5.4.5  Enter source address    ‘SrC’
This  function  allows  a  known  fieldbus  device
source address to be  entered  and  allocated to the
listener input selected in the edit function. To enter
the  function  press  P  which  will  reveal  the  existing
two  digit  hexadecimal  address  with  one  digit
flashing which may be changed by operating the 

or 

 button.   When set as required operating the

P button will transfer control to the second digit that
may  be  adjusted  in  the  same  way.    When  both
digits  are  set  as  required  operating  the  E  button
will  enter  the  selection  and  return  to  the  ‘SrC’
prompt in the edit sub-menu.

5.4.6  Enter destination address    ‘dSt’
This  function  allows  a  known  fieldbus  device
destination address to be entered and allocated to
the  listener  input  selected  in  the  Edit  function.  To
enter  the  function  press  P  which  will  reveal  the
existing  two  digit  hexadecimal  address  with  one
digit  flashing  which  may  be  changed  by  operating
the 

 or 

 button. When set as required operating

the P button will transfer control to the second digit
that may be adjusted in the same way.  When both
digits  are  set  as  required  operating  the  E  button
will  enter  the  selection  and  return  to  the  ‘dSt’
prompt in the edit sub-menu.

5.4.7  Enter Index    ‘ind’
Index  defines  the  location  of  the  required  process
variable in the data string.  The ‘ind’ function allows
a  known  Index  for  the  selected  fieldbus  Source
Address  to  be  entered  and  allocated  to  the
BA648CF-P  listener  input  selected  in  the  Edit
function. The data location is manufacturer specific
and  can  not  be  automatically  determined;  the
device 

documentation 

should 

therefore 

be

consulted.  To enter the function press P which will
reveal the existing two digit hexadecimal Index with
one  digit  flashing  which  may  be  changed  by
operating the 

 or 

 button. When set as required

operating  the  P  button  will  transfer  control  to  the
second digit that may be adjusted in the same way.
When both digits are set as required operating the
E  button  will  enter  the  selection  and  return  to  the
‘ind’ prompt in the edit sub-menu.

5.4.8  Decimal point position    ‘dP’
This  defines  the  position  the  decimal  point  in  the
numeric  display.    To  enter  the  function  press  P
which  will  reveal  the  existing  decimal  point
position.    Operating  the 

  or 

  button  will  move

the decimal point to the required position, omit it, or
activate  all  the  decimal  points  which  automatically
provides  maximum  resolution  in  the  display  mode
irrespective of the numeric value.
When  positioned  as  required,  operating  the  E
button will enter the selection and return to the ‘dP’
prompt in the edit sub-menu.

5.4.9 Configuration of bargraph display   ‘bAr’
This  function  contains  three  sub-functions  that
enable  the  bargraph,  justify  its  position  and  define
the  relationship  between  the  bargraph  and  the
instrument’s numeric display.

Sub-function  ‘b.tYPE’  enables  the  bargraph  to  be
left,  centre  or  right  justified,  or  to  be  turned  off.
Sub-functions  ‘bArLo’  and  ‘bArhi’  define  the
listener’s  numeric  display  at  which  the  bargraph
starts and is at full scale.
The ‘bAr’ function may be selected from within the
edit  sub-menu  by  operating  the 

  or 

  button.

To enter the function press P which will display the
‘b.tYPE’  sub-function,  pressing  P  again  will  reveal
the  existing  bargraph  justification.    The 

  or 

button will scroll through the four options, when the
required  justification  is  displayed,  pressing  E  will
enter  the  selection  and  return  the  display  to  the
‘b.tYPE’  prompt  in  the  edit  sub-menu  from  which
‘bArLo’ may be selected using the 

 or 

 button.

‘bArLo’  defines  the  listener’s  numeric  display  at
which  the  bargraph  starts,  to  enter  the  function
press P which will reveal the existing setting.   The
display may  be changed using the 

  or 

  button

to  adjust  the  flashing  digit  and  the  P  button  to
move control to  the  next  digit.   When  the  required
starting  display  has  been  selected,  press  E  to
return  to  the  ‘bArLo’  prompt  in  the  edit  sub-menu
from which the ‘bArHi’ function may be selected.

‘bArHi’  defines  the  listener’s  numeric  display  at
which  the  bargraph  is  full  scale,  to  enter  the
function  press  P  which  will  reveal  the  existing
setting.   The display may be changed using the 

or 

  button  to  adjust  the  flashing  digit  and  the  P

button to move control to the next digit.  When the
required  display  has  been  selected,  press  E  twice
to  enter  the  new  values  and  return  to  the  ‘bAr’
prompt in the edit sub-menu.

Note:  If  the  ‘dP’  function  has  been  set  to  provide
automatic  maximum  resolution  irrespective  of  the
displayed  value,  it  may  be  necessary  to  manually
position  the  decimal  point  before  adjusting  ‘bArLo’
or  ‘bArHi’.      This  can  be  achieved  by  repeatedly
operating  the  P  button  until  the  activated  decimal
point  flashes,  the  decimal  point  can  then  be
positioned  using  either  the 

  or 

  button.

Pressing  the  P  button  again  will  return  control  to
one of the digits.

5.4.10  Scale numeric display    ‘SCALE’
A  scaling  factor  ‘Gain’  and  an  offset  ‘oFFSt’  may
be  applied  to  the  fieldbus  process  variable  using
this  function,  thus  allowing  the  listener  to  display
the fieldbus process variable in alternative units.

Summary of Contents for BA648CF-P

Page 1: ...Issue 2 23 rd June 2011 BA648CF P PROFIBUS PA Panel mounting 8 variable Fieldbus Indicator Issue 2...

Page 2: ...parameters 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configura...

Page 3: ...n label There is an alternative version of the fieldbus display order code BA648CF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configurat...

Page 4: ...panel mounting clips Fig 2 BA648CF P dimensions 4 2 Installation Procedure a Insert the BA648CF P into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite...

Page 5: ...d digit flashing which may be changed by operating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digit...

Page 6: ...dresses of the data sources to be displayed by the BA648CF P listener are not known In the SCAn function pressing the P button causes the BA648CF P listener to search the fieldbus segment to which it...

Page 7: ...7...

Page 8: ...eters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input...

Page 9: ...ource address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a l...

Page 10: ...mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph dis...

Page 11: ...evised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus nod...

Page 12: ...ation after a few seconds the firmware version will be displayed prior to entering the operational mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA648...

Page 13: ...a scale for the horizontal bargraph 7 2 Tag number The BA648CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 7 3 BEKA PROFIBUS PA Display Fieldbus...

Reviews: