4.  MAINTENANCE

4.1 Fault finding during commissioning
If 

BA614DF-F 

fails 

to 

function 

during

commissioning  the  following  procedure  should  be
followed:

Symptom

Cause

Check:

No Display

Instrument not

correctly

connected or

powered.

9 to 32V between

terminals 1 & 2.

Display shows

‘9.9.9.9.9’ with all

decimal points

flashing; all

bargraph

segments

activated and

bargraph scale

flashing.

Value

over-range

Variable source

Decimal point
configuration.

Display shows

‘-9.9.9.9.9’ with

all decimal points

flashing; no

bargraph

segments

activated and

bargraph scale

flashing.

Value

under-range

Variable source

Decimal point

configuration

Display

alternates

between value

and the word

‘bAd’.  Bargraph

flashes.

Status of fieldbus

variable has a

quality of ‘BAD’

or a fault state is

active.

Display has not

yet received

data.

Variable source

Fieldbus

configuration.

Bargraph scale

flashes.

Variable is

outside the limits

defined for the

bargraph.

Bargraph

configuration.

All display

segments
activated.

Display is

initialising.

This is normal

operation, after a

few seconds the

firmware version
will be displayed

prior to entering

the operational

mode.

4.2  Fault finding after commissioning

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

If  a  BA614DF-F  fails  after  it  has  been  functioning
correctly,  the  table  shown  in  section  4.1  may  help
to identify the cause of the failure.

If  this  procedure  does  not  reveal  the  cause  of  the
fault,  it  is  recommended  that  the  instrument  is
replaced.

4.3  Servicing
We  recommend  that  faulty  BA614DF-F  Fieldbus
Indicators  are  returned  to  BEKA  associates  or  to
our local agent for repair.

4.4 Routine maintenance
The  mechanical  and  electrical  condition  of  the
instrument  should  be  regularly  checked.    Initially
annual  inspections  are  recommended,  but  the
inspection frequency should be adjusted to suit the
environmental conditions.

4.5  Guarantee
Instruments  which  fail  within  the  guarantee  period
should be returned to BEKA associates or our local
agent.  It is helpful if a brief description of the fault
symptoms is provided.

4.6  Customer comments
BEKA  associates  is  always  pleased  to  receive
comments from customers about our products and
services.    All  communications  are  acknowledged
and 

whenever 

possible, 

suggestions 

are

implemented.

Summary of Contents for FOUNDATION BA614DF-F

Page 1: ...Issue 2 23 rd June 2011 BA614DF F FOUNDATION fieldbus Field mounting Fieldbus Indicator Issue 2 ...

Page 2: ...ding during commissioning 4 2 Fault finding after commissioning 4 3 Servicing 4 4 Routine maintenance 4 5 Guarantee 4 6 Customer comments 5 Accessories 5 1 Scale and Tag marking 5 2 Tag plate 5 3 Pipe mounting kits 5 4 Fieldbus Interface Guide CONTENTS The BA614DF F is CE marked to show compliance with the European EMC Directive 89 336 EEC ...

Page 3: ...EM DESIGN The BA614DF F Indicator is powered and communicates via the fieldbus which is connected to non polarised terminals 1 and 2 As shown in Fig 1 the instrument may be connected to any fieldbus segment which can supply the additional 13mA required to power the instrument Fig 1 Fieldbus system 3 INSTALLATION 3 1 Location The BA614DF F Fieldbus Indicator is housed in a robust IP66 glass reinfor...

Page 4: ...stall the required glands conduit fittings or blanking plugs Note The temporary dust seals fitted for transit do not maintain the IP66 protection of the BA614DF F enclosure d Connect the field wiring to the terminals as shown in Fig 3 e Replace the instrument terminal cover and evenly tighten the two A screws Fig 2 BA614DF F installation procedure 3 3 EMC The BA614DF F complies with the requiremen...

Page 5: ...ation after a few seconds the firmware version will be displayed prior to entering the operational mode 4 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA614DF F fails after it has been functioning correctly the table shown in section 4 1 may help to identify the cause of the failure If this procedure does not reveal the cause of the fault it is recommend...

Page 6: ... the instrument enclosure 5 2 Tag plate The BA614DF F can be supplied with a blank or custom laser marked stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9 alphanumeric characters 10mm high or 1 row of 11 alphanumeric characters 7mm high or 2 rows of 18 alphanumeric characters 5mm high 5 3 Pipe mounting kits Two pipe mounting...

Reviews: