![Beko Bekoblizz LC 12-355 Instructions For Installation And Operation Manual Download Page 17](http://html.mh-extra.com/html/beko/bekoblizz-lc-12-355/bekoblizz-lc-12-355_instructions-for-installation-and-operation-manual_17384017.webp)
Installation
BEKOBLIZZ® LC 12-355
17
8.4
Connection to the compressed-air system
Danger!
Compressed air!
All works must only be carried out by qualified skilled personnel.
Never work on compressed-air systems which are under pressure.
The operator or the user must ensure that the chiller is never operated with a pressure exceeding the
maximum pressure value indicated on the name plate.
Exceeding the maximum operating pressure can be dangerous for the operator but also for the device.
The air temperature and the air flow at the inlet of the chiller must lie within the limit values indicated on the name
plate. The connecting lines must be free from dust, iron rust, shards and other contaminations and correspond to the
flow rate of the chiller. Should air with a very high temperature be treated, the installation of an aftercooler may be
necessary. For the implementation of maintenance works, the installation of a bypass system is recommended.
Note!
Pulsation and vibrations!
Pulsations and vibrations must be eliminated from the compressed air and IN/OUT piping to avoid
possible fatigue failure.
Do not use the chiller to treat air containing corrosive substances for copper and its alloys..
CAUTION!
During the piping of the chiller, the inlet and outlet connections need to be supported as is shown in the
illustration.
Non-observance will cause damage.
===== Ende der Stückliste =====
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3) or poorer quality, we
recommend the additional installation of a prefilter (e.g. CLEARPOINT F040), to avoid clogging of the
heat exchanger.
8.5
Connection to the cooling-water network
Danger!
Compressed air and unqualified personnel!
All works must only be carried out by qualified skilled personnel.
Never work on compressed-air systems which are under pressure.
The user must ensure that the chiller is never operated with a pressure exceeding the nominal values.
Possible overpressure can be dangerous for the operator but also for the device.
The temperature and the amount of cooling water need to correspond to the limit values indicated on the name plate.
The cross-section of the connecting lines, which should preferably be flexible, must be free from dust, iron rust, shards
and other contaminations. We recommend employing connecting lines (flexible hoses, vibration-inhibiting fittings etc.)
which protect the chiller against possible vibrations in the pipework.
Note!
Contaminated intake water!
In the event that the intake water is strongly contaminated we recommend the additional installation of a
prefilter (500 micron), to avoid clogging of the heat exchanger.
Summary of Contents for Bekoblizz LC 12-355
Page 23: ...Technical data BEKOBLIZZ LC 12 355 23 10 2 Technical data BEKOBLIZZ LC 55 355 1 230 50 ...
Page 24: ...Technical data 24 BEKOBLIZZ LC 12 355 10 3 Technical data BEKOBLIZZ LC 12 150 1 115 60 ...
Page 25: ...Technical data BEKOBLIZZ LC 12 355 25 10 4 Technical data BEKOBLIZZ LC 55 355 1 230 60 ...
Page 40: ...Maintenance troubleshooting spare parts and dismantling 40 BEKOBLIZZ LC 12 355 ...
Page 41: ...Maintenance troubleshooting spare parts and dismantling BEKOBLIZZ LC 12 355 41 ...
Page 44: ...Appendices 44 BEKOBLIZZ LC 12 355 13 1 2 Chiller dimensions BEKOBLIZZ LC 55 ...
Page 45: ...Appendices BEKOBLIZZ LC 12 355 45 13 1 3 Chiller dimensions BEKOBLIZZ LC 90 115 ...
Page 46: ...Appendices 46 BEKOBLIZZ LC 12 355 13 1 4 Chiller dimensions BEKOBLIZZ LC 150 240 ...
Page 47: ...Appendices BEKOBLIZZ LC 12 355 47 13 1 5 Chiller dimensions BEKOBLIZZ LC 355 ...
Page 49: ...Appendices BEKOBLIZZ LC 12 355 49 13 2 2 Exploded diagram BEKOBLIZZ LC 12 35 ...
Page 50: ...Appendices 50 BEKOBLIZZ LC 12 355 13 2 3 Exploded diagram BEKOBLIZZ LC 55 ...
Page 51: ...Appendices BEKOBLIZZ LC 12 355 51 13 2 4 Exploded diagram BEKOBLIZZ LC 90 115 ...
Page 52: ...Appendices 52 BEKOBLIZZ LC 12 355 13 2 5 Exploded diagram BEKOBLIZZ LC 150 240 ...
Page 53: ...Appendices BEKOBLIZZ LC 12 355 53 13 2 6 Exploded diagram BEKOBLIZZ LC 355 ...
Page 60: ...Appendices 60 BEKOBLIZZ LC 12 355 ...
Page 61: ...EC Declaration of Conformity BEKOBLIZZ LC 12 355 61 14 EC Declaration of Conformity ...
Page 62: ...EC Declaration of Conformity 62 BEKOBLIZZ LC 12 355 ...