5.3.1  Access
Access  to  the  listener  configuration  menu  is
obtained  by  operating  the  P  and  E  buttons
simultaneously.    If  the  BA648CF-P  listener
configuration  menu  is  not  protected  by  an  access
code  the  first  parameter  'SCAn’  will  be  displayed.
If the BA648CF-P is protected by an access code,
‘CodE’ will be displayed first.  Pressing P will allow
the  four  digit  security  code  to  be  entered  digit  by
digit using the 

 or 

 button to adjust the flashing

digit and P to move control to the next digit.  When
the correct code has been entered, pressing E will
cause  the  first  parameter  ‘SCAn’  to  be  displayed.
If  an  incorrect  code  is  entered,  or  no  button  is
pressed  for  ten  seconds,  the  indicator  will
automatically return to the display mode.

Section  5.3.2  contains  a  summary  of  each
configuration  function  including  a  cross  reference
to a more detailed description.

5.3.2 Summary of listener configuration
         functions

   Instrument          Summary
   display               of function

‘SCAn’

Scan fieldbus segment 
Identifies  all  data  sources  on  the
fieldbus segment to which the listener is
connected and enables selected data to
be allocated to one of the eight  listener
inputs in-1 to in-8.
See section 5.4.1

‘LiSt’

List configured input parameters
For  each  of  the  eight  BA648CF-P
listener  inputs,  in-1  to  in-8  shows  if  the
input  is  enabled;  Source  Address;
Destination  Address  and  the  Index
which 

have 

been 

allocated.

Parameters  can  not  be  changed  from
within this function.
See section 5.4.2

‘Edit’

Enter addresses and display
parameters
Sub-menu which allows known fieldbus
device addresses to  be  entered  and  all
display parameters adjusted for each of
the eight fieldbus listener inputs.
See section 5.4.3

 

‘Enb’

Enable selected input
Enables  each  of  the  eight
listener  inputs  in-1  to  in-8  to
be 

enabled 

or 

disabled

without 

affecting 

any

parameters.
See section 5.4.4

‘SrC’

Enter Source Address
Allows  hexadecimal  fieldbus
device  source  address  for
each  of  the  eight  listener
inputs  in-1  to  in-8  to  be
entered.
See section 5.4.5

‘dSt’

Enter Destination Address
Allows  hexadecimal  fieldbus
device  destination  address
for each listener input in-1 to
in-8 to be entered.
See section 5.4.6

‘ind’

Enter Index
Allows  hexadecimal  index
for  specified fieldbus source
address  to  be  entered  for
each  listener  input    in-1  to
in-8.
See section 5.4.7

‘dP’

Decimal point position
Defines position of displayed
decimal 

point 

for 

each

listener input in-1 to in-8.
See section 5.4.8

‘bAr’

Configuration of bargraph
Defines 

the 

bargraphs

justification  and  the  digital
display 

at 

which 

the

bargraph  is  zero  and  full
scale  for  each  listener  input
in-1 to in-8.
See section 5.4.9

‘SCALE’ Scale numeric display

Applies  zero  offset  and
scale  factor  to  the  numeric
display  for  each  listener
input in-1 to in-8.
See section 5.4.10

‘CodE’

Access code for listener
configuration menu
Enters  a  four  digit  security  access
code  for  configuration  menu.    Default
code 0000 disables this function.
See section 5.4.11

tYPE’

Change from listener to node
Enables 

the 

instrument 

to 

be

conditioned  as a fieldbus listener or  a
fieldbus node.
See section 5.4.12

‘rESEt’

Reset to listener factory defaults
Returns  the  BA648CF-P  listener  to
factory defaults.
See section 5.4.13

Summary of Contents for BA648CF-P

Page 1: ...Issue 2 23 rd June 2011 BA648CF P PROFIBUS PA Panel mounting 8 variable Fieldbus Indicator Issue 2...

Page 2: ...parameters 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configura...

Page 3: ...n label There is an alternative version of the fieldbus display order code BA648CF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configurat...

Page 4: ...panel mounting clips Fig 2 BA648CF P dimensions 4 2 Installation Procedure a Insert the BA648CF P into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite...

Page 5: ...d digit flashing which may be changed by operating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digit...

Page 6: ...dresses of the data sources to be displayed by the BA648CF P listener are not known In the SCAn function pressing the P button causes the BA648CF P listener to search the fieldbus segment to which it...

Page 7: ...7...

Page 8: ...eters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input...

Page 9: ...ource address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a l...

Page 10: ...mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph dis...

Page 11: ...evised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus nod...

Page 12: ...ation after a few seconds the firmware version will be displayed prior to entering the operational mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA648...

Page 13: ...a scale for the horizontal bargraph 7 2 Tag number The BA648CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 7 3 BEKA PROFIBUS PA Display Fieldbus...

Reviews: