11 Technical description
11.1 Control
panel
The control panel explained below is the only dryer user interface.
K
3
P
Q
S
0
0
4
7
T4
T3
T1
T2
set
log
info
ESC
reset
1
Main switch
2
Electronic control unit DMC 24
3
Air and refrigerant-gas flow chart
11.2 Functional
description
Operating principle
– All dryer models described in this manual function according to the same principle. The hot and
moisture-loaded air is led into an air/air heat exchanger. Afterwards, the air flows through an evaporator, which is also
known as an air/refrigerant heat exchanger. The air temperature is reduced to approximately 2°C, so that water vapour
condenses to liquid. The continuously accumulating condensate is collected in the separator to be discharged via the
condensate drain. Subsequently, the cold and dry air is led through the air/air heat exchanger, so that it is reheated to
up to 8°C below the inlet temperature when leaving the dryer.
Refrigeration cycle
– The refrigerant is conducted through the compressor and reaches a condenser under high
pressure. There, cooling-down takes place, making the refrigerant condense to a liquid state which is under high
pressure. The liquid is pressed through a capillary tube where the resulting pressure drop ensures that the refrigerant
evaporates at a defined temperature. The liquid refrigerant which is under low pressure is led into the heat exchanger,
where it expands. The cold resulting from the expansion serves to cool down the compressed air in the heat exchanger.
During this process, the refrigerant evaporates. The low-pressure gas is resupplied to the compressor, where it is
compressed again. It then re-enters the cycle. In phases of a reduced compressed-air load, the excess refrigerant is
resupplied automatically to the compressor via the hot gas bypass valve.
Summary of Contents for DRYPOINT RA 1080-8800
Page 24: ...Technical data 24 DRYPOINT RA 1080 8800 10 2 Technical data DRYPOINT RA 1080 8800 3 460 60 ...
Page 42: ...Maintenance troubleshooting spare parts and dismantling 42 DRYPOINT RA 1080 8800 ...
Page 45: ...Appendices DRYPOINT RA 1080 8800 45 13 1 2 Dimensions DRYPOINT RA 2400 4400 ...
Page 46: ...Appendices 46 DRYPOINT RA 1080 8800 13 1 3 Dimensions DRYPOINT RA 5400 6600 ...
Page 47: ...Appendices DRYPOINT RA 1080 8800 47 13 1 4 Dimensions DRYPOINT RA 7200 8800 ...
Page 49: ...Appendices DRYPOINT RA 1080 8800 49 13 2 2 Exploded diagram DRYPOINT RA 1080 2200 AC ...
Page 50: ...Appendices 50 DRYPOINT RA 1080 8800 13 2 3 Exploded diagram DRYPOINT RA 2400 4400 AC ...
Page 51: ...Appendices DRYPOINT RA 1080 8800 51 13 2 4 Exploded diagram DRYPOINT RA 5400 6600 AC ...
Page 52: ...Appendices 52 DRYPOINT RA 1080 8800 13 2 5 Exploded diagram DRYPOINT RA 7200 8800 AC ...
Page 53: ...Appendices DRYPOINT RA 1080 8800 53 13 2 6 Exploded diagram DRYPOINT RA 1080 2200 WC ...
Page 54: ...Appendices 54 DRYPOINT RA 1080 8800 13 2 7 Exploded diagram DRYPOINT RA 2400 4400 WC ...
Page 55: ...Appendices DRYPOINT RA 1080 8800 55 13 2 8 Exploded diagram DRYPOINT RA 5400 6600 WC ...
Page 56: ...Appendices 56 DRYPOINT RA 1080 8800 13 2 9 Exploded diagram DRYPOINT RA 7200 8800 WC ...
Page 71: ...Appendices DRYPOINT RA 1080 8800 71 ...
Page 72: ...Appendices 72 DRYPOINT RA 1080 8800 ...
Page 73: ...Declaration of conformity CE DRYPOINT RA 1080 8800 73 14 Declaration of conformity CE ...
Page 74: ...Declaration of conformity CE 74 DRYPOINT RA 1080 8800 ...