
immunity
Standard
applications
Navy applications Railway
applications
Substation
applications
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge
± 4 kV
± 6 kV
± 6 kV
± 8 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge
± 8 kV
± 8 kV
± 8 kV
± 15 kV
Electromagnetic field
EN 61000-4-3
80 MHz ... 3000 MHz
10 V/m
10 V/m
—
10 V/m
Summary of Contents for Hirschmann EAGLE20