Technical description
BEKOBLIZZ® LC 12-355
33
11.17.5 Operation of the potential-free failure/alarm contact
The DMC 18 is equipped with a potential-free contact to indicate failures or alarm conditions.
4
5
chiller is switched on and no service warning/alarm is active.
4
5
chiller is off or a service warning/alarm is active.
11.17.6 Operating parameters – setup menu
The setup menu can be used to change the chiller’s operating parameters.
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is
not responsible for malfunctioning or failure due to modification to the operating parameters.
With chiller ON simultaneously press buttons
Set
+
for at least 5 seconds to enter the setup menu.
Access to the menu is confirmed by message
on the display (first parameter of menu).
Keep
Set
pressed to display the value of the selected parameter and use arrows
and
to change
the value. Release the button
Set
to confirm the value and skip to following parameter.
Press
+
to exit setup menu (if no button is pressed after 30 seconds the menu is exited
automatically).
ID Description Limits
Resolution
Standard
setup
HdS - High DewPoint Setting : Alarm threshold for a
high DewPoint (the alarm disappears when the
temperature drop 0.5°C / 1°F below alarm point)
0.0…25.0 °C or
32 … 77 °F
0.5 °C
or
1 °F
20
or
68
Hdd - High DewPoint Delay : high DewPoint alarm
enable delay
01 … 20
minutes
1 min
15
LdS - Low DewPoint Setting : Alarm threshold for a low
DewPoint (the alarm disappears when the temperature
becomes 0.5°C / 1°F higher than the alarm point)
-10 … 0.0 °C or
14 … 32 °F
0.5 °C
or
1 °F
-5
or
23
Ldd – Low DewPoint Delay : low DewPoint alarm
enable delay
01 … 20
minutes
1 min
5
SrV - Service Setting: setting of service warning timer.
00 = service warning timer disabled.
0.0 … 9.0
(x 1000) hours
0.5
(x1000) hours
8.0
SCL - Scale: display scale of temperatures.
°C … °F
-
°C
11.17.7 Selection of the Bekomat drain model
The DMC18 controls two types of BEKOMAT drains.
The correct settings are carried out in the factory and proper functioning is checked during the
final inspection of the chiller.
Summary of Contents for Bekoblizz LC 12-355
Page 23: ...Technical data BEKOBLIZZ LC 12 355 23 10 2 Technical data BEKOBLIZZ LC 55 355 1 230 50 ...
Page 24: ...Technical data 24 BEKOBLIZZ LC 12 355 10 3 Technical data BEKOBLIZZ LC 12 150 1 115 60 ...
Page 25: ...Technical data BEKOBLIZZ LC 12 355 25 10 4 Technical data BEKOBLIZZ LC 55 355 1 230 60 ...
Page 40: ...Maintenance troubleshooting spare parts and dismantling 40 BEKOBLIZZ LC 12 355 ...
Page 41: ...Maintenance troubleshooting spare parts and dismantling BEKOBLIZZ LC 12 355 41 ...
Page 44: ...Appendices 44 BEKOBLIZZ LC 12 355 13 1 2 Chiller dimensions BEKOBLIZZ LC 55 ...
Page 45: ...Appendices BEKOBLIZZ LC 12 355 45 13 1 3 Chiller dimensions BEKOBLIZZ LC 90 115 ...
Page 46: ...Appendices 46 BEKOBLIZZ LC 12 355 13 1 4 Chiller dimensions BEKOBLIZZ LC 150 240 ...
Page 47: ...Appendices BEKOBLIZZ LC 12 355 47 13 1 5 Chiller dimensions BEKOBLIZZ LC 355 ...
Page 49: ...Appendices BEKOBLIZZ LC 12 355 49 13 2 2 Exploded diagram BEKOBLIZZ LC 12 35 ...
Page 50: ...Appendices 50 BEKOBLIZZ LC 12 355 13 2 3 Exploded diagram BEKOBLIZZ LC 55 ...
Page 51: ...Appendices BEKOBLIZZ LC 12 355 51 13 2 4 Exploded diagram BEKOBLIZZ LC 90 115 ...
Page 52: ...Appendices 52 BEKOBLIZZ LC 12 355 13 2 5 Exploded diagram BEKOBLIZZ LC 150 240 ...
Page 53: ...Appendices BEKOBLIZZ LC 12 355 53 13 2 6 Exploded diagram BEKOBLIZZ LC 355 ...
Page 60: ...Appendices 60 BEKOBLIZZ LC 12 355 ...
Page 61: ...EC Declaration of Conformity BEKOBLIZZ LC 12 355 61 14 EC Declaration of Conformity ...
Page 62: ...EC Declaration of Conformity 62 BEKOBLIZZ LC 12 355 ...