background image

36 / 120 EN

Split-type room air conditioner / Installation Manual

5. After checking to make sure every connection is secure, loop the wires around to prevent rain water 

from flowing into the terminal.

6. Using the cable clamp, fasten the cable to the unit. Screw the cable clamp down tightly.
7. Insulate unused wires with PVC electrical tape. Arrange them so that they do not touch any 

electrical or metal parts.

8. Replace the wire cover on the side of the unit, and screw it in place.

Cover

Outdoor Unit Wiring Diagram is located 

on the inside of the wire cover on the 

outdoor unit.

Fig. 6.6

Outdoor unit installation

Summary of Contents for BEHPI 090

Page 1: ...Split type room air conditioner Installation Manual EN SI BEHPI 090 BEHPI 091 BEHPI 120 BEHPI 121 BEHPI 180 BEHPI 181 BEHPI 240 BEHPI 241 02M 8899283200 4920 01 ...

Page 2: ......

Page 3: ...Note on pipe length 37 7 2 Connection instructions refrigerant piping 37 7 3 Instructions for connecting piping to indoor unit 41 7 4 Instructions for connecting piping to outdoor unit 42 8 Air evacuation 44 8 1 Preparations and precautions 44 8 2 Evacuation instructions 44 9 Electrical and gas leak checks 48 9 1 Electrical safety checks 48 9 2 Gas leak checks 49 10Test run 50 10 1 Before test run...

Page 4: ...other than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrigeration cycle This can cause explosion and injury t Do not allow children to play with the air conditioner Children must be supervised around the unit at all times t Installationmustbeperformedbyanauthorizeddealerorspeciali...

Page 5: ...t other appliances to the same outlet Insufficient electrical capacity or defects in electrical work can cause electrical shock or fire t For all electrical work use the specified cables Connect cables tightly and clamp them securely to prevent external forces from damaging the terminal Improper electrical connections can overheat and cause fire and may also cause shock t Allwiringmustbeproperlyar...

Page 6: ... for example open flames an operating gas appliance or an operating electric heater 2 Do not pierce or burn 3 Appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specific for operation 4 Be aware that refrigerants may not contain an odour C Note Clause 1 to 4 are required for the units adopt R32 R290 Refrigerant Warning t Forunitsthathaveanauxili...

Page 7: ...dgasses 1 Thisair conditioningunitcontainsfluorinatedgasses Forspecificinformationonthetypeofgasandthe amount pleaserefertotherelevantlabelontheunit itself 2 Installation service maintenanceandrepairofthisunit mustbeperformedbyacertifiedtechnician 3 Productuninstallationandrecyclingmustbeperformed byacertifiedtechnician 4 Ifthesystemhasaleak detectionsysteminstalled it mustbecheckedforleaksatleast...

Page 8: ...install the air conditioner Improper installation may result in water leakage electrical shock and fire or cause the equipment to fail Name Shape Quantity Mounting plate 1 Clip anchor 5 Mounting plate fixing screw ST3 9 X 25 5 Remote controller 1 Fixing screw for remote controller holder ST2 9 x 10 2 Optional Parts Remote controller holder 1 Dry battery AAA LR03 2 2 Accessories ...

Page 9: ...nual EN 02M 8899283200 4920 01 Split type room air conditioner Installation Manual EN SI BEHPI 090 BEHPI 091 BEHPI 120 BEHPI 121 BEHPI 180 BEHPI 181 BEHPI 240 BEHPI 241 02M 8899283200 4920 01 Split type room air conditioner User Manual EN SI BEHPI 090 BEHPI 091 BEHPI 120 BEHPI 121 BEHPI 180 BEHPI 181 BEHPI 240 BEHPI 241 02M 8899283200 4920 01 ...

Page 10: ...32 frigerant models Appliance shall be installed operated and stored in a room with a floor area larger than 4m2 Appliance shall not be installed in an unvertilated space if that space is smaller than 4m2 For R290 refrigerant models the minimum room size needed 9000Btu h units 13m2 9000Btu h and 12000Btu h units 17m2 12000Btu h and 18000Btu h units 26m2 18000Btu h and 24000Btu h units 35m2 2 Acces...

Page 11: ...allation Manual 11 120 EN 12cm 4 75in 15cm 5 9in 12cm 4 75in 2 3m 90 55in Select Installation Location Page 14 Determine Wall Hole Position Page 15 3 Attach Mounting Plate Page 15 Drill Wall Hole Page 16 3 Installation summary indoor unit ...

Page 12: ...it type room air conditioner Installation Manual 5 Connect Piping Page 37 Connect Wiring Page 22 Prepare Drain Hose Page 18 Wrap Piping and Cable Page 25 Mount Indoor Unit Page 26 3 Installation summary indoor unit ...

Page 13: ... 4 Signal Cable 5 Refrigerant Piping 6 Remote Holder 7 Remote Control Some Units 8 Outdoor Unit Power Cable Some Units 9 Functional Filter On Front of Main Filter Some Units 10 Louver 11 Front Panel C Note Illustrationsinthismanualareforexplanatorypurposes Theactualshapeofyourindoor unitmaybeslightlydifferent Theactualshapeshallprevail 4 Unit parts ...

Page 14: ...ropriate location for the unit Proper installation locations meet the following standards t Good air circulation t Convenient drainage t Noise from the unit will not disturb other people t Firm and solid the location will not vibrate t Strong enough to support the weight of the unit t A location at least one meter from all other electrical devices e g TV radio computer DO NOT install unit in the f...

Page 15: ...15cm 5 9in or more 12cm 4 75in or more 12cm 4 75in or more 2 3m 90 55in or more Fig 5 1 Step 2 Attach mounting plate to wall The mounting plate is the device on which you will mount the indoor unit 1 Remove the screw that attaches the mounting plate to the back of the indoor unit 2 Place the mounting plate against the wall in a location that meets the standards in the Select Installation Location ...

Page 16: ... on the position of the mounting plate Refer to Mounting Plate Dimensions on the next page to help you determine the optimal position The wall hole should have a 65mm 2 5in diameter at least and at a slightly lower angle to facilitate drainage 2 Using a 65 mm 2 5in core drill drill a hole in the wall Make sure that the hole is drilled at a slight downward angle so that the outdoor end of the hole ...

