belfuse.com/power-solutions
BCD20021-G Rev AF, 29 November 2021
Page 8 of 26
X Series
375, 500 Watt AC-DC and DC-DC DIN-Rail Converters
© 2021 Bel Power Solutions & Protection
Power Factor, Harmonics
All converters feature active power factor correction.
0
1
2
3
4
3
5
7
9
11
13
mA/W
04067a
Limit class D according
to IEC/EN 61000-3-2
Harm.
LXN1601-6
0
0.2
0.4
0.6
0.8
1
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
PF
04066a
I
o
I
o nom
V
i
= 125 VAC
V
i
= 230 VAC
Fig. 4
Harmonic currents at input current, measured at
V
i
= 230 VAC, I
o
= I
o nom
(LXN1601-6)
Fig. 5
Power factor versus load
Electrical Output Data
Table 6a: Output data of 375 Watt standard models. General conditions: T
A
= 25 °C, unless T
A
is specified; R input open-circuit
Model
LXR1601
LXR1701
LXR1801
Unit
Characteristics
Conditions
min
typ
max
min
typ
max
min
typ
max
V
o nom
Output voltage nominal
1
V
i nom
,
I
o nom
24.25
24.7
25.2
36.37
37.05
37.8
48.5
49.4
50.4
V
*
24.55
24.7
24.85
36.82
37.05
37.28
49.1
49.4
49.7
V
o worst
Output voltage range of
tolerance
V
i min
–
V
i max
,
I
o
= (0.1 –
1)
I
o nom
24.0
25.8
36.0
38.7
48.0
51.6
V
o L
Overvoltage protection
28.5
30
42.75
45
57
60
P
o nom
Nominal output power
V
i
= 100 V –
V
i max
371
371
371
W
I
o nom
Output current nominal
V
i
= 100 V –
V
i max
15
10
7.5
A
I
o L
Output current limit
3
V
i
= 100 V –
V
i max
15.1
17.2
10.1
11.4
7.57
8.7
I
op
Output current boost
4
typ. 1 s
22.5
15
11.3
Ripple and noise
V
i
= 230 VAC,
f
i
= 50 Hz,
I
o nom
100
100
100
mV
pp
1100
2
1200
2
1200
2
∆
V
o u
Static line regulation
100 VAC
–
V
i max,
I
o nom
±0.1
±0.15
±0.15
V
∆
V
o I
Static load regulation
(droop)
V
i nom
I
o
= (0.1 –
1)
I
o nom
–0.4
–0.6
–0.8
v
od
Dynamic load regulation
Voltage deviation
Recovery time
V
i nom ,
I
o
=
(0.5
↔
1)
I
o nom
±1.2
±1.5
±1.8
40
80
80
ms
α
vo
Temperature coefficient
T
C min
– T
C max
±0.02
±0.02
±0.02
%/K
t
or
Start-up time
V
i
=
0
→
V
i nom,
I
o nom
700
700
700
ms
t
oh min
Hold-up time
I
o nom,
V
o nom
→
0.8
V
o nom
15
20
25
* Converters with version V105 or higher
1
Setting voltage with open R-input
2
Superimposed low frequency ripple at 2 •
f
i
3
Rectangular current limit characteristic (continuous operation)
4
Short-term peak power capability 150% of
P
o nom
for approx. 1 s