
38 / 172 EN
Split Type Air Conditioner / User Manual
5 Refrigerant piping connection
Torque requirements
Outer Diameter of
Pipe (mm)
Tightening Torque (N•m) Flare dimension(B) (mm)
Flare shape
Ø 6.35 (Ø 0.25”)
18~20 (180~200kgf.cm)
8.4~8.7 (0.33~0.34”)
Ø 9.52 (Ø 0.375”)
32~39 (320~390kgf.cm)
13.2~13.5 (0.52~0.53”)
Ø 12.7 (Ø 0.5”)
49~59 (490~590kgf.cm)
16.2~16.5 (0.64~0.65”)
Ø 16 (Ø 0.63”)
57~71 (570~710kgf.cm)
19.2~19.7 (0.76~0.78”)
Ø 19 (Ø 0.75”)
67~101 (670~1010kgf.cm)
23.2~23.7 (0.91~0.93”)
WARNING!
Excessive force can
break the nut or damage the
refrigerant piping. You must not
exceed torque requirements shown
in the table above.
5.3 Instructions for connecting
piping to outdoor unit
1. Unscrew the cover from the packed valve on the
side of the outdoor unit.
2. Remove protective caps from ends of valves.
3. Align flared pipe end with each valve, and
tighten the flare nut as tightly as possible by
hand.
4. Using a spanner, grip the body of the valve. Do
not grip the nut that seals the service valve.
Valve cover
Valve cover
5. While firmly gripping the body of the valve, use a
torque wrench to tighten the flare nut according
to the correct torque values.
6. Loosen the flaring nut slightly, then tighten
again.
7. Repeat Steps 3 to 6 for the remaining pipe.
A
CAUTION!
Torque from tightening
the flare nut can snap off other
parts of valve.
Summary of Contents for BEHPH 090
Page 2: ...ENGLISH 3 56 ITALIANO 57 114 FRANÇAIS 115 172 CONTENTS V2110002 AB UM ...
Page 172: ...Arçelik A Ş Karaağaç Caddesi No 2 6 34445 Sütlüce İstanbul Türkiye www beko com ...
Page 173: ...User Manual 10M 8505543200 4921 01 EN IT FR Remote Control ...
Page 174: ...ENGLISH 3 19 ITALIANO 20 37 FRANÇAIS 38 56 CONTENTS V2110002 AB RC ...
Page 228: ...Arçelik A Ş Karaağaç Caddesi No 2 6 34445 Sütlüce İstanbul Türkiye www beko com ...