Page 17: ... plate t Height of indoor unit relative to plate t Recommended position of wall hole both to the left and right of mounting plate t Relative distances between screw holes Correct orientation of Mounting Plate Indoor unit outline Indoor unit outline Right rear wall hole 65mm 2 5in Right rear wall hole 65mm 2 5in Left rear wall hole 65mm 2 5in 348 4mm 13 7in 426mm 16 8in 101mm 4in 192mm 7 55in 722mm...

Page 18: ...47mm 1 85in 47mm 1 85in 40mm 1 55in Step 4 Prepare refrigerant piping The refrigerant piping is inside an insulating sleeve attached to the back of the unit You must prepare the piping before passing it through the hole in the wall Refer to the Refrigerant Piping Connection section of this manual for detailed instructions on pipe flaring and flare torque requirements technique etc 1 Based on the p...

Page 19: ... piping connect the indoor unit s refrigerant piping to the connective piping that will join the indoor and outdoor units Refer to the Refrigerant Piping Connection section of this manual for detailed instructions 5 Based on the position of the wall hole relative to the mounting plate determine the necessary angle of your piping 6 Grip the refrigerant piping at the base of the bend 7 Slowly with e...

Page 20: ...tach drain hose extension purchased separately to the end of drain hose 3 Wrap the connection point firmly with Teflon tape to ensure a good seal and to prevent leaks 4 For the portion of the drain hose that will remain indoors wrap it with foam pipe insulation to prevent condensation 5 Remove the air filter and pour a small amount of water into the drain pan to make sure that water flows from the...

Page 21: ...ure proper drainage NOT CORRECT Kinks in the drain hose will create water traps NOT CORRECT Kinks in the drain hose will create water traps NOT CORRECT Do not place the end of the drain hose in water or in containers that collect water This will prevent proper drainage Fig 5 5 Fig 5 7 Fig 5 6 Fig 5 8 5 Indoor unit installation ...

Page 22: ...olesandhasacontactseparationofatleast1 8in 3mm mustbeincorporatedinthe fixedwiring Thequalifiedtechnicianmustuseanapprovedcircuitbreakerorswitch 7 Onlyconnecttheunittoanindividualbranchcircuitoutlet Donotconnectanother appliancetothatoutlet 8 Makesuretoproperlygroundtheairconditioner 9 Everywiremustbefirmlyconnected Loosewiringcancausetheterminaltooverheat resultinginproductmalfunctionandpossiblef...

Page 23: ...s determined by the maximum current of the unit The maximum current is indicated on the nameplate located on the side panel of the unit Refer to this nameplate to choose the right cable fuse or switch Take note of fuse specifications The air conditioner s circuit board PCB is designed with a fuse to provide overcurrent protection The specifications of the fuse are printed on the circuit board such...

Page 24: ... right side of the unit This will reveal the terminal block Terminal block Wire cover Screw Cable clamp Fig 5 9 The Wiring Diagram is located on the inside of the indoor unit s wire cover A Warning Allwiringmustperformedstrictlyinaccordancewiththe wiringdiagramlocatedontheinsideoftheindoorunits wirecover 4 Unscrew the cable clamp below the terminal block and place it to the side 5 Facing the back ...

Page 25: ...ssing the piping drain hose and the signal cable through the wall hole you must bundle them together to save space protect them and insulate them 1 Bundle the drain hose refrigerant pipes and signal cable according to Fig 5 10 Indoor Unit Space behind unit Refrigerant piping Insulation tape Signal wire Drain hose Fig 5 10 Drain hose must be on bottom Make sure that the drain hose is at the bottom ...

Page 26: ... sealed to prevent dirt or foreign materials from entering the pipes 3 Slowly pass the wrapped bundle of refrigerant pipes drain hose and signal wire through the hole in the wall 4 Hook the top of the indoor unit on the upper hook of the mounting plate 5 Check that unit is hooked firmly on mounting by applying slight pressure to the left and right hand sides of the unit The unit should not jiggle ...

Page 27: ...he bracket or wedge that is propping up the unit 7 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate Unit is adjustable Keep in mind that the hooks on the mounting plate are smaller than the holes on the back of the unit If you find that you don t have ample room to connect embedded pipes to the...

Page 28: ...at will help you choose an appropriate location for the unit Proper installation locations meet the following standards t Meets all spatial requirements shown in Installation Space Requirements Fig 6 1 t Good air circulation and ventilation t Firm and solid the location can support the unit and will not vibrate t Noise from the unit will not disturb others t Protected from prolonged periods of dir...

Page 29: ...disturb others t Near animals or plants that will be harmed by hot air discharge t Near any source of combustible gas t In a location that is exposed to large amounts of dust t In a location exposed to a excessive amounts of salty air Special considerations for extreme weather If the unit is exposed to heavy wind Install unit so that air outlet fan is at a 90 angle to the direction of the wind If ...

Page 30: ...uire a drain joint Before bolting the outdoor unit in place you must install the drain joint at the bottom of the unit Note that there are two different types of drain joints depending on the type of outdoor unit If the drain joint comes with a rubber seal see Fig 6 4 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain joi...

Page 31: ... A B Base pan hole of outdoor unit Seal Drain joint Seal Fig 6 4 A In cold climates Incoldclimates makesurethatthedrainhoseisasverticalaspossibletoensureswift waterdrainage Ifwaterdrainstooslowly itcanfreezeinthehoseandfloodtheunit Step 3 Anchor outdoor unit The outdoor unit can be anchored to the ground or to a wall mounted bracket Unit mounting dimensions The following is a list of different out...

Page 32: ...1 6 325 12 8 700x550x275 27 5 x21 6 x10 82 450 17 7 260 10 24 770x555x300 30 3 x21 85 x11 81 487 19 2 298 11 73 800x554x333 31 5 x21 8 x13 1 514 20 24 340 13 39 845x702x363 33 25 x27 63 x14 29 540 21 26 350 13 8 900x860x315 35 4 x33 85 x12 4 590 23 2 333 13 1 945x810x395 37 2 x31 9 x15 55 640 25 2 405 15 95 946x810x420 37 21 x31 9 x16 53 673 26 5 403 15 87 946x810x410 37 21 x31 9 x16 14 673 26 5 4...

Page 33: ...theweightoftheunit 1 Mark the position of bracket holes based on dimensions in the Unit Mounting Dimensions chart 2 Pre drill the holes for the expansion bolts 3 Clean dust and debris away from holes 4 Place a washer and nut on the end of each expansion bolt 5 Thread expansion bolts through holes in mounting brackets put mounting brackets in position and hammer expansion bolts into the wall 6 Chec...

Page 34: ...r to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1 8in 3mm must be incorporated in the fixed wiring The qualified technician must use an approved circuit breaker or switch 7 Only connect the unit to an individual branch circuit outlet Do not connect another appliance to that outlet 8 Make sure to properly ground the air conditioner 9...

Page 35: ... inside b Strip the insulation from the ends of the wires c Using a wire crimper crimp u lugs on the ends of the wires Pay attention to live wire While crimping wires make sure you clearly distinguish the Live L Wire from other wires A Warning All wiring must performed strictly in accordance with the wiringdirgramlocatedinsidetheoutdoorunitswirecover 2 Unscrew the electrical wiring cover and remov...

Page 36: ... the cable clamp fasten the cable to the unit Screw the cable clamp down tightly 7 Insulate unused wires with PVC electrical tape Arrange them so that they do not touch any electrical or metal parts 8 Replace the wire cover on the side of the unit and screw it in place Cover Outdoor Unit Wiring Diagram is located on the inside of the wire cover on the outdoor unit Fig 6 6 6 Outdoor unit installati...

Page 37: ...ight m R410A inverter split air conditioner 15 000 25 82ft 10 33ft 15 000 and 24 000 30 98 5ft 20 66ft 24 000 and 36 000 50 164ft 25 82ft 36 000 and 60 000 65 213ft 30 98 5ft 7 2 Connection instructions refrigerant piping Step 1 Cut pipes When preparing refrigerant pipes take extra care to cut and flare them properly This will ensure efficient operation and minimize the need for future maintenance...

Page 38: ...t piping connection They must be completely removed 1 Hold the pipe at a downward angle to prevent burrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Point down Reamer Fig 7 2 Step 3 Flare pipe ends Proper flaring is essential to achieve an airtight seal 1 After removing burrs from cut pipe seal the ends with PVC tape to preve...

Page 39: ...PVC tape from ends of pipe when ready to perform flaring work 5 Clamp flare form on the end of the pipe The end of the pipe must extend beyond the edge of the flare form in accordance with the dimensions shown in the table below Fig 7 4 Piping extension beyond flare form Outer diameter of pipe mm A mm Min Max Ø 6 35 Ø 0 25 0 7 0 0275 1 3 0 05 Ø 9 52 Ø 0 375 1 0 0 04 1 6 0 063 Ø 12 7 Ø 0 5 1 0 0 04...

Page 40: ...e form then inspect the end of the pipe for cracks and even flaring Step 4 Connect pipes When connecting refrigerant pipes be careful not to use excessive torque or to deform the piping in any way You should first connect the low pressure pipe then the high pressure pipe Minimum bend radius When bending connective refrigerant piping the minimum bending radius is 10cm See Fig 7 6 Radius 10cm 4in Fi...

Page 41: ...r grip the nut on the unit tubing 4 While firmly gripping the nut on the unit tubing use a torque wrench to tighten the flare nut according to the torque values in the Torque Requirements table below Loosen the flaring nut slightly then tighten again Fig 7 8 Torque requirements Outer diameter of pipe mm 5ʣHIUFOʣOH UPSRVF tDN EE UʣHIUFOʣOH UPSRVF tN Ø 6 35 Ø 0 25 MC t GU MC t GU Ø 9 52 Ø 0 375 MC t...

Page 42: ...he cover from the packed valve on the side of the outdoor unit See Fig 7 9 Valve cover Fig 7 9 2 Remove protective caps from ends of valves 3 Align flared pipe end with each valve and tighten the flare nut as tightly as possible by hand 4 Using a spanner grip the body of the valve Do not grip the nut that seals the service valve See Fig 7 10 C Usespannertogripmainbodyofvalve Torquefromtighteningth...

Page 43: ...g 7 10 5 While firmly gripping the body of the valve use a torque wrench to tighten the flare nut according to the correct torque values 6 Loosen the flaring nut slightly then tighten again 7 Repeat Steps 3 to 6 for the remaining pipe 7 Refrigerant piping connection ...

Page 44: ...nd moisture from the system Evacuation should be performed upon initial installation and when unit is relocated Before performing evacuation t Check to make sure that both highpressure and low pressure pipes between the indoor and outdoor units are connected properly in accordance with the Refrigerant Piping Connection section of this manual t Check to make sure all wiring is connected properly 8 ...

Page 45: ...pound Meter reads 76cmHG 105 Pa 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that there has been no change in system pressure 8 If there is a change in system pressure refer to Gas Leak Check section for information on how to check for leaks If there is no change in system pressure unscrew the cap from the packed valve high pressu...

Page 46: ... further using a torque wrench if needed C Openvalvestemsgently Whenopeningvalvestems turnthehexagonalwrenchuntilithitsagainstthestopper Donottrytoforcethevalvetoopenfurther C Noteonaddingrefrigerant Some systems require additional charging depending on pipe lengths The standard pipe length varies according to local regulations For example in North America the standard pipe length is 7 5m 25 In ot...

Page 47: ...Z ft Inverter R410A Pipe length standard length x 15g m Pipe length standard length x 0 16oZ ft Fixed frequency R410A Pipe length standard length x 20g m Pipe length standard length x 0 21oZ ft Liquid Side Ø 9 52 ø 0 375 R22 Pipe length standard length x 60g m Pipe length standard length x 0 64oZ ft Inverter R410A Pipe length standard length x 30g m Pipe length standard length x 0 32oZ ft Fixed fr...

Page 48: ... be less than 4 Note This may not be required for some locations in the US During test run Check for Electrical Leakage During the Test Run use an electroprobe and multimeter to perform a comprehensive electrical leakage test If electrical leakage is detected turn off the unit immediately and call a licensed electrician to find and resolve the cause of the leakage Note This may not be required for...

Page 49: ...d detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If using leak detector refer to the device s operation manual for proper usage instructions After performing gas leak checks After confirming that the all pipe connection points DO NOT leak replace the valve cover on the outside unit 9 Electrical and gas leak ...

Page 50: ... button on the remote controller to turn it on 3 Press the MODE button to scroll through the following functions one at a time t COOL Select lowest possible temperature t HEAT Select highest possible temperature 4 Let each function run for 5 minutes and perform the following checks List of checks to perform Pass Fail No electrical leakage Unit is properly grounded All electrical terminals properly...

Page 51: ... following a Using remote control return unit to normal operating temperature b Using insulation tape wrap the indoor refrigerant pipe connections that you left uncovered during the indoor unit installation process If ambient temperature is below 17 C 63 F You can t use the remote controller to turn on the COOL function when the ambient temperature is below 17 C In this instance you can use the MA...

Page 52: ...52 120 EN Do not C 11 ...

Page 53: ...cycling should be carried out by natural persons that hold relevant certificates If the system has a leakage detection system installed leakage checks should be performed at least every 12 months make sure system operate properly If product must be performed leakage checks it should specify Inspection cycle establish and save records of leakage checks C Note For hermetically sealed equipment porta...

Page 54: ... for use with flammable refrigerants i e no sparking adequately sealed or intrinsically safe 5 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts appropriate fire extinguishing equipment shall be available to hand Have a dry power or CO2 fire extinguisher adjacent to the charging area 6 No ignition sources No person carrying out ...

Page 55: ...rical components shall include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is necessary to continue operation and adequate temporary solution shall be used This shall be reported to the own...

Page 56: ...ontinual vibration from sources such as compressors or fans 13 Detection of flammable refrigerants Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks A halide torch or any other detector using a naked flame shall not be used 14 Leak detection methods The following leak detection methods are deemed acceptable for systems contain...

Page 57: ...rk to take place This operation is absolutely vital if brazing operations on the pipe work are to take place Ensure that the outlet for the vacuum pump is not closed to any ignition sources and there is ventilation available 16 Charging procedures In addition to conventional charging procedures the following requirements shall be followed t Ensure that contamination of different refrigerants does ...

Page 58: ...nder even temporarily j When the cylinders have been filled correctly and the process completed make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off k Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked 18 Labelling Equipment shall be labelled stating th...

Page 59: ...mpressor oils are to be removed ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant The evacuation process shall be carried out prior to returning the compressor to the suppliers Only electric heating to the compressor body shall be employed to accelerate this process When oil is drained from a system it shall ...

Page 60: ......

Page 61: ...ilnega sredstva 95 7 3 Navodila za priključitev cevi na notranjo enoto 99 7 4 Navodila za priključitev cevi na zunanjo enoto 100 8 Izpraznitev zraka 102 8 1 Priprave in previdnostni ukrepi 102 8 2 Navodila za praznjenje 102 9 Preverjanje električne napeljave in preverjanje uhajanja plina 106 9 1 Preverjaje varnosti električne napeljave 106 9 2 Preverjanje uhajanja plina 107 10Preskus delovanja 108...

Page 62: ...redstvapazite davenotoneprodrejo druge snovi ali plini razen navedenega hladilnega sredstva Prisotnostdrugihplinovalisnovizmanjšazmogljivostenoteinlahko povzroči neobičajno visok tlak v hladilnem ciklu To lahko povzroči eksplozij ali poškodbo t Otrokomnedovolite daseigrajosklimatskonapravo Otrokemorate v bližini enote ves čas nadzirati t Napravo mora namestiti pooblaščeni prodajalec ali strokovnja...

Page 63: ...ujte drugih naprav v isto vtičnico Nezadostna električna zmogljivost ali napake v električni inštalaciji lahko povzročijo električni udar ali požar t Za vso električno inštalacijo uporabite navedene kable Kable tesno povežite in jih trdno spnite da preprečite da bi zunanje sile poškodovale terminal Nepravilne električne povezave se lahko pregrejejo ter povzročijo požar in električni udar t Vsa ele...

Page 64: ...i delujoč električni grelnik 2 Naprave ne luknjajte ali sežigajte 3 Napravo hranite v dobro prezračenem območju kjer velikost prostora ustreza območju prostora ki je navedeno za delovanje 4 Upoštevajte da je hladilno sredstvo lahko brez vonja C Opomba Točke 1 do 4 so zahtevane za enote ki uporabljajo hladilno sredstvo R32 R290 Opozorilo t Enot s pomožnim električnim grelnikom ne namestite v območj...

Page 65: ...fluoriranih plinov 1 Klimatska naprava vsebuje fluorirane pline Za natančne informacije o vrsti in količini plina si oglejte ustrezno oznako nameščeno na sami enoti 2 Namestitev servisiranje vzdrževanje in popravilo enote mora izvesti certificiran tehnik 3 Izdelek mora odstraniti in reciklirati certificiran tehnik 4 Če je v izdelku nameščen sistem za zaznavanje uhajanja ga morate preveriti za uhaj...

Page 66: ... dodatno opremo Napačna namestitev lahko privede do iztekanja vode električnih udarov in požara ali povzroči okvaro opreme Ime Oblika Količina Montažna plošča 1 Zidni vložek 5 Pritrdilni vijak za montažno ploščo ST3 9 X 25 5 Daljinski upravljalnik 1 Pritrdilni vijak za nosilec daljinskega upravljalnika ST2 9 x 10 2 Izbirni deli Nosilec daljinskega upravljalnika 1 Suha baterija AAA LR03 2 2 Dodatki...

Page 67: ...er Manual EN 02M 8899283200 4920 01 Split type room air conditioner Installation Manual EN SI BEHPI 090 BEHPI 091 BEHPI 120 BEHPI 121 BEHPI 180 BEHPI 181 BEHPI 240 BEHPI 241 02M 8899283200 4920 01 Split type room air conditioner User Manual EN SI BEHPI 090 BEHPI 091 BEHPI 120 BEHPI 121 BEHPI 180 BEHPI 181 BEHPI 240 BEHPI 241 02M 8899283200 4920 01 ...

Page 68: ...stvom R32 Naprava mora biti nameščena se mora uporabljati in biti shranjena v prostoru s talno površino večjo od 4 m2 Naprava ne sme biti nameščena v neprezračenem prostoru manjšem od 4 m2 Za modele s hladilnim sredstvom R290 je najmanjša zahtevana velikost prostora naslednja Enote 9000 Btu h 13 m2 Enote 9000 Btu h in 12000 Btu h 17 m2 Enote 12000 Btu h in 18000 Btu h 26 m2 Enote 18000 Btu h in 24...

Page 69: ...69 120 SI 12 cm 4 75 in 15 cm 5 9 in 12 cm 4 75 in 2 3 m 90 55 in Izberite mesto za namestitev stran 72 Določite položaj luknje v steni stran 73 3 Namestite montažno ploščo stran 73 Izvrtajte luknjo v steno stran 74 3 Kratek pregled namestitve notranja enota ...

Page 70: ...a Navodila za namestitev 5 Priključite cevi stran 95 Priključite električno napeljavo stran 80 Pripravite cev za odvajanje vode stran 76 Ovijte cevi in kable stran 83 Namestite notranjo enoto stran 84 3 Kratek pregled namestitve notranja enota ...

Page 71: ...dstva 6 Nosilec daljinskega upravljalnika 7 Daljinski upravljalnik pri nekaterih enotah 8 Napajalni kabel zunanje enote pri nekaterih enotah 9 Funkcionalni filter na sprednji strani glavnega filtra pri nekaterih enotah 10 Loputa 11 Sprednja plošča C Opomba Ilustracije v tem priročniku so samo za obrazložitvene namene Dejanska oblika vaše notranje enote se lahko nekoliko razlikuje Pomembna je dejan...

Page 72: ...o namestitve za enoto Ustrezna mesta namestitve izpolnjujejo naslednje standarde t Dobro kroženje zraka t Priročno odvajanje t Hrup iz enote ne bo motil drugih oseb t Trdno in stabilno mesto namestitve mora biti brez vibracij t Dovolj močno da podpira težo enote t Mesto ki je najmanj en meter oddaljeno od drugih električnih naprav npr televizorja radia računalnika Enote NE nameščajte na naslednjih...

Page 73: ...5 cm 5 9 in ali več 12 cm 4 75 in ali več 12 cm 4 75 in ali več 2 3 m 90 55 in ali več Skica 5 1 2 korak Namestite montažno ploščo na steno Montažna plošča je pripomoček na katerega namestite notranjo enoto 1 Odstranite vijak s katerim je montažna plošča pritrjena na zadnjo stran notranje enote 2 Montažno ploščo položite ob steno na mestu ki izpolnjuje standarde v koraku Izberite mesto za namestit...

Page 74: ...ložaj montažne plošče Za pomoč pri določitvi optimalnega položaja glejte razdelek Dimenzije montažne plošče na naslednji strani Luknja v steni mora imeti premer najmanj 65 mm 2 5 palca in nekoliko nižji kot za lažje odvajanje vode 2 Izvrtajte luknjo v steno s kronskim vrtalnikom premera 65 mm 2 5 palca Luknjo morate izvrtati pod kotom nekoliko navzdol tako da je zunanji del luknje nižje od notranj...

Page 75: ...ščo t Priporočeni položaj luknje v steni levo in desno od montažne plošče t Relativne razdalje med luknjami za vijake Pravilna usmerjenost montažne plošče Obris notranje enote Obris notranje enote Izvrtina v steni na desni strani zadaj 65 mm 2 5 in Izvrtina v steni na desni strani zadaj 65 mm 2 5 in Izvrtina v steni na levi strani zadaj 65 mm 2 5 in 348 4 mm 13 7 in 426 mm 16 8 in 101 mm 4 in 192 ...

Page 76: ...52 mm 2 05 in 58 mm 2 3 in 319 mm 12 55 in 335 mm 13 2 in 362 mm 14 25 in 57 mm 2 25 in 47 mm 1 85 in 47 mm 1 85 in 40 mm 1 55 in 4 korak Pripravite cev hladilnega sredstva Cev hladilnega sredstva se nahaja v izolacijskem rokavu nameščenem na zadnji strani enote Cev morate pripraviti preden jo napeljete skozi luknjo v steni Glejte razdelek Povezava cevi hladilnega sredstva v tem priročniku za podr...

Page 77: ...Če cev ni vgrajena priključite cev hladilnega sredstva notranje enote na povezovalno cev s čimer boste povezali notranjo in zunanjo enoto Za podrobna navodila glejte razdelek Povezava cevi hladilnega sredstva 5 Na podlagi položaja luknje v steni glede na montažno ploščo določite potreben kot za cevi 6 Cev hladilnega sredstva primite na jedru upogiba 7 Cev počasi in z enakomernim pritiskom upognite...

Page 78: ...e podaljšek cevi na voljo ločeno 3 Priključnotočkotrdnoovijtesteflonskimtrakom dazagotovitedobrotesnjenjeinpreprečiteiztekanja 4 Del cevi za odvajanje ki bo ostal v notranjih prostorih ovijte s penasto izolacijo za cevi da preprečite kondenzacijo 5 Odstranite filter za zrak in zlijte malo količino vode v posodo za odvajanje da se prepričate da voda nemoteno izteka iz enote C Opomba glede postavitv...

Page 79: ...strezno odvajanje vode NAPAČNO Upogibanje cevi za odvajanje vode povzroči vodne pasti NAPAČNO Upogibanje cevi za odvajanje vode povzroči vodne pasti NAPAČNO Konca cevi za odvajanje vode ne postavite v vodo ali v posodo za zbiranje vode S tem bi preprečili pravilno odvajanje vode Skica 5 5 Skica 5 7 Skica 5 6 Skica 5 8 5 Montaža notranje enote ...

Page 80: ...i zagotavlja izklop napajanja na vseh polih in ima med kontakti razmik vsaj 1 8 palca 3 mm Odobren odklopnik ali stikalo mora uporabljati usposobljen tehnik 7 Enoto priključite samo na ločeno vtičnico odcepnega tokokroga V tisto vtičnico ne priključujte drugih naprav 8 Klimatsko napravo morate ustrezno ozemljiti 9 Vsaka žica mora biti trdno povezana Ohlapno ožičenje lahko povzroči pregrevanje term...

Page 81: ...a varovalke ali stikala si oglejte napisno ploščico Upoštevajte specifikacije varovalke Ploščatiskanegavezja PCB klimatskenapravejeopremljenazvarovalkozaprenapetostnozaščito Specifikacijevarovalkesonavedenenaploščitiskanegavezja mednjimi T3 15A 250VAC T5A 250VACitd Notranja enota T5A 250VAC Zunanja enota velja samo za enote ki uporabljajo hladilno sredstvo R32 ali R290 T20A 250VAC 18000Btu h enot ...

Page 82: ...a biti izvedeno strogo v skladu z diagramom ožičenja ki se nahaja na notranji strani pokrova za žice na notranji enoti 4 Odvijte kabelsko spojko pod priključnim blokom in jo postavite ob stran 5 Ko ste obrnjeni proti zadnji strani enote odstranite plastično ploščo na spodnji levi strani 6 Skozi to režo napeljite signalni kabel z zadnje strani enote proti sprednji 7 Ko ste obrnjeni proti sprednji s...

Page 83: ...skladu s skico 5 10 Notranja enota Prostor za enoto Cev hladilnega sredstva Izolacijski trak Signalni kabel cev za odtekanje vode Skica 5 10 Cev za odvajanje vode mora biti spodaj Cev za odvajanje mora biti v snopu spodaj Če postavite cev za odvajanje vode v snopu zgoraj lahko pride do prevelikega pretoka v posodo za odvajanje kar lahko povzroči požar ali škodo na vodah Signalnega kabla ne preplet...

Page 84: ...ode in signalnega kabla skozi izvrtino v steni 4 Obesite zgornji del notranje enote na zgornji kavelj montažne plošče 5 Prepričajte se da je enota trdno nameščena na montažni plošči tako da jo narahlo potisnete navzdol na levi in desni strani enote Enota se ne sme zibati ali premikati 6 Z enakomernim pritiskom potiskaje navzdol spodnjo polovico enote Enoto potiskajte navzdol dokler se ne zaskoči n...

Page 85: ...čno točko z izolacijskim trakom 6 Odstranite nosilec ali zagozdo ki podpira enoto 7 Z enakomernim pritiskom potiskaje navzdol spodnjo polovico enote Enoto potiskajte navzdol dokler se ne zaskoči na kavlje ob dnu montažne plošče Enota je prilagodljiva Kavlji na montažni plošči so manjši kot luknje na zadnji strani enote Če nimate dovolj prostora za priključitev vgrajenih cevi na notranjo enoto lahk...

Page 86: ...jo katerih boste izbrali ustrezno mesto namestitve za enoto Ustrezna mesta namestitve izpolnjujejo naslednje standarde t Izpolnjuje prostorske zahteve prikazane v prostorskih zahtevah za namestitev skica 6 1 t Dobro kroženje zraka in prezračenost t Trdno in stabilno mesto namestitve mora podpirati enoto in biti brez vibracij t Hrup iz enote ne bo motil drugih oseb t Zaščiteno pred daljšimi obdobji...

Page 87: ...ali kjer bi hrup iz enote motil druge osebe t V bližini živali ali rastlin ki bi jih lahko poškodoval izpust vročega zraka t V bližini virov vnetljivih plinov t Na mestih izpostavljenih večjim količinam prahu t Na mestih izpostavljenih večji količini slanega zraka Kaj morate upoštevati pri skrajnih vremenskih pogojih Če je enota izpostavljena močnemu vetru Enoto namestite tako da je izhodni ventil...

Page 88: ...h s toplotno črpalko potrebujete odtočni spoj Preden zunanjo enoto privijete na mesto morate na njeni spodnji strani namestiti odtočni spoj Na voljo sta dve različni vrsti odtočnih spojev odvisno od vrste zunanje enote Če je odtočni spoj opremljen z gumijastim tesnilom glejte skico 6 4 A storite naslednje 1 Namestite gumijasto tesnilo na koncu odtočnega spoja ki bo priključen na zunanjo enoto 2 Vs...

Page 89: ...ji enoti Tesnilo Odtočni spoj Tesnilo Skica 6 4 A V hladnih podnebnih območjih V hladnih podnebnih območjih mora biti cev za odvajanje vode postavljena čim bolj navpično da zagotovite hitro odvajanje vode Če se voda odvaja prepočasi lahko zamrzne v cevi in poplavi enoto 3 korak Pritrdite zunanjo enoto Zunanjo enoto lahko pritrdite na tla ali stenski nosilec Dimenzije za namestitev enote V nadaljev...

Page 90: ...310 31 9x22x12 2 549 21 6 325 12 8 700x550x275 27 5x21 6x10 82 450 17 7 260 10 24 770x555x300 30 3x21 85x11 81 487 19 2 298 11 73 800x554x333 31 5x21 8x13 1 514 20 24 340 13 39 845x702x363 33 25x27 63x14 29 540 21 26 350 13 8 900x860x315 35 4x33 85x12 4 590 23 2 333 13 1 945x810x395 37 2x31 9x15 55 640 25 2 405 15 95 946x810x420 37 21x31 9x16 53 673 26 5 403 15 87 946x810x410 37 21x31 9x16 14 673 ...

Page 91: ...ikratno težo teže enote 1 Označite položaj izvrtin za nosilec na podlagi dimenzij v tabeli z dimenzijami za namestitev enote 2 Vnaprej izvrtajte luknje za raztezne vijake 3 Očistite prah in ostanke stran od izvrtin 4 Namestite podložke in matice na koncih posameznih razteznih vijakov 5 Vstavite raztezne vijake skozi luknje na montažnih nosilcih namestite montažne nosilce in s kladivom zabijte razt...

Page 92: ...iksno ožičenje morate vanj vključiti stikalo ali odklopnik ki zagotavlja izklop napajanja na vseh polih in ima med kontakti razmik vsaj 1 8 palca 3 mm Odobren odklopnik ali stikalo mora uporabljati usposobljen tehnik 7 Enoto priključite samo na ločeno vtičnico odcepnega tokokroga V tisto vtičnico ne priključujte drugih naprav 8 Klimatsko napravo morate ustrezno ozemljiti 9 Vsaka žica mora biti trd...

Page 93: ...ščami za snemanje izolacije kablov odstranite gumijasti ovoj z obeh koncev kabla da razkrijete približno 40 mm 1 57 palca žic v kablu b Odstranite izolacijo s koncev žic c S kleščami za stiskanje žic stisnite ušesa v obliki črke U na konce žic Bodite pozorni na žice pod napetostjo Med stiskanjem žic morate jasno razlikovati med žico pod napetostjo L in drugimi žicami A Opozorilo Vsoožičenjemorabit...

Page 94: ...5 Potem ko preverite ali so vse povezave trdne z žicami naredite zanko da preprečite da bi v terminal tekla deževnica 6 Pritrdite kabel na enoto s kabelsko spojko Kabelsko spojko trdno privijte 7 Izolirajte neuporabljene žice z električnim trakom iz PVC Razporedite jih tako da se ne dotikajo nobenih električnih ali kovinskih delov 8 Znova namestite pokrov za žice na stran enote in jo privijte na m...

Page 95: ...lna klimatska naprava s pretvornikom R410A 15 000 25 82 ft 10 33 ft 15 000 in 24 000 30 98 5 ft 20 66 ft 24 000 in 36 000 50 164 ft 25 82 ft 36 000 in 60 000 65 213 ft 30 98 5 ft 7 2 Navodila za povezavo cev hladilnega sredstva 1 korak Odrežite cevi Pri pripravi cevi hladilnega sredstva bodite posebej pozorni da jih ustrezno odrežete in robite S tem boste zagotovili učinkovito delovanje in zmanjša...

Page 96: ...t povezave cevi hladilnega sredstva Zato morajo biti popolnoma odstranjene 1 Cev držite pod kotom navzdol da preprečite da bi vanjo padale iglice 2 Z orodjem za posnemanje robov ali orodjem za raziglevanje odstranite vse iglice z odrezanega dela cevi Cev Obrnjeno navzdol Orodje za posnemanje robov Skica 7 2 3 korak Robljenje koncev cevi Ustrezno robljenje je ključnega pomena za doseganje nepredušn...

Page 97: ...akrena cev Skica 7 3 4 Ko ste pripravljeni na izvajanje robljenja odstranite PVC trak s koncev cevi 5 Spnite model za robljenje na koncu cevi Konec cevi mora segati preko roba modela za robljenje v skladu z dimenzijami prikazanimi v spodnji tabeli Skica 7 4 Podaljšanje cevi preko modela za robljenje Zunanji premer cevi mm A mm Min Maks Ø 6 35 Ø 0 25 0 7 0 0275 1 3 0 05 Ø 9 52 Ø 0 375 1 0 0 04 1 6 ...

Page 98: ...el za robljenje nato pa preglejte konec cevi če so na njem razpoke in če je enakomerno zarobljen 4 korak Priključite cevi Ob priključitvi cevi hladilnega sredstva ne uporabite prevelikega navora in pazite da ne deformirate cevi Najprej morate priključiti nizkotlačno cev nato pa visokotlačno cev Minimalni upogibni polmer Minimalniupogibnipolmerpriupogibanjupovezovalnecevihladilnegasredstvaje10cm Gl...

Page 99: ...m primite matico na cevi enote 4 Ko trdno držite matico na cevi enote z navornim ključem privijte matico z zarobkom v skladu z vrednostmi navora v spodnji tabeli Zahteve glede navora Matico z zarobkom rahlo odvijte nato pa jo znova privijte Skica 7 8 Zahteve glede navora Zunanji premer cevi mm BWPS QSʣWʣUKB tDN PEBUOʣ OBWPS QSʣWʣUKB tN Ø 6 35 Ø 0 25 MC t GU MC t GU Ø 9 52 Ø 0 375 MC t GU MC t GU Ø...

Page 100: ...1 Odvijte pokrov z zapornega ventila na strani zunanje enote Glejte skico 7 9 Pokrov ventila Skica 7 9 2 Odstranite zaščitne pokrove s koncev ventilov 3 Poravnajte konec zarobljene cevi s posameznim ventilom in matico z zarobkom trdno privijte z roko 4 S ključem primite ohišje ventila Ne primite matice ki tesni servisni ventil Glejte skico 7 10 C Glavno ohišje ventila primite s ključem Navor zarad...

Page 101: ... Skica 7 10 5 Ko trdno držite ohišje ventila z navornim ključem privijte matico z zarobkom v skladu z ustreznimi vrednostmi navora 6 Matico z zarobkom rahlo odvijte nato pa jo znova privijte 7 Ponovite korake 3 do 6 za preostalo cev 7 Povezava cevi hladilnega sredstva ...

Page 102: ...ranite morebitne pline ki ne kondenzirajo in vlago Praznjenje mora biti izvedeno ob prvotni namestitvi in ob prestavitvi enote Pred praznjenjem t Prepričajte se da sta visokotlačna in nizkotlačna cev med notranjo in zunanjo enoto pravilno povezani v skladu z razdelkom Povezava cevi hladilnega sredstva v tem priročniku t Prepričajte se da je vsa električna napeljava pravilno povezana 8 2 Navodila z...

Page 103: ...okler na merilniku zmesi ni prikazana vrednost 76 cmHG 105 Pa 6 Zaprite nizkotlačno stran razdelilnega ventila in izklopite vakuumsko črpalko 7 Počakajte 5 minut in se nato prepričajte da se tlak v sistemu ni spremenil 8 Če se je tlak v sistemu spremenil si oglejte razdelek o preverjanju uhajanja plina za informacije o preverjanju uhajanj Če se tlak v sistemu ni spremenil odvijte pokrov z zaporneg...

Page 104: ...ornim ključem C Steblo ventila nežno odprite Pri odpiranju stebel ventilov vrtite šesterokotni ključ dokler ne dosežete omejilca Ventila ne poskušajte odpirati naprej C Opomba glede dodajanja hladilnega sredstva Pri nekaterih sistemih je potrebno dodatno polnjenje odvisno od dolžine cevi Standardna dolžina cevi se razlikuje glede na lokalne predpise V Severni Ameriki je na primer standardna dolžin...

Page 105: ...etvornik R410A dolžina cevi standardna dolžina x 15 g m dolžinacevi standardnadolžina x0 16oZ ft S fiksno frekvenco R410A dolžina cevi standardna dolžina x 20 g m dolžinacevi standardnadolžina x0 21oZ ft Tekočinska stran Ø 9 52 ø 0 375 R22 dolžina cevi standardna dolžina x 60 g m dolžinacevi standardnadolžina x0 64oZ ft Pretvornik R410A dolžina cevi standardna dolžina x 30 g m dolžinacevi standard...

Page 106: ...apravo za preizkus ozemljitvenega upora Ozemljitveni upor mora biti manjši kot 4 Opomba To morda ni zahtevano za nekatere lokacije v ZDA Med preskusom delovanja Preverjanje električnega uhajanja Med preskusom delovanja s senzorjem napetosti in multimetrom izvedite temeljito preverjanje električnega uhajanja Če je zaznano električno uhajanje nemudoma izklopite enoto in pokličite licenciranega elekt...

Page 107: ...in z milom in vodo Z mehko ščetko nanesite milnico ali tekoči detergent na vse priključne točke cevi na notranji in zunanji enoti Če se pojavijo mehurčki to pomeni uhajanje Način z detektorjem uhajanja V primeru uporabe detektorja uhajanja si oglejte navodila za uporabo naprave za navodila o pravilni uporabi Po preverjanju uhajanja plina Ko ste potrdili da na vseh priključnih točkah cevi NI zaznat...

Page 108: ...da vklopite enoto 3 Pritisnite gumb MODE Način za pomikanje po naslednjih funkcijah eno po eno t COOL Hlajenje izberite najnižjo možno temperaturo t HEAT Ogrevanje izberite najvišjo možno temperaturo 4 Vsaka funkcija naj deluje 5 minut pri čemer opravite naslednja preverjanja Seznam preverjanj ki jih opravite Uspešno neuspešno Ni električnega uhajanja Enota je pravilno ozemljena Vsi električni pri...

Page 109: ...to z daljinskim upravljalnikom preklopite nazaj na običajno delovno temperaturo b Notranje povezave cevi hladilnega sredstva ki ste jih med postopkom namestitve notranje enote pustili odkrite ovijte z izolacijskim trakom Če je temperatura okolice nižja od 17 C 63 F Če je temperatura okolice nižja od 17 C z daljinskim upravljalnikom ne morete vklopiti funkcije COOL Hlajenje V tem primeru lahko funk...

Page 110: ...110 120 SI ne Ob nakupu nove naprave bo prodajalec brezplačno prevzel staro napravo C 11 ...

Page 111: ...me in recikliranje naj izvajajo osebe ki imajo pripadajoča potrdila Če ima sistem nameščen sistem za zaznavanje uhajanja izvajajte preverjanje uhajanja vsaj vsakih 12 mesecev da se prepričate da sistem pravilno deluje V primeru izvajanja preverjanja uhajanja zabeležite cikel preverjanja ter določite in shranite zapise o preverjanju uhajanja C Opomba Preverjanje uhajanja ni potrebno za hermetično z...

Page 112: ...5 Prisotnost gasilnega aparata Če bodo dela izvajana na opremi s hladilnim sredstvom ali katerih koli povezanih delih mora biti na dosegu roke pripravljena ustrezna gasilna oprema V bližini polnilnega območja naj bo pripravljen gasilni aparat s suhim prahom ali gasilni aparat s CO2 6 Brez virov vžiga Nobena oseba ki izvaja delo v zvezi s hladilnim sistemom ki vključuje izpostavljanje katerih koli ...

Page 113: ... ogrozila varnost ne smete priključiti električnega napajanja na tokokrog dokler napake ne odpravite Če napake ne morete takoj odpraviti vendar pa potrebujete delovanje naprave morate uporabiti ustrezno začasno rešitev To morate sporočiti lastniku opreme tako da so o tem obveščene vse udeležene osebe Začetni varnostni pregledi vključujejo sledeče t preverjanje ali so kondenzatorji izpraznjeni to m...

Page 114: ...13 Zaznavanje vnetljivega hladilnega sredstva V nobenih okoliščinah ne smete pri iskanju ali odkrivanju uhajanja hladilnega sredstva uporabiti potencialnih virov vžiga Ne uporabljajte halogenidnega gorilnika ali nobenega drugega detektorja ki uporablja odprt plamen 14 Način zaznavanja uhajanja Za sisteme ki vsebujejo vnetljivo hladilno sredstvo so sprejemljivi naslednji načini zaznavanja uhajanja ...

Page 115: ...kom brez kisika morate sistem spustiti na atmosferski tlak da omogočite izvajanje dela Ta postopek je skrajno pomemben če boste na ceveh izvajali spajkanje Prepričajte se da izhod za vakuumsko črpalko ni zaprt za vire vžiga in da je na voljo prezračevanje 16 Postopki polnjenja Poleg običajnih postopkov polnjenja morate upoštevati naslednje zahteve t Ob uporabi opreme za polnjenje poskrbite da ne p...

Page 116: ...jenega delovnega tlaka jeklenke niti samo začasno j Ko so jeklenke ustrezno napolnjene in je postopek končan morate jeklenke in opremo takoj odstraniti z lokacije in zapreti vse izolacijske ventile na opremi k Zbranega hladilnega sredstva ne smete polniti v drug hladilni sistem če ni bilo očiščeno in preverjeno 18 Označevanje Opremo morate opremiti z oznako da je bila razgrajena in je iz nje odstr...

Page 117: ... za zbiranje in zlasti ne v jeklenkah t Ob odstranjevanju kompresorjev ali kompresorskih olj se prepričate da je izpraznjeno do sprejemljive ravni da zagotovite da vnetljivo hladilno sredstvo ne ostane v mazivu Postopek izpraznitve morate izvesti pred vrnitvijo kompresorja dobavitelju Za pospešitev tega postopka lahko uporabite samo električno ogrevanje ohišja kompresorja Odstranjevanje olja iz si...

Page 118: ......

Page 119: ......

Page 120: ...www beko com ...

Reviews: