Installation EAGLE20/30

Release 11 09/2020

45

Digital input (optional)

Note: 

Only for supply voltage with the following characteristic values:

CC

K9

The support of the function depends on the software release. Software 
support for the function is unimplemented at the time of printing this 
manual.

Climatic 
conditions 
during 
operation

Ambient air temperature

a

Devices with operating temperature 
characteristic value S (standard):
0 °C ... +60 °C (+32 °F ... +140 °F)
Devices with operating temperature 
characteristic value E and T (extended):

40 °C ... +70 °C

b,c

Humidity

5 % ... 95 %
(non-condensing)

Air pressure

minimum 700 hPa (+9842 ft; +3000 m)
maximum 1060 hPa (

1312 ft; 

400 m)

Climatic 
conditions 
during storage

Ambient air temperature

d

40 °F ... +185 °F (

40 °C ... +85 °C)

Humidity

10 % ... 95 %
(non-condensing)

Air pressure

minimum 700 hPa (+9842 ft; +3000 m)
maximum 1060 hPa (

1312 ft; 

400 m)

“FAULT”
 signal contact

Switching current

max. 1 A, SELV

Switching voltage

max. 60 V DC or max. 30 V AC, SELV

Pollution degree

2

Protection 
classes

Laser protection

Class 1 in compliance with IEC 60825-1

Degree of protection

IP20

a. Temperature of the ambient air at a distance of 2 inches (5 cm) from the device

b. Only use the SFP transceiver with the extension  “EEC”.

c. +85 °C for 16 hours (tested in accordance with IEC 60068-2-2)

d. Temperature of the ambient air at a distance of 2 inches (5 cm) from the device

Maximum permitted input voltage range

32 V DC … +32 V DC

Input voltage, low level, status “0”

0.3 V DC … +5.0 V DC

Input voltage, high level, status “1”

+11 V DC … +30 V DC

Maximum input current at 24 V input voltage

15 mA

Input characteristic acc. to IEC 61131-2 (current-consuming)

Type 3

Summary of Contents for Hirschmann EAGLE20

Page 1: ...Installation EAGLE20 30 Release 11 09 2020 Technical support https hirschmann support belden com User Manual Installation Industrial Security Router EAGLE20 30...

Page 2: ...he performance features described here are binding only if they have been expressly agreed when the contract was made This document was produced by Hirschmann Automation and Control GmbH according to...

Page 3: ...100 Mbit s twisted pair port 21 1 5 2 100 1000 Mbit s F O port optional 21 1 5 3 100 1000 Mbit s twisted pair port optional 22 1 5 4 Pin assignments 22 1 6 WAN port optional 23 1 7 Display elements 2...

Page 4: ...ly voltage with the characteristic value CC 36 2 5 4 Signal contact 36 2 6 Operating the device 37 2 7 Connecting data cables 37 2 7 1 Twisted Pair ports 37 2 7 2 100 1000 Mbit s F O port optional 38...

Page 5: ...es described in the Hirschmann product information including this manual Operate the product only according to the technical specifications See Technical data on page 44 Connect to the product only co...

Page 6: ...relieves in such a way that they prevent any mechanical damage to cables wires or conductors caused by external influences or their own weight To prevent damage to device connections connectors and ca...

Page 7: ...ements listed are complied with All of the following requirements are complied with The electrical wires are voltage free The cables used are permitted for the temperature range of the application cas...

Page 8: ...r supply complies with the requirements for a safety extra low voltage SELV as per IEC EN 60950 1 A fuse suitable for DC voltage is located in the plus conductor of the power supply The minus conducto...

Page 9: ...G EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS WARNING EXPLOSION HAZARD SUBSTITUTION OF ANY COMPONENT MAY I...

Page 10: ...de of the type designation on the device Relay contacts Equipment with non incendive field wiring parameters Polarity is not relevant The relay terminals are dependent upon the following entity parame...

Page 11: ...Code NEC NFPA 70 article 501 The earth conductor must be at least the same wire size mm or AWG as the supply conductors WARNING EXPLOSION HAZARD SUBSTITUTION OF ANY COMPONENTS MAY IMPAIR SUITABILITY F...

Page 12: ...cations system is illegal The SHDSL port is used exclusively for direct data connections between SHDSL enabled devices Warning This is a class A device This device can cause interference in living are...

Page 13: ...d operation Note This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable pr...

Page 14: ...l HiVision Network Management software provides you with additional options for smooth configuration and monitoring ActiveX control for SCADA integration Auto topology discovery Browser interface Clie...

Page 15: ...low you to set up switched and routed industrial Ethernet networks that conform to the IEEE 802 3 standard The devices work without a fan The device is mounted by latching in place on a DIN rail There...

Page 16: ...uter with gigabit ports 8 hyphen 9 10 Number Fast Ethernet ports 04 4 11 12 Number Gigabit Ethernet ports 00 0 02 2 13 15 Configuration of the uplink ports 2O6 2 SFP slot 999 Not present 16 17 Configu...

Page 17: ...ifications Note You will find detailed information on the certificates and declarations applying to your device in a separate overview See table 5 on page 18 Item Product characteristic Characteristic...

Page 18: ...X X X X X X X X X UL 508 X X X X X X X X X X X EN 60950 1 X X X X X X X X X X X X X X X EN 61131 2 X X X X X X X X X X X X X X X FCC X X X X X X X X X X X X X X X UL 60950 1 X X X X X X X X X Oil and...

Page 19: ...acteristic value K9 1 voltage input 3 pin terminal block Supply voltage with the characteristic value KK 2 voltage inputs for redundant power supply 3 pin terminal block 10 Connection for the signal c...

Page 20: ...4 2 Supply voltage with the characteristic value KK For the redundant power supply of the device two 3 pin terminal blocks are available For further information see Supply voltage with the characteris...

Page 21: ...nents according to the IEEE 802 3 10BASE T 100BASE TX standard This port supports Autonegotiation Autopolarity Autocrossing if autonegotiation is activated 100 Mbit s half duplex mode 100 Mbit s full...

Page 22: ...components according to the IEEE 802 3 100BASE FX 1000BASE SX 1000BASE LX standard This port supports Autonegotiation Full duplex mode 1 5 4 Pin assignments RJ45 Pin 10 100 Mbit s 1000 Mbit s PoE MDI...

Page 23: ...Aggregation of 2 links within the same port SHDSL Single Pair High Bit Rate Digital Subscriber Line M12 4 pin D coded Pin Data PoE 1 TX Positive VPSE 2 RX Negative VPSE 3 TX Positive VPSE 4 RX Negati...

Page 24: ...Status None Device starts Device is not ready for operation Green Lights up Device is ready for operation Characteristics can be configured Red Lights up The device reports a detected error See Refere...

Page 25: ...on the software release Software support for the function is unimplemented at the time of publishing this manual Display Color Activity Meaning Link status None Device detects an invalid or missing li...

Page 26: ...obally disabled 2 The configured VRRP instances have not met the preconditions for operation Green Lights up At least 1 VRRP instance is in Master mode Yellow Lights up No VRRP instances are in Master...

Page 27: ...device The V 24 interface is electrically insulated from the supply voltage Figure 1 Pin assignment of the V 24 interface and the DE9 connector The terminal cable is available as an accessory See Acce...

Page 28: ...is used for saving loading the configuration data and diagnostic information and for loading the software The USB interface has the following properties Supports the USB master mode Supports USB 2 0...

Page 29: ...ontact indicates the device status It can be configured using the device management 1 9 2 Digital input optional Note Only for supply voltage with the following characteristic values CC K9 The support...

Page 30: ...nstalling an SFP transceiver optional Connecting the terminal blocks Operating the device Connecting data cables Filling out the inscription label 2 1 Checking the package contents Check whether the p...

Page 31: ...s Slide the upper snap in guide of the device into the DIN rail Press the media module downwards onto the clip in bar Snap in the device WARNING FIRE HAZARD Install the device in a fire enclosure acco...

Page 32: ...aturing supply voltage with the characteristic value K9 or KK have a connection for protective grounding The device variants featuring supply voltage with the characteristic value CC and not featuring...

Page 33: ...chmann SFP transceivers See Accessories on page 54 Figure 5 Installing SFP transceivers Installation sequence Proceed as follows Take the SFP transceiver out of the transport packaging 1 Remove the pr...

Page 34: ...fore connecting the electrical wires always verify that the requirements listed are complied with See Requirements for connecting electrical wires on page 7 Failure to follow these instructions can re...

Page 35: ...d perform the following steps Remove the power connector from the device Connect the wires according to the pin assignment on the device with the clamps Fasten the wires connected by tightening the te...

Page 36: ...power failure You can avoid this message by changing the configuration in the management or with power supply units of the same type by feeding the supply voltage in through both inputs 2 5 4 Signal...

Page 37: ...s provide a sufficient separation between the power supply cables and the data cables Ideally install the cables in separate cable channels Verify that power supply cables and data cables do not run p...

Page 38: ...on page 21 2 7 3 WAN port optional Note In general you should adhere to the following recommendations for data cable connections in environments with high electrical interference levels Provide coppe...

Page 39: ...addresses Input via the V 24 interface Input via the HiView or Industrial HiVision application You find further information about the applications HiView or Industrial HiVision on the Internet at the...

Page 40: ...ou to type in a new password Type in your new password To help increase security choose a password that contains at least 8 characters which includes upper case characters lower case characters numeri...

Page 41: ...68 F 20 C higher than the ambient temperature This depends on the configuration of your device 5 Maintenance and service When designing this device Hirschmann largely avoided using high wear parts The...

Page 42: ...nal blocks Disconnect the grounding To remove the device from the DIN rail press the device downwards and pull it out from under the DIN rail Figure 9 Removal from the DIN rail WARNING ELECTRIC SHOCK...

Page 43: ...er optional Figure 10 De installing SFP transceivers De installation sequence Proceed as follows Open the locking mechanism of the SFP transceiver 1 Pull the SFP transceiver out of the slot via the op...

Page 44: ...replaceable fuse Back up fuse Nominal rating Characteristic 6 3 A slow blow Peak inrush current 4 A Power supply Supply voltage with the characteristic value K9 and KK See Requirements for connecting...

Page 45: ...40 F 185 F 40 C 85 C Humidity 10 95 non condensing Air pressure minimum 700 hPa 9842 ft 3000 m maximum 1060 hPa 1312 ft 400 m FAULT signal contact Switching current max 1 A SELV Switching voltage max...

Page 46: ...NorthAmerica Annex_A 32 TCPAM 2800 9186 3 2048 4096 13 5 NorthAmerica Annex A 16 TCPAM 3300 10827 4 1024 2048 13 5 NorthAmerica Annex A 16 TCPAM 4500 14764 5 704 1408 13 5 NorthAmerica Annex A 16 TCP...

Page 47: ...r the characteristic value see Device name and product code on page 16 Figure 12 Dimensions of the device variants without WAN ports with operating characteristic value E and T For the characteristic...

Page 48: ...name and product code on page 16 Figure 14 Dimensions of the device variants with WAN ports with operating characteristic value E and T For the characteristic value see Device name and product code on...

Page 49: ...032 AC and DC supply connections Class A Class A GL Guidelines AC and DC supply connections EMC 1 FCC 47 CFR Part 15 AC and DC supply connections Class A Class A EN 61000 6 4 AC and DC supply connecti...

Page 50: ...nnection EN 61000 4 5 IEEE 1613 line ground 2 kV 1 kV 2 kV 5 kV EN 61000 4 5 line line 1 kV 0 5 kV 1 kV 1 kV Voltage surges AC supply connection EN 61000 4 5 IEEE 1613 line ground 2 kV 1 kV 2 kV 5 kV...

Page 51: ...300 A m Stability Standard applications Navy applications Railway applications Substation applications IEC 60068 2 6 test Fc Vibration 5 Hz 8 4 Hz with 0 14 in 3 5 mm amplitude 2 Hz 13 2 Hz with 0 04...

Page 52: ...dB km 800 MHz km LX LC MM 1310 nm c 62 5 125 m 0 10 5 dB 0 550 m 1 0 dB km 500 MHz km LX LC SM 1310 nm 9 125 m 0 10 5 dB 0 20 kmd d Including 2 5 dB system reserve when compliance with the fiber data...

Page 53: ...km MM LC MM 1310 nm 62 5 125 m 0 11 dB 0 4 km 1 0 dB km 500 MHz km SM LC SM 1310 nm 9 125 m 0 13 dB 0 25 km 0 4 dB km 3 5 ps nm km SM LC SM 1310 nm 9 125 m 10 29 dB 25 65 km 0 4 dB km 3 5 ps nm km LH...

Page 54: ...ue K9 2 3 pin terminal block for the supply voltage only for device variants featuring supply voltage with characteristic value KK 2 2 pin terminal block for the supply voltage only for device variant...

Page 55: ...tiation mode including autocrossing M SFP SX LC 943 014 001 M SFP SX LC EEC 943 896 001 M SFP MX LC EEC 942 108 001 M SFP LX LC 943 015 001 M SFP LX LC EEC 943 897 001 M SFP LX LC 942 023 001 M SFP LX...

Page 56: ...nk loss detection times compared to twisted pair ports provided by the device directly Not applicable for combo ports Not applicable for ports which support only Gigabit Ethernet To set autocrossing m...

Page 57: ...c compatibility of multimedia equipment Emission Requirements EN 60950 1 Information technology equipment Safety Part 1 General requirements EN 61000 6 2 Electromagnetic compatibility EMC Part 6 2 Gen...

Page 58: ...Competence Center is ahead of its competitors on three counts with its complete range of innovative services Consulting incorporates comprehensive technical advice from system evaluation through netw...

Page 59: ...Installation EAGLE20 30 Release 11 09 2020 59...

Page 60: ......

Reviews: