6.  MAINTENANCE

6.1 Fault finding during commissioning
If  a  BA648CF-F  indicator  fails  to  function  during
commissioning  the  following  procedure  should  be
followed:

Symptom

Cause

Check:

No Display

Instrument not

correctly

connected or

powered.

9 to 32V between

terminals 1 & 2.

When configured

as a listener

displays

‘no ConF’

No inputs are

enabled.

Configuration of

each input.

When configured

as a listerer

displays

‘no dAtA’

No data being

received with the

current

configuration.

Device Address

and Variable

Identities are

correct.

That data has

DS-65 format.

Display shows

‘9.9.9.9.9’ with all

decimal points

flashing; all

bargraph

segments

activated and

bargraph scale

flashing.

Value

over-range

Configuration.

and

decimal point

position.

Display shows

‘-9.9.9.9.9’ with

all decimal points

flashing; no

bargraph

segments

activated and

bargraph scale

flashing.

Value

under-range

Configuration

And

decimal point

position.

Display

alternates

between value

and the word

‘bAd’.  Bargraph

flashes.

Status of fieldbus

variable has a

quality of ‘BAD’

or a fault state is

active.

Fieldbus

configuration.

Bargraph scale

flashes.

Process variable

is outside the

limits defined for

the bargraph.

Bargraph

configuration.

All display

segments
activated.

Display is

initialising.

This is normal

operation, after a

few seconds the

model number

followed by the

firmware version
will be displayed

prior to entering

the display

mode.

6.2  Fault finding after commissioning

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

If  a  BA648CF-F  fails  after  it  has  been  functioning
correctly,  the  table  shown  in  section  6.1  may  help
to identify the cause of the failure.

If  this  procedure  does  not  reveal  the  cause  of  the
fault,  it  is  recommended  that  the  instrument  is
replaced.

6.3  Servicing
We  recommend  that  faulty  BA648CF-F  Fieldbus
indicators  are  returned  to  BEKA  associates  or  to
our local agent for repair.

6.4 Routine maintenance
The  mechanical  and  electrical  condition  of  the
instrument  should  be  regularly  checked.    Initially
annual  inspections  are  recommended,  but  the
inspection frequency should be adjusted to suit the
environmental conditions.

6.5  Guarantee
Instruments  which  fail  within  the  guarantee  period
should be returned to BEKA associates or our local
agent.  It is helpful if a brief description of the fault
symptoms is provided.

6.6  Customer comments
BEKA  associates  is  always  pleased  to  receive
comments from customers about our products and
services.    All  communications  are  acknowledged
and 

whenever 

possible, 

suggestions 

are

implemented.

Summary of Contents for BA648CF-F

Page 1: ...Issue 3 23 rd June 2011 BA648CF F FOUNDATION fieldbus Panel mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...ss display parameters 5 3 6 Enable selected input 5 3 7 Enter Device Address 5 3 8 Enter Variable Identity 5 3 9 Decimal point position 5 3 10 Configuration of bargraph 5 3 11 Scale numeric display 5...

Page 3: ...protocol is shown on the rear of the instrument The F order code suffix also indicates the protocol but is not shown on the instrument idendification label There is an alternative version of the fiel...

Page 4: ...r panel mounting clips Fig 2 BA648CF F dimensions 4 2 Installation Procedure a Insert the BA648CF F into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite...

Page 5: ...nditioned as a fieldbus listener see section 5 3 13 to change it to a fieldbus node 5 2 1 Reset the indicator to node factory defaults rESEt The BA648CF F may be reset to the factory defaults that are...

Page 6: ...the P button causes the BA648CF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 7: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 5 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 8: ...8...

Page 9: ...splayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be selec...

Page 10: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 11: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 12: ...bargraph Bargraph configuration All display segments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed...

Page 13: ...und the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bargraph 7 2 Tag number The BA648CF F c...

Reviews